![Danfoss CCR2 Installation Manual Download Page 12](http://html1.mh-extra.com/html/danfoss/ccr2/ccr2_installation-manual_3778522012.webp)
12
Installation Guide
CCR2
SMT/SI
VI.D1.E2.1R
Heating Solutions
No
LCD Display
INSTALL MENu - FuNCTION DESCRIPTION
65
CCR2 is
… … .
Status of CCR2:
Register
- functions only as temperature registration
Reg+Dis
- functions as disinfection control with temperature registration
Factory setting: Reg+Dis
66
Reset
… … .
Reset to factory settings
yes
- return to factory settings
No
– keep adjusted settings
Note:
To complete reset procedure turn CCR3 off and back on.
67
Ecs?
+ YES
Exit windows from Install Menu. Enter “+” to close setting or basic menu will close automatically after
4 minutes
10. SCH setting: weekly schedule programme menu settings (code 760)
From ACCESS CODE menu enter code: 760
(procedure in chapter 7). The Schedule menu is
displayed as in the table below.
The arrow keys “
▲
/
▼
” move the menu windows,
the “+/ - “ keys change the values in the window
selected by the arrows.
To exit the setting menu, press the up arrow
key after changing the last setting. The settings
menu is closed automatically after 4 minutes of
inactivity.
Entrance to the Menu Settings discontinue
disinfection process and alarm signal.
No
LCD Display
PRG - SCHEDuLE PROGRAMME MENu - FuNCTION DESCRIPTION
68
Schedule
Menu
Information about menu: Schedule
69
P1 Start
10
: 20
Programme P1 starts time “hour” for the weekly schedule. The same settings apply for programmes
P2 … P7.
70
P1 Start
10:
20
Programme P1 starts time “minute” for the weekly schedule. The same settings apply for programmes
P2 … P7.
71
P1 Stop
10
: 20
Programme P1 stops time “hour” for the weekly schedule. The same settings apply for programmes
P2 … P7.
72
P1 Stop
10:
20
Programme P1 stops time “minute” for the weekly schedule. The same settings apply for programmes
P2 … P7.
73
P1 Activ
A12 - - - 67
Sets the activity of the entire P1 programme and its activities for individual days of the week.
The arrow keys”
▼
/
▲
” navigate the cursor through the digits. The “+/ - “ keys change the digit values.
Figures 1 … 7 represent days of the week:
1 – Monday, 2 – Tuesday … 7 – Sunday.
The first setting to the left can be A or N:
A
– Programme P1 is active - subsequent settings are read,
N
– Programme P1 is entirely deactivated - subsequent settings 1 … 7 are dismissed, and the
programme is not started.
The second left setting:
1
– Programme P1 is activated on Monday.
“
-
“ – Programme P1 is not activated on Monday.
The third left setting:
2
– Programme P1 is activated on Tuesday.
“
-
” – Programme P1 is not activated on Tuesday.
The fourth left setting:
3
– Programme P1 is activated on Wednesday.
“
-
“ – Programme P1 is not activated on Wednesday.
The fifth left setting:
4
– Programme P1 is activated on Thursday.
“
-
“ – Programme P1 is not activated on Thursday.
The sixth left setting:
5
– Programme P1 is activated on Friday.
“
-
“ – Programme P1 is not activated on Friday.
The seventh left setting:
6
– Programme P1 is activated on Saturday.
“
-
“ – Programme P1 is not activated on Saturday.
The eighth left setting:
7
– Programme P1 is activated on Sunday.
“
-
“ – Programme P1 is not activated on Sunday.
The same Activity settings apply for programmes P2..P7.
74
Ecs?
+ YES
Exit windows from Install Menu. Enter “+” to close setting or basic menu will close automatically after
4 minutes