User Guide | Danfoss troubleshooting guide for supermarket electronics

8 | BC337731384771en-000301

© Danfoss | Climate Solutions | 2022.02

6. Storeview

7. AK-SC 255

Unable to Connect to Site that Works in Web Browser 

1.  Delete site from Storeview, re-add.

Battery Replacement/Low Battery Alarm

1.  Do not power down controller
2.  Remove old battery. Be careful not to bend the battery clip any more than necessary; battery clip 

can break

3.  Insert new battery

255 Alarm Dialout Issues

1.  Verify modem has power
2.  Reset modem, 255
3.  Verify info on Alarm Routing screen
4.  Verify phoneline is active (inbound call from phone)
5.  Verify phone # is correct (outbound call from corded phone on modem phoneline)
6.  Verify modem config screen

‘Press 9 to Clear Database’ Message

1.  Database must be cleared, no options to bypass.
2.  Press 9 to clear
3.  Reload database after clear is complete

‘Alarm’ Flashing on 255, LED Red but no active/acknowledged alarms

1.  Go to Configuration 

 Alarms 

 Service

a.  To reset the Alarm! Message and LED, try enabling a one-time Test Alarm 
b.  If this does not work, use ‘Clear Alarm Log’ option

IO Offline

1.  Verify Power to modules, Complete rescan
2.  Verify ‘Channel Lonworks’ enabled on Network Nodes screen

a.  If not, update and rescan afterwards

3.  Verify EOL resistor in place at end of loop

a.  120 Ω resistor or term switch in On position at last comm module
b.  If term switches exist on modules in middle of loop, need to be in Off position

4.  Verify comm module addresses via rotary switches
5.  Isolate loop in sections, rescan

a.  Identifies where comm problem may be introduced

6.  If module is still offline, remove power to communication module for 15 seconds, repower.  Do 

Complete Rescan again.

Missing License

1.  Please contact Danfoss Tech Support and supply the MAC address. Tech support will help reinsert 

the license

2.  The controller will still operate regularly, but you won’t be able to make any changes to 

configuration

a.  In need of immediate assistance, you may load in the back-up/old database to bring the license 

back

3.  Verify CPU card is inserted correctly. Reset the controller

Black Display Screen

1.  Verify ribbon cable between the screen and CPU board

a.  If not loose or disconnected, the unit will need to be replaced

White Display Screen

1.  Verify that ribbon cable from the baseboard is connected at both ends (Connector at the display 

may have worked loose)

Summary of Contents for AK-SM 800A

Page 1: ...User Guide Danfoss troubleshooting guide for supermarket electronics www danfoss com...

Page 2: ...C 550A to AK SM 800 7 Dual Temp Setup 7 4 AK CC 750 7 Replacing AK CC 750 7 5 AK XM Modules 7 AKS Temp Sensor not Reading on IO Module 7 AK XM 103A module not coming online 7 Relay will not respond to...

Page 3: ...should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable and rescan afterwards 3 Verify term resistor switch position at AK SM 800 is correct a If 1 loop from pl...

Page 4: ...4 Replace AK SM 800 IO Offline 1 Verify Power to modules Complete rescan a Power supply to comm modules should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable...

Page 5: ...ue address 3 Verify connection from AK SM 800 to switch and switch to network a Could be the issue with the cable b Power cycle network switch router or cell modem 4 Reset AK SM 800 a Make sure to res...

Page 6: ...dc c Measure voltage across terminals 31 32 Should be in range of 0 5 4 5Vdc d Verify transducer type Label of transducer should say AKS32R HFC or AKS 2050 CO2 S3 Error E25 1 If no return air s3 senso...

Page 7: ...e or loose connection between module and probe b If reading closed likely a short in cable between module and probe c If reading expected resistance compare to temp ohm chart for PT1000 move sensor to...

Page 8: ...ion IO Offline 1 Verify Power to modules Complete rescan 2 Verify Channel Lonworks enabled on Network Nodes screen a If not update and rescan afterwards 3 Verify EOL resistor in place at end of loop a...

Page 9: ...oftware reinstall AKA65 software outside of Program Files or Program Files x86 folder 3 Obtain generic copy of aka65 ini file place in C Windows folder replace existing Unable to locate compatible Win...

Page 10: ...Danfoss Climate Solutions 2022 02 BC337731384771en 000301 10...

Reviews: