User Guide | Danfoss troubleshooting guide for supermarket electronics

4 | BC337731384771en-000301

© Danfoss | Climate Solutions | 2022.02

Compressors not coming on with high suction

1.  Check status screen of rack to see if any warnings are listed (i.e. phase loss, high discharge pressure, 

oil fail, etc)

a.  For high discharge pressure, check settings tab to confirm cutin/cutout values for “Disch 

pressure safety” are appropriate (cutout should be higher than cutin)

b.  For phase loss, oil fail, see if the device sending Danfoss a signal is tripped (i.e. phase loss 

monitor, oil sensor). If so, that device needs to be investigated. 

c.  If the device is not tripped, check wiring and polarity in program (under Addresses on-off inputs 

tab) to ensure proper config (i.e open/closed/voltage/no voltage).

2.  If no warnings are listed, check staging pattern of controller (auto/manual) under Settings

a.  If set to manual, # of steps should be greater than 0, and individual steps should show 

compressors selected with capacity increases from one step to the next.

b.  Reset the controller after reviewing this section (even if no changes made). Staging pattern 

changes do not take effect until after a reset. 

3.  Check Address section to ensure relay address for compressor still exists, polarity correct.
4.  Under status screen for rack, select “Service” and confirm no manual overrides on compressors

Keypad not Responsive

1.  Reset unit
2.  Remove keypad from AK-SM 800 and reconnect
3.  Ensure excessive wiring does not exist behind keypad

a.  If so, shorten cables where possible

4.  Replace AK-SM 800

IO Offline

1.  Verify Power to modules, Complete rescan

a.  Power supply to comm modules should be 24 V AC/DC

2.  Verify ‘Channel Lonworks’ enabled on Network Nodes screen

a.  If not, enable and rescan afterwards

3.  Verify term resistor switch position at AK-SM 800 is correct

a.  If 1 loop from plug, switch = ‘On’ position
b.  If 2 loops from plug, switch = ‘Off’ position

4.  Verify EOL resistor in place at end of loop(s)

a.  120 Ω resistor or term switch in On position 
b.  If term switches exist on modules in middle of loop, need to be in Off position

5.  Verify comm module addresses via rotary switches
6.  Verify that there are no hairline shorts on the comm loop terminal
7.  Verify comm loop is run as point-to-point daisy chain (no branches, etc)
8.  Verify comm cable type 

a.  EIA RS 485 (max. 4000’) for Modbus and LON RS485 devices
b.  120 Ω impedance, 42– 75.5 pF/m capacitance, typically 22-24 AWG

9.  Isolate loop in sections, rescan

a.  Identifies where comm problem may be introduced

Database will not load via USB

1.  Verify filename ends in ‘.s55’ extension
2.  Verify filename is 8 characters or less, no special characters 
3.  Verify file is on root drive of USB, not subfolder
4.  Verify controller firmware version equal or higher than database version 

a.  Database version can be verified in RMT
b.  If database is 255 database being converted, must be v2.191 or higher.

5.  Reset AK-SM 800 and attempt to load again

Case Controller ‘Mismatch’ Issue

1.  Go to Network Nodes 

 Scan Status 

 Controllers

a.  Locate address in list
b.  Note controller version, part #, type shown

2.  Go to Configuration 

 Control 

 Refrigeration 

 Circuits 

 Type

a.  Confirm type matches info from #1 above
b.  If not, change selection in list to proper choice
c.  Rescan after updating

2. AK-SM 800

Summary of Contents for AK-SM 800A

Page 1: ...User Guide Danfoss troubleshooting guide for supermarket electronics www danfoss com...

Page 2: ...C 550A to AK SM 800 7 Dual Temp Setup 7 4 AK CC 750 7 Replacing AK CC 750 7 5 AK XM Modules 7 AKS Temp Sensor not Reading on IO Module 7 AK XM 103A module not coming online 7 Relay will not respond to...

Page 3: ...should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable and rescan afterwards 3 Verify term resistor switch position at AK SM 800 is correct a If 1 loop from pl...

Page 4: ...4 Replace AK SM 800 IO Offline 1 Verify Power to modules Complete rescan a Power supply to comm modules should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable...

Page 5: ...ue address 3 Verify connection from AK SM 800 to switch and switch to network a Could be the issue with the cable b Power cycle network switch router or cell modem 4 Reset AK SM 800 a Make sure to res...

Page 6: ...dc c Measure voltage across terminals 31 32 Should be in range of 0 5 4 5Vdc d Verify transducer type Label of transducer should say AKS32R HFC or AKS 2050 CO2 S3 Error E25 1 If no return air s3 senso...

Page 7: ...e or loose connection between module and probe b If reading closed likely a short in cable between module and probe c If reading expected resistance compare to temp ohm chart for PT1000 move sensor to...

Page 8: ...ion IO Offline 1 Verify Power to modules Complete rescan 2 Verify Channel Lonworks enabled on Network Nodes screen a If not update and rescan afterwards 3 Verify EOL resistor in place at end of loop a...

Page 9: ...oftware reinstall AKA65 software outside of Program Files or Program Files x86 folder 3 Obtain generic copy of aka65 ini file place in C Windows folder replace existing Unable to locate compatible Win...

Page 10: ...Danfoss Climate Solutions 2022 02 BC337731384771en 000301 10...

Reviews: