Danfoss AK-SC255 Installation Manual Download Page 5

2.0 Programming AK-SC255 Database

One of the central tasks involved in retro-fitting the Com-Trol front end unit is the configuration of the AK-SC255 database that 

allows the Danfoss controller to fully replace the Com-Trol unit(s).  Review the following section for guidance in creating the 

AK-SC255 database, which replaces the Com-Trol 4k2/4K2e systems.

     Using the Com-trol 

EZCom

 software, pull back and save the existing Com-Trol 4K or 4K2e controllers to be converted to  

  the Danfoss AK-SC255

     The Com-Trol files can be viewed with the Com-Trol 

EzSet

 software utility

     Using the Danfoss AKA65 software service tool, create a blank database by using the simulate function.  Ensure the correct 

version of simulated database is created to avoid compatibility issues on site (i.e. use the same version for the database pro-

gramming that will be installed in the physical AK-SC255 unit)  

 

3a

 Start configuration of the AK-SC255 database by setting the Legacy I/O type to COMTL (found in the Store Info / 

  Preferences)  

Figure 4

 

3b

 Configure the Modbus channel under the Communications / I/O Network / Rescan Channels page.  If Danfoss AK I/O  

  boards are also to be used, ensure the channel ‘LonWorks’ is checked also.  

Figure 5

 

3c

 When assigning Com-Trol board points, first press F4 to convert the board-point type to the Com-Trol format.  

Figure 6

         Relay configuration (table 1)

     

      Sensor offsets used  in Com-Trol controllers should be transferred to the AKA65 database

Com-Trol format (EzSet)

Danfoss format (AKA65)

Relay

Normal

N-Closed

Invert

N-Open

Digital Input

Normal

Open

Invert

Closed

Table 1

1

2

3

4

5

Preferences screen

(set Legacy I/O to COMTROL)

Sensor Configure screen

(select from drop down type list)

Rescan screen

(check Modbus)

Figure 4

Figure 5

Figure 6

new Com-Trol 

sensor selection