1.0 Intended application (Hardware / Software)

The following important points define the intended application scope for a Com-Trol (local bus) retro-fit installation.  Please 

read these fundamental requirements before continuing. 

•  One Com-Trol 4K/4K2e should be replaced with one Danfoss AK-SC255 unit

•  The Danfoss AK-SC255 RS-485 (Modbus) port is used for communication to the Com-Trol I/O boards (figure 1).  

Host 

      communication to other AK -SC255 and/or AK-SC255 Loggers must be done via the Ethernet port

.

•  Only one local bus loop can be connected to the AK-SC255 (figure 1) - No star wiring configurations allowed

•  Valid local bus termination and wiring rules must be applied and maintained (see figure 3 below)

•  Existing system capacity for number of Com-Trol I/O boards (defined by Com-Trol documentation) must be maintained

•  AK-SC255 software version R2.151 and above must be used in order to provide Com-Trol support

•  The AK-SC255 being used in the application must have a valid Com-Trol license installed.   If a license is required contact

      Danfoss Customer service on 410-931-8714 with the AK-SC255 MAC address