Operating

Function

Press

View set point

 

Change set point

 + 

 / 

"Change" menu ("ro"............."tEu")

 + 

 (4 seconds)

Return

 + 

 (4 seconds)

"Set-up" menu ("AC" ............. "reL" )

 + 

 + 

 (4 seconds)

Return

 + 

 (4 seconds)

List of Level 1 variables (User Level)

Variables Explanation

Default

r0

Differential 

above main SETPOINT

0.2 - 10K

2K

d0

Defrost interval (hours)

0 - 24 hours

4 hours

d2

End-of-defrost setpoint.

Defrosting stops when the defrost sensor exceeds 
the value, 

-35 - 45 °C

15 °C

d3

Max defrost duration

1 - 240 min

25 min

d7

Drip duration

At the end of defrost, the compressor and fans remain 

at standstill for time d7 and the defrost LED on the 

front panel flashes.

0 - 10 min

0 min

F5

Fan pause 

after defrost (minutes)

Allows fans to be kept at standstill for time F5 after 

dripping. This time begins at the end of dripping. If no 

dripping has been set, the fan pause starts directly at 

the end of defrost.

0 - 10 min

0 min

A1

Maximum temperature alarm

Allows user to define a maximum temperature for 

the room being refrigerated. Above value A2 an 

alarm trips: the alarm LED flashes, the displayed 

temperature flashes and the buzzer sounds to 

indicate the problem.

-45 °C

A2

Maximum temperature alarm

Allows user to define a maximum temperature for 

the room being refrigerated. Above value A2 an 

alarm trips: the alarm LED flashes, the displayed 

temperature flashes and the buzzer sounds to 

indicate the problem.

+45 °C

tEu

Evaporator sensor temperature display

(displays nothing if 

dE =1)

(read only)

-

List of Level 2 variables (Installer Level)

AC 

Door switch status

0  =  normally open,  1 = normally closed

0

F3

Fan status with compressor off

0  =  fans run continuously

1  =  fans only run when compressor is working

1

F4

Fan pause during defrost

0  =  fans run during defrost

1  =  fans do not run during defrost

1

dE   

Sensor presence

0  =  evaporator sensor present

1  =  no evaporator sensor

0

d1 

Defrost type

1=hot gas, 0=electric

0

Ad

Not to be used

Ald

Minimum and maximum temperature alarm 

1...240 min

120 min

C1

Minimum time between shutdown and 

subsequent switching on of the compressor. 

0...15 min

0 min

CAL

Correction of sensor signal

-10...+10

0

Pc

Compressor protection contact status

0=NO, 1=NC

0 = NO

doC

Compressor safety time for door switch

0...5 minutes

0

tdo

Restart time, if the door remains open

0... 240 min. (0=no function)

0

Fst

FAN shutdown TEMPERATURE

-45...+45 °C

+45 °C

Fd

Fan differential below Fst

0...+10K

2K

LSE

Min. limit of set point setting

-45...HSE

-45°C

HSE

Max. limit of set point setting

45... LSE

45°C

tA

NO – NC 

alarm relay switching

0  =  activates when alarm is on 

1  =  deactivates when alarm is on

1

AU

Auxiliary/alarm relay control

  

0  =  alarm relay

1  =  manual auxiliary relay controlled via AUX key

2  =  automatic auxiliary relay managed by StA temp. 

setting with 2°C differential

3  =  not used

4  =  pump-down function (see manual)

5  =  free voltage contact for  

 

 

 condensing unit (AUX relay and compressor relay in 

parallel)

6=Relay used to control a heating element in the 

crankcase. The relay is on when the compressor is 

stopped.

7=not used

0

StA

Temp. setting for aux. relay

-45...+45 °C

0

In1

Man in cold room alarm

0  =  compressor protection

1  =  man-in-room alarm

0

P1

Password type of protection

( active when PA does not equal 0)

0  =  display set point only

1  =  display set point, AUX, light access

2  =  access to programming not permitted

3  =  access to second level programming not 

permitted

3

PA

Password

(see P1 for the type of protection), 0...999, 0=not 

active

0

reL

Software version 

(Read only)

-

See manual for further information

Summary of Contents for AK-RC 101

Page 1: ...lslutninger Connections Anschlüsse Raccordements Conexión Anslutningar AK RC 101 AK RC 103 Se også manual RS8FD RS8FE See also manual Siehe auch Manual Voir aussi manuel Ver también manual Se också manual AK RC 101 AK RC 101 OPTYMATM AK RC 101 AK RC 103 ...

Page 2: ...e Válvula solenoide Kriwan Kriwan Kriwan Kriwan Kriwan Pressure Pressostat HT LT Druckschalter Pressostat Control de présion Pump down Pump down Pump down Pump down Pump down Pump d mode Pump down mode Pump down Modus Pump down mode Pump down mode Th mode Termostatmode Thermostat Modus Thermostat mode Termostato mode Amb sensor Rumføler Raumfühler Température ambiente Temperatura ambiente Def sens...

Page 3: ... slukket 0 ventilatorerne kører kontinuerligt 1 ventilatorerne kører kun når kompressoren arbejder 1 F4 Ventilatorpause under afrimning 0 ventilatorerne kører under afrimning 1 ventilatorerne kører ikke under afrimning 1 dE Sensortilstedeværelse 0 fordampersensor til stede 1 ingen fordampersensor 0 d1 Afrimningstype 1 varmgas 0 elektrisk 0 Ad Benyttes ikke Ald Min og maks temperatur alarm 1 240 mi...

Page 4: ... registreret en EEPROM hukommelses alarm Alle udgange bortset fra alarmen deaktiveres Sluk enheden og tænd den igen E8 Person i kølerum alarm Nulstil alarmindgangen i kølerummet Ec Kompressorbeskyttelse udløst f eks termisk beskyttelse eller maks pressostat Alle udgange bortset fra alarmen hvis relevant deaktiveres Kontrollér at kompressoren fungerer korrekt Kontrollér kompressorens forbrug Hvis p...

Page 5: ...run continuously 1 fans only run when compressor is working 1 F4 Fan pause during defrost 0 fans run during defrost 1 fans do not run during defrost 1 dE Sensor presence 0 evaporator sensor present 1 no evaporator sensor 0 d1 Defrost type 1 hot gas 0 electric 0 Ad Not to be used Ald Minimum and maximum temperature alarm 1 240 min 120 min C1 Minimum time between shutdown and subsequent switching on...

Page 6: ...ROM memory alarm has been detected All outputs except the alarm are deactivated Switch unit off and back on again E8 Man in cold room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm where applicable are deactivated Check that compressor is working properly Check compressor absorption If the...

Page 7: ...ur wenn der Verdichter in Betrieb ist 1 F4 Lüfterstopp während des Abtauens 0 Lüfter laufen beim Abtauen 1 Lüfter laufen beim Abtauen nicht 1 dE Fühler 0 Abtaufühler vorhanden 1 kein Abtaufühler 0 d1 Abtaumethode 1 Heißgas 0 Elektroheizung 0 Ad Wird nicht benutzt Ald Mindest und Höchsttemperaturalarm 1 240 Min 120 Min C1 Mindestzeit zwischen dem Herunterfahren und dem nachfolgenden Einschalten des...

Page 8: ...estellt alle Ausgänge außer dem Alarm sind deaktiviert Schalten Sie die Anlage ab und dann wieder ein E8 Alarm Person im Kühlraum Setzen Sie den Alarmgeber im Kühlraum zurück Ec Verdichterschutz ausgelöst z B Thermoschutzschalter oder Hochdruckschalter Alle Ausgänge außer dem Alarm sind deaktiviert Prüfen Sie ob der Verdichter ordnungs gemäß funktioniert Überprüfen Sie die Stromaufnahme des Verdic...

Page 9: ...s en marche continue 1 ventilateurs en marche uniquement si le compresseur fonctionne 1 F4 Arrêt des ventilateurs pendant le dégivrage 0 ventilateurs en marche pendant le dégivrage 1 ventilateurs arrêtés pendant le dégivrage 1 dE Présence sonde 0 sonde évaporateur présente 1 pas de sonde d évaporateur 0 d1 Type de dégivrage 1 gaz chaud 0 résistance 0 Ad Ne pas utiliser Ald Temporisation signalisat...

Page 10: ...de l alarme Éteindre puis rallumer l appareil E8 Alarme de présence d une personne dans la chambre Réinitialiser l entrée de l alarme ou le bouton coup de poing dans la chambre froide Ec Activation de la protection du compresseur exemple protection thermique ou pressostat les sorties sont toutes désactivées excepté l alarme le cas échéant Vérifier que le compresseur fonctionne correctement Contrôl...

Page 11: ...n funcionamiento continuo 1 ventiladores en marcha solo durante el funcionamiento del compresor 1 F4 Pausa de los ventiladores durante el desescarche 0 los ventiladores funcionan durante el desescarche 1 ventiladores parados durante el desescarche 1 dE Presencia del sensor 0 sensor de evaporador presente 1 sensor de evaporador ausente 0 d1 Tipo de desescarche 1 gas caliente 0 resistencia 0 Ad No u...

Page 12: ...arán todas las salidas excepto las de alarma Apague el equipo y vuelva a encenderlo E8 Alarma de persona en la cámara frigorífica Restablezca la entrada de alarma en el interior de la cámara frigorífica Ec Protección del compresor activada p ej protección térmica o presostato de alta Se desactivarán todas las salidas excepto las de alarma si existen Compruebe que el compresor funciona correctament...

Page 13: ... normalt stängd 0 F3 Fläktstatus med kompressor OFF 0 fläktarna kör kontinuerligt 1 fläktarna kör bara när kompressorn arbetar 1 F4 Fläktstopp under avfrostning 0 fläktarna kör under avfrostning 1 fläktarna kör ej under avfrostning 1 dE Förångargivare 0 förångargivare ansluten 1 ingen förångargivare 0 d1 Avfrostningstyp 1 hetgas 0 elektrisk 0 Ad Används ej Ald Min och max temperatur larm 1 240 min...

Page 14: ...ts Alla utgångar förutom larmreläet deaktiverade Slå av och på enheten E8 Man i kylrum larm Reset the alarm input inside the cold room Ec Kompressorskydd utlöst termiskt skydd eller tryckbrytare Alla utgångar förutom larmreläet vid tillämpligt deaktiverade Återställ larmet i kylrummet Kontrollera att kompressorn arbetar som den ska Om problemet kvarstår kontakta teknisk assistans Ed Öppen dörr lar...

Page 15: ...AK RC 101 103 Instructions RI8NN35K Danfoss 01 2010 15 ...

Page 16: ... AK RC 101 103 The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic waste According to Local and currently valid legislation DE BD ...

Reviews: