62
RS8HP102 © Danfoss 2018-09
AK-CC 750A
Set alarm priorities
1. Go to Configuration menu
2. Select Alarm priorities
3. Set priorities for Temperature alarms
Press the
+
-button to go on to the next page
4. Set Alarm priorities for sensor error
Press the
+
-button to go on to the next page
Very many functions have an alarm connected.
Your choice of functions and settings has connected all the relevant
alarms that are current. They will be shown with text in the three
pictures.
All alarms that can occur can be set for a given order of priority:
• ”High” is the most important one
• ”Log only” has lowest priority
• ”Disconnected” gives no action
The interdependence between setting and action can be seen in the
table.
Setting
Log
Alarm relay selection
Net-
work
AKM-
dest.
Non
High
Low - High
High
X
X
X
X
1
Medium
X
X
X
2
Low
X
X
X
3
Log only
X
4
Discon-
nected
Configuration - continued
In our example we select the settings shown here in the display
In our example we select the settings shown here in the display