AK-CC 750A
RS8HP102 © Danfoss 2018-09
15
Signal
Module
Point
Terminal
Signal type /
Active at
1
(AI 1)
1 - 2
2
(AI 2)
3 - 4
3
(AI 3)
5 - 6
4
(AI 4)
7 - 8
5
(AI 5)
17 - 18
6
(AI 6)
19 - 20
7
(AI 7)
21 - 22
8
(AI 8)
23 - 24
Point
Signal
Signal
type
S
Pt 1000 ohm/0°C
S2
S3
S4
S5
Saux
Pt 1000
P
AKS 32R
AKS 2050
AKS 32
P0
Pc
Paux
AKS 32R
AKS 2050
MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
U
...
0 - 5 V
0 - 10 V
On/Off
Ext.
Main
switch
Day/
Night
Door
Defrost
Active at:
Closed
/
Open
Point
5
6
7
8
Type
AI5
AI6
AI7
AI8
Point
1
2
3
4
Type
AI1
AI2
AI3
AI4
Terminal
9:
12 V
Terminal
10:
5 V
Terminal
15:
5 V
Terminal
16:
12 V
Terminal
11, 12, 13, 14:
(Cable screen)
The screen on the pressure
transmitter cables must only
be connected at the end of the
controller.
At the top the
signal input is
the left of the
two terminals.
At the bottom
the signal input
is the right of the
two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red