background image

Controller for evaporator control

AK-CC 750A

User Guide

ADAP-KOOL

®

 Refrigeration control systems

Summary of Contents for AK-CC 750A

Page 1: ...Controller for evaporator control AK CC 750A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...39 Ordering 40 3 Mounting and wiring 41 Mounting 42 Mounting of extension module on the basic module 42 Wiring 43 4 Configuration and operation 45 Configuration 47 Connect PC 47 Authorization 48 Unloc...

Page 3: ...tat Defrost on demand based on evaporator capacity Appliance cleaning function Light control using door switch or network signal depending on day night operation Rail heat pulsing depending on day nig...

Page 4: ...requirements are changed Flexible concept Controller series with common construction One principle many regulation uses Modules are selected for the actual connection requirements The same modules ar...

Page 5: ...o a number of general functions such as time table manual operation log function alarms and service configuration Network linking The controller can be linked up into a LON network together with other...

Page 6: ...field If you want to know more about a current alarm you can click on it and obtain an information display on the screen A corresponding display exists for all earlier alarms Here you can upload infor...

Page 7: ...pecific software and by which input and output signals the relevant application will require If it is an application with few connections the controller module top part with belonging bottom part may...

Page 8: ...ulation is planned set up it will generate a need for a number of connections distributed on the mentioned types This connection must then be made on either the controller module or an extension modul...

Page 9: ...ed continuously AK CM 102 Communication module Data communication for external exten sion modules Type Function Application AK CC 750A Controller for evaporator control Refrigeration appliances contro...

Page 10: ...tage must not be connected to the same output group Solid state outputs Can be used for loads that are cut in and out frequently e g rail heat fans and AKV valve Max 240 V a c Min 48 V a c Max 0 5 A L...

Page 11: ...2018 09 11 Dimensions The module dimension is 72 mm Modules in the 100 series consist of one module Modules in the 200 series consist of two modules Controllers consist of three modules The length of...

Page 12: ...Address setting When the controller is connected to a gateway type AKA 245 the controller s address must be set between 1 and 119 1 200 at AK SM Service PIN When the controller is connected to the dat...

Page 13: ...1 12 7 AI 7 13 14 8 AI 8 19 20 9 AI 9 21 22 10 AI 10 23 24 11 AI 11 25 26 12 DO 1 31 32 13 DO 2 33 34 14 DO 3 35 36 15 DO 4 37 38 16 DO 5 39 40 41 17 DO6 42 43 44 18 DO7 45 46 47 19 DO8 48 49 50 24 25...

Page 14: ...pply voltage The supply voltage to the module comes from the previous mod ule in the row Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending o...

Page 15: ...2 1 zz bar U 0 5 V 0 10 V On Off Ext Main switch Day Night Door Defrost Active at Closed Open Point 5 6 7 8 Type AI5 AI6 AI7 AI8 Point 1 2 3 4 Type AI1 AI2 AI3 AI4 Terminal 9 12 V Terminal 10 5 V Term...

Page 16: ...on The module contains 8 inputs for on off voltage signals Signal AK XM 102A is for low voltage signals AK XM 102B is for high voltage signals Supply voltage The supply voltage to the module comes fro...

Page 17: ...11 12 7 DI 7 13 14 8 DI 8 15 16 Point Signal Active at DI Ext Main switch Day Night Door Defrost Closed voltage on Open voltage off Point 5 6 7 8 Type DI5 DI6 DI7 DI8 Point 1 2 3 4 Type DI1 DI2 DI3 D...

Page 18: ...ious module in the row Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type Galvanic isolation The inputs are galvanically...

Page 19: ...0 10 V On Off Ext Main switch Day Night Door Level switch Active at Closed Open AO 0 10 V Point 5 6 7 8 Type AO1 AO2 AO3 AO4 Point 1 2 3 4 Type AI1 AI2 AI3 AI4 Point Terminal 9 12 V Terminal 10 5 V Te...

Page 20: ...to over ride the relay s function Either to position OFF or ON In position Auto the controller carries out the control Light emitting diodes There are two rows with LED s They indicate the following L...

Page 21: ...Active at 1 DO 1 25 27 2 DO 2 28 30 3 DO 3 31 33 4 DO 4 34 36 5 DO 5 37 39 6 DO 6 40 41 42 7 DO 7 43 44 45 8 DO 8 46 47 48 Signal Active at DO Fan Alarm Light Railheat Defrost Night blind Valve Compr...

Page 22: ...ight change over switches at the front make it possible to over ride the relay s function Either to position OFF or ON In position Auto the controller carries out the control Light emitting diodes The...

Page 23: ...050 AKS 32 P0 Pc Paux AKS 32R AKS 2050 MBS 8250 1 xx bar AKS 32 1 zz bar U 0 5 V 0 10 V On Off Ext Main switch Day Night Door Defrost Active at Closed Open DO Fan Alarm Light Rail heat Defrost Night b...

Page 24: ...ssary if the valves need to open close during a power failure Light emitting diodes There is one row with LED s It indicate the following Voltage supply to the module Communication active with the bot...

Page 25: ...n CCMT Point 1 2 3 4 5 6 7 8 Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 Terminal 17 12 V Terminal 18 5 V Terminal 19 20 Cable screen The screen on the pressure transmitter cables must only be connected at t...

Page 26: ...The supply voltage to the module comes from the controller module Placing The module is placed on the PC board in the controller module Point The two outputs have points 24 and 25 They are shown on th...

Page 27: ...rts up the display will show the output that is connected 1 output A 2 output B etc Placing The extension module can be placed at a distance of up to 15 m from the controller module Point No point has...

Page 28: ...ler Supply voltage 230 V a c or 115 V a c from 100 V a c to 240 V a c Placing On DIN rail Effect Type Output tension Output current Power AK PS 075 24 V d c 0 75 A 18 VA AK PS 150 24 V d c adjustable...

Page 29: ...The 24 V can be sourced from the same supply that supplies the controller The supply for the communication module is galvani cally separated from the connected extension modules The terminals must not...

Page 30: ...ge over switches switches that can override the indi vidual relays into either OFF or ON position Data communication The controller module has terminals for LON data communication The requirements to...

Page 31: ...upply When programming the pressure trans mitter s pressure range must be set ON OFF voltage inputs DI This signal must be connected to two terminals The signal must have two levels either 0 V or volt...

Page 32: ...appliance functions Make a sketch of the system in question Follow these 12 steps AK CC 750A Application Control of cold room or freezing room x Control of refrigeration or freezing appliances x Regu...

Page 33: ...pe AKV The function cannot be used in combination with pulsation of fans If you want to know more about the functions go to chapter 5 A bit more about the functions Common thermostat The thermostat te...

Page 34: ...inputs which can be used for monitoring and alarm function On Off inputs Contact function on an analog input or voltage signal on an extension module External start stop of regulation Pulse pressure o...

Page 35: ...s Inject ON Start of defrost pulse pressure Door contact Night setback General DI alarm inputs 1 10 Open close Night blind pulse pressure On off outputs AKV valves 3 Solenoid valves in liquid line Fan...

Page 36: ...hether there is connection to the connected modules This status can be followed by the light emitting diode When the two catches for the DIN rail mounting are in open posi tion the module can be pushe...

Page 37: ...d for the programming Columns 2 and 4 are used for the connection diagram Example continued Signal Module Point Terminal Signal type Active at Air temperature S3A 1 1 AI 1 1 2 Pt 1000 Air temperature...

Page 38: ...at dwg and dxf You may then yourself write the module number in the circle and draw the individual connections Example continued AKV A S3A 3 x EKA 163B S3B 1 1 1 2 2 3 3 4 4 5 6 7 8 12 13 14 15 16 17...

Page 39: ...be necessary to safeguard the voltage to the controller and valves using UPS Transformer size The power consumption grows with the number of modules used Module Type Number Effect Controller 1 x 8 8...

Page 40: ...ation module Data communication for external extension mod ules 080Z0064 Type Function Application Language Code no Example continued AK CC 750A Controller for evaporator control 1 2 3 or 4 sections E...

Page 41: ...ing This section describes how the controller Is fitted Is connected We have decided to work on the basis of the example we went through previously i e the following modules AK CC 750A controller modu...

Page 42: ...K assembly 2 Assemble the extension module and the basic module The basic module must not be connected to voltage In our example one extension module is to be fitted to the basic module The sequence i...

Page 43: ...t 1000 Air temperature S4C 6 AI 6 11 12 Pt 1000 Defrost sensor S5A 7 AI 7 13 14 Pt 1000 Defrost sensor S5B 8 AI 8 19 20 Pt 1000 Defrost sensor S5C 9 AI 9 21 22 Pt 1000 Gas temperature S2A 10 AI 10 23...

Page 44: ...vice Pin When the controller is set correct on the network the LED sta tus will flash quickly for 10 minutes 6 The controller is now ready to be configured The connections for the example can be seen...

Page 45: ...nfiguration and operation This section describes how the controller Is configured Is operated We have decided to work on the basis of the example we went through previously i e a frost appliance with...

Page 46: ...Refrigeration 3 AKV valves Superheat measured with P0 and 3 S2 sensors S3 is alarm sensor S4 is thermostat sensor Night setback on 3K Defrost The defrost is stopped individually based on temperature...

Page 47: ...view of it will always appear In case the overview is empty This is because the controller has not yet been set up The red alarm bell at the bottom right tells you that there is an active alarm in the...

Page 48: ...ecific system and a corresponding access code for this person The controller will utilize the same language that is selected in the service tool but only if the controller contains this language If th...

Page 49: ...ation lock can be Unlocked Configuration lock The controller can only be fully configured when the configuration lock is set to Un locked The settings are only applied when it is set to Locked again A...

Page 50: ...ayed in here Alarm text can be in a different language to the operating language Clock When the time is set the PC s time can be transferred to the controller When the controller is connected to a net...

Page 51: ...ue with the settings and check the values If you change some of the settings the new values will come into force Number of evaporators Select the number of evaporators that you want the controller to...

Page 52: ...d The temperature is controlled individual by ON OFF in each evaporator section 1 valve per evaporator individual modulating thermostat Here one valve per evaporator is used The temperature is control...

Page 53: ...ation Display control Select whether you want to connect to display type EKA 163B EKA 164B to indicate the appliance temperature for section A Set tings are non weighted S3 S4 or product temperature s...

Page 54: ...fans should be on during defrost Defrost stop method Define whether defrost is to be concluded with Time Temperature individual in each section or Tempera ture common for all sections Defrost term sen...

Page 55: ...nd thermostat cutout Fan night eco at EC or VSD Fan speed during night operation and thermostat cutout EC min start speed at EC or VSD Lowest speed the first 10 seconds after start Fan stop on S5 Sele...

Page 56: ...r alarm delay If the door has been open for more than the time delay set here a door alarm is triggered Light control Select whether the light should be controlled by a door switch a day night signal...

Page 57: ...unction can be used to monitor all kinds of digital signals No of inputs Set the number of digital alarm inputs Adjust for each input Name Delay time for DI alarm Alarm text Setup general alarm inputs...

Page 58: ...sensors Each thermostat has a separate outlet to control external automation No of thermostats Set the number of general thermostats 1 5 For each thermostat adjust Name Which of the sensors is used A...

Page 59: ...m message via the data communication Setup separate voltage functions 3 Voltage inputs The general volt inlet can be used to monitor external voltage signals Each volt inlet has a separate outlet to c...

Page 60: ...DO7 1 18 ON Rail heat DO8 1 19 ON We set up the controller s digital outputs by keying in which module and point on this module each one of these has been connected to We furthermore select for each...

Page 61: ...Bar AKS 32 1 20 Bar AKS 32R 1 20 Bar AKS 32 1 34 Bar AKS 32R 1 34 Bar AKS 32 1 50 Bar AKS 32R 1 50 Bar AKS 2050 1 59 Bar AKS 2050 1 99 bar AKS 2050 1 159 bar MBS 8250 1 159 Bar Voltage signals for re...

Page 62: ...larms that are current They will be shown with text in the three pictures All alarms that can occur can be set for a given order of priority High is the most important one Log only has lowest priority...

Page 63: ...priorities for Various alarms Press the button to go on to the next page 6 Set Alarm priorities for General functions Configuration continued In our example we select the settings shown here in the d...

Page 64: ...rison of selected func tions and define inputs and outputs The result can be seen in the next section where the setup is controlled Configuration continued Press in the field against Configuration loc...

Page 65: ...t number on the selected mod ule had been set up for something different The error is corrected by setting up the output correctly Remember that the setup must be unlocked be fore you can change modul...

Page 66: ...s controls requires that the setup is locked By means of the manual control of each output it can be checked whether the output has been correctly connected Activate the various functions the door swi...

Page 67: ...check that all the settings are as they should be The overview display will now show one line for each of the general functions Behind each icon there is a number of displays with the different setti...

Page 68: ...ress the blue overview button at the bottom left of the display and then press the defrost symbol 10 Settings for defrost 11 Go to defrost schedule Press the schedule button to continue to the defrost...

Page 69: ...starts Use the copying functions if there are several days with identical defrosts The end result with two defrosts per 24 hours can be seen here above 14 Go to common functions Press the blue overvie...

Page 70: ...row of the two other address switches must point at 0 2 Push the Service Pin Press down the service pin and keep it down until the Service Pin LED lights up 3 Wait for answer from the system unit Depe...

Page 71: ...remove cancelled alarms from the alarm list 5 Check active alarm again In our case we have a series of alarms We will tidy them up so that we only have those that are relevant In our case an active al...

Page 72: ...ttom of the display 2 Start control First start of control continued Press in the field against Main switch Select ON The controller will now start the controlling when the external function switch is...

Page 73: ...start display for new logs Start by defining which type of log has to be defined Here it is determined which parameters have to be included in the setup of data Select a function here then a paramete...

Page 74: ...74 RS8HP102 Danfoss 2018 09 AK CC 750A Manual defrost 1 Go to Configuration menu 2 Select defrost 3 Start defrost If you want to carry out manual defrost proceed as follows Activate...

Page 75: ...AK CC 750A RS8HP102 Danfoss 2018 09 75 5 Regulating functions This section describes how the different functions work...

Page 76: ...need for defrost will adapt the number of defrosts so that no energy is wasted on un necessary defrosts and subsequent cooling down cycles Among the different functions can briefly be mentioned Contr...

Page 77: ...common valve for all evaporators common ON OFF ther mostat A line up of refrigeration appliances which are to be regulated to the same temperature is a typical example The temperature is controlled ac...

Page 78: ...ossible stable superheating This ensures that the cooling process takes place as quickly as possible In the case of stable loads the thermostat will reduce the open ing time for the AKV valve so the t...

Page 79: ...ed on the basis of the air temperature sen sors S3 S4 or both Definition of the thermostat temperature takes place using one setting which is based on the S4 value With a setting of 100 only the S4 me...

Page 80: ...ation is to take place When a Night blind is used the distribution of air in the appliance will change radically A change of the thermostat s weighted S3 S4 ratio will therefore be required As a rule...

Page 81: ...re For too high temperature during normal regulation For too high temperature during cooling down after activation of internal or external start stop during a defrost after a power failure after appli...

Page 82: ...arge fans In order to prevent this situation the controller can stop the fans if the temperature at S5 exceeds a set limit value The function can also be used as a sort of MOP function during start up...

Page 83: ...s possible to open them using a switch signal on the digital input If this input is activated the night blinds will open and the refrigeration appliance can be filled with new products If the input is...

Page 84: ...minutes of the end of forced closing defrosting will restart the moment forced closing ends Alarm relay If the controller is to give alarm at a relay output the relay must be defined A setting determ...

Page 85: ...her use one of the sensors used by the control function Po Pc or an independent sensor Paux1 Paux2 Paux3 Cutin and cutout limits are set for the pressure control Coupling of the pressure control s out...

Page 86: ...to all sections When regulating with a flooded evaporator three separate superheat settings are used It is the installer s responsibility to ensure that signal loss to the controller will not result i...

Page 87: ...e and a drain valve A time delay can be set which defers opening of the hot gas valve Defrost start Defrost can be started in several ways Once started it will continue until a defrost stop signal is...

Page 88: ...n the evaporator outlet For large evaporators there should be two S5 sensors S5 1 and S5 2 The defrost is stopped when both temperatures have at tained the set value If the defrost time exceeds the se...

Page 89: ...rted is set meas ured always with the S5 sensors The max permissible time delay in minutes is set The time delay for fan start will not commence until the time delay for liquid injection if applicable...

Page 90: ...be used if one of the following refrigerants are used for regulation R23 R513B R13B1 or user defined This function can only cancel planned defrosts which start from a defrost schedule either an inter...

Page 91: ...on the evapora tor but it may also be due to reduced air flow as a consequence of severe over stacking of goods or dropout of fans After this alarm the function will not cancel defrosts This alarm is...

Page 92: ...on the appliance with the heaviest load Forced refrigeration The controller will undertake refrigeration when this signal is received Refrigeration will continue until the signal is removed The funct...

Page 93: ...ntroller will shut down and restart 4 Once the controller has restarted open parameter 093 and the configuration lock is opened value 0 5 If AKV stepper valves are used you must also select refrigeran...

Page 94: ...his value hat to be set in a RMS value Some valve manufacturers are using peak current Soft Landing after Valve Init At power on the valve is performing a valve Initialization i e closing the valve wi...

Page 95: ...KM menu description for further details Regulating status The controller goes through some regulating situations You can see the actual situation here When operating with AK ST the text is written on...

Page 96: ...densing pressure faulty Paux1 sensor error High Paux1 sensor error Paux1 pressure transmitter signal faulty Paux2 sensor error High Paux2 sensor error Paux2 pressure transmitter signal faulty Paux3 se...

Page 97: ...alarm input DI x Stepper valve High Stepper Inj A B C D Open coil Shorted output Error Power failure Check supply to the actual valve System alarms The alarm priority can not be altered on system ala...

Page 98: ...Door Main s Po AKV A AKV B Def A Def B Suction Comp Room 3 Air S3 S2A S3A S2B S2C For cl Door Main s Po AKV A AKV B AKV C Light Rail heat Comp Room 3 El S3 S2A S3A S5A S2B S5B For cl Door Main s Po A...

Page 99: ...15 pt 16 High temp Low temp Fan Alarm 1 Fan Alarm 2 3 Fan Alarm 4 5 Fan Alarm 6 Fan Alarm 7 8 Fan Alarm 47 48 Rail heat Comp Fan Alarm Suction Drain Light 10 12 Fan Alarm 9 11 Fan Alarm 13 Def C Rail...

Page 100: ...KV A AKV B Def A Def B Rail heat Comp CO2 2 El S3 S4 S2A S3A S4A S5A S2B S3B S4B S5B For cl Main s Po AKV A AKV B Def A Def B CO2 2 evap 2 El S3 S4 S2A S3A S4A S5 1A S2B S3B S4B S5 1B For cl Main s Po...

Page 101: ...heat Comp Fan Alarm Suction Drain Light Blinds 62 Fan Alarm 35 Fan Alarm S2C S3C S4C Light 51 Fan Alarm S2C S3C S4C Light Blinds 71 Def C S2C S3C S4C S5C Rail heat Comp Fan Alarm Light 36 37 Def C S2...

Page 102: ...A S5A Clean Blinds Po AKV A Def Blinds Rail heat Gas S3 S4 S2A S3A S4A S5A Clean Blinds Po AKV A Def Suction Drain Blinds Rail heat 2 Air S3 S4 S2A S3A S4A S2B S3B S4B Clean Blinds Po AKV A AKV B Blin...

Page 103: ...Def C Def D Rail heat Light Fan 37 38 Def C Def D Rail heat Light Fan Suction Drain 39 40 Light Fan 1 Light Fan 2 3 Light Fan 4 5 Light Fan 11 Light Fan 12 13 Light Fan 14 15 Light Fan 21 Light Fan S...

Page 104: ...A LLSV B LLSV C LLSV D Def A Def B Gas S3A S4A S3A S4A S5A S5B S5C S5D Door LLSV A LLSV B LLSV C LLSV D Def A Def B Case 1 Air S3 S4 S3A S4A Clean Blinds LLSV A Blinds Rail heat EL S3 S4 S3A S4A S5A...

Page 105: ...ht Fan 57 58 Light Fan 59 60 Light Fan 66 Light Fan 67 68 Suction Drain Rail heat Light Fan 69 70 Light Fan 76 Def C Def D Rail heat Light Fan 77 78 Def C Def D Rail heat Light Fan Suction Drain 79 80...

Page 106: ...es the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specificat...