Danfoss AK-CC 550A User Manual Download Page 33

AK-CC 

550A 

Manual RS8FS402 © Danfoss 2016-03 

33

Coordinated defrost via 

data communication

Coordinated defrost via 

cable connections

The following controllers can be connected 

up in this way:

EKC 204A, AK-CC 210, AK-CC 250, 

AK-CC 450, AK-CC 550A,

Refrigeration is resumed when all 

controllers have “released” the signal for 

defrost.

The setting of controllers to coordinate 

their defrosting takes place in the 

gateway/system manager.

Refrigeration is resumed when all 

controllers have “released” the signal for 

defrost.

DO1

Connection of expansion valve type AKV or AKVA. The coil must 

be a 

230 V a.c. coil.

DO2

Alarm

There is a connection between terminal 7 and 8 in alarm 

situations and when the controller is without power.

Rail heat and heating element in drip tray

There is connection between terminal 7 and 9 when heating 

takes place.

Night blind

There is connection between terminal 7 and 9 when the night 

blind is up.

Suction line valve

There is connection between terminal 7 and 9 when the 

suction line must be open.

DO3

Refrigeration, Rail heat, Heat function, Defrost 2

There is connection between terminal 10 and 11 when the 

function must be active.

Heating element in drip tray

There is connection between terminal 10 and 11 when heating 

takes place.

DO4

Defrost

There is connection between terminal 12 and 14 when 

defrosting takes place.

Hot gas / drain valve

There is connection between terminal 13 and 14 during normal 

operation.  

There is connection between terminal 12 and 14 when the hot 

gas valves must open.

DO5

Fan

There is connection between terminal 15 and 16 when the fan 

is on.

DO6

Light relay

There is connection between terminal 17 and 18 when the 

light must be on.

Rail heat, Compressor 2

There is connection between terminal 17 and 19 when the 

function must be active.

DI3

Digital input signal.  

The signal must have a voltage of 0 / 230 V AC. 

The function is defined in o84. 

Data communication

If data communication is used, it is important that the installation 

of the data communication cable is performed correctly.

See separate literature No. RC8AC…

Electric noise

Cables for sensors, DI inputs and data communication 

must

 be 

kept separate from other electric cables:

- Use separate cable trays

- Keep a distance between cables of at least 10 cm

- Long cables at the DI input should be avoided

Installation considerations

Accidental damage, poor installation, or site conditions, can give 

rise to malfunctions of the control system, and ultimately lead to a 

plant breakdown.
Every possible safeguard is incorporated into our products to 

prevent this. However, a wrong installation, for example, could still 

present problems. Electronic controls are no substitute for normal, 

good engineering practice.
Danfoss will not be responsible for any goods, or plant compo-

nents, damaged as a result of the above defects. It is the installer's 

responsibility to check the installation thoroughly, and to fit the 

necessary safety devices.
Special reference is made to the necessity of signals to the 

controller when the compressor is stopped and to the need of 

liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further 

advice, etc.
 

Max. 10

Summary of Contents for AK-CC 550A

Page 1: ...Controller for appliance control AK CC 550A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...ting sensor In addition to the outlet to the electronic injection valve of the type AKV the controller has 5 relay outputs which are defined by the use selected the individual usage options are descri...

Page 3: ...ange depending on the selected applica tion Application 9 This use is for refrigeration appliances with one valve two evapo rators and two refrigeration sections Here the temperature and alarm monitor...

Page 4: ...after the evaporator S4 respectively A setting for the thermostat alarm thermostat and display reading deter mines how much the two sensor values should influence each individual function e g 50 will...

Page 5: ...s for the product sensor Appliance cleaning This function makes it easy for the shop s staff to carry out a cleaning of the appliance according to a standard procedure Appliance cleaning is activated...

Page 6: ...efrosting When defrosting is commenced the heating element is activated The heating element remains activated until a set time after defrosting has ended by time or temperature Start of defrost A defr...

Page 7: ...ght The setting is also recommended for rooms A value is calculated for the evaporator air flow The evaporator is monitored and the next scheduled defrost will be carried out as required If the functi...

Page 8: ...ave top priority during normal regulation But if one of the override functions is activated the Min On time will be disregarded Railheat It is possible to pulse control the power to the rail heat in o...

Page 9: ...the data communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be con...

Page 10: ...forced closing the fans can be defined to be stopped or in operation Door contact The door contact function can via the digital inputs be defined for two different applications Alarm monitoring The co...

Page 11: ...hanged to one of the same type but with Index A version with screw terminals The controllers address must be set higher than 0 in order for the display to be able to communicate with the controller If...

Page 12: ...a product sensor but in application 9 and 10 it has a different use DI1 DI2 and DI3 are contact functions that can be used for one of the fol lowing functions door function alarm function defrost star...

Page 13: ...en the light is switched off the night blinds are down In addition a digital input provides the option of forced opening of the blinds so that the appliance can be filled with products Application 8 H...

Page 14: ...dicating application 1 If you employ another use signs are provided so that you can mount the relevant one It is only the lower sign that needs to be mounted The number is indicated on the left hand s...

Page 15: ...re values in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the set ting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from...

Page 16: ...et time delay has been passed The time delay is set in minutes A03 Alarm delay Time delay for door alarm The time delay is set in minutes The function is defined in o02 o37 or in o84 A04 DoorOpen del...

Page 17: ...ress u58 comp7 LLSV Here you can read the status of the compressor relay Defrost Defrost control The controller contains a timer function that is zeroset after each defrost start The timer function wi...

Page 18: ...ost Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again The time when water is tied to the evaporator d07 FanStartDel Fan start temperature...

Page 19: ...ers a higher temperature than the one set here the fans will be stopped There will be re start at 2 K below the setting The function is not active during a defrost or start up after a defrost With set...

Page 20: ...he address is set between 0 and 240 depending on the system unit and the selected data communication If the system unit is gateway type AKA 245 the version must be 6 20 or higher o03 The address is se...

Page 21: ...et ting is selected to either 2 or 3 When the door is opened the relay will cut in When the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but i...

Page 22: ...that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point value where the rail heat i...

Page 23: ...ctual superheat reference u22 SH ref Read the valve s actual opening degree u23 AKV OD Read the evaporating pressure u25 Evap press Pe Read the evaporating temperature u26 Evap temp Te Read the temper...

Page 24: ...or S15 15 Refrigeration stopped due to open ON input or stopped regulation S16 16 Door is open DI input is open S17 17 Melt function in progress Refrigeration is interrupted S18 18 Modulating thermost...

Page 25: ...A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Appliance cle...

Page 26: ...on to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower button and select the new value 3 Push the middle button again...

Page 27: ...arm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 12h 8h 8h 6h Defrost sensor...

Page 28: ...m A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 1 1 1 1 1 1 1 1 50 C 50 C 8 Low...

Page 29: ...07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0 Clock Setting of minute t08 1 1 1 1 1 1 1 1 1 1 0 min 59 min 0 Clock Setting of date t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1 Clock Setting of month t46 1 1 1 1 1 1...

Page 30: ...ulse signal 5 ext main switch 6 night operation 7 thermostat band changeover activate r21 8 Not used 9 Not used 10 Appliance cleaning pulse signal 11 forced cooling at hot gas defrost 12 night cover 1...

Page 31: ...ction line u64 1 Status on relay for compressor 2 u67 1 Temperature measured with S5B sensor u75 1 Temperature measured with S3B sensor u76 1 Status on relay for hot gas drain valve u80 1 Status on re...

Page 32: ...Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data communication...

Page 33: ...he hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail heat...

Page 34: ...During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density IP 20 Mounting DIN rail or wall Weight 0 4 Kg Data communication Fixed MODBUS Extension optio...

Page 35: ...ernal display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw terminals 084B8562...

Page 36: ...erves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi...

Reviews: