Configuration of alarm relay
The alarm relay will be activated upon an alarm signal from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
The groups that are to activate the alarm relay must be set by using a numerical value
which is the sum of the groups that must be activated.
(E.g.: a value of 5 will activate all high temperature alarms and all sensor error and 0
will cancel relay function
P41
Al.Rel. Conf.
Case shut down
Service
Service
Temperature measured with S5 sensor
u09
S5 temp.
Status on DI1 input. on/1=closed
u10
DI1 status
Read the duration of the ongoing defrost or the duration of the last completed
defrost.
u11
Defrost time
Temperature measured with S3 sensor
u12
S3 air temp
Status at the day-/night operation (night operation: on/off)
u13
Night Cond.
Temperature measured with S4 sensor
u16
S4 air temp
Thermostat temperature
u17
Ther. air
Read the ongoing cutin time for the thermostat or the duration of the last com-
pleted cutin
u18
Ther runtime
Read the temperature at the S2 sensor
u20
S2 temp.
Read superheat
u21
Superheat
Read the control’s actual superheat reference
u22
SH ref.
Read the valve’s actual opening degree
u23
AKV OD %
Read the evaporating pressure
u25
Evap.press Pe
Read the evaporating temperature
u26
Evap.temp Te
Read the temperature at the S6 sensor
u36
S6 temp
Status on DI2 output. on/1=closed
u37
DI2 status
Air temperature. Weighted S3 + S4
u56
Display air
Measured temperature for alarm thermostat
u57
Alarm air
* Status on relay for cooling
u58
Comp1/LLSV
* Status on relay for fan
u59
Fan relay
* Status on relay for defrost
u60
Def. relay
* Status on relay for railheat
u61
Railh. relay
* Status on relay for alarm
u62
Alarm relay
* Status on relay for light
u63
Light relay
* Status on relay for valve in suction line
u64
SuctionValve
* Status on relay for compressor 2
u67
Comp2 relay
* Temperature measured with S5B sensor
u75
S5 temp. B
* Temperature measured with S3B sensor
u76
S3 temp. B
* Status on relay for hot gas
u80
Hotgas valve
* Status on relay for heating element in drip tray
u81
Drip tray
* Status on relay for night blinds
u82
Blinds relay
* Status on relay for defrost B
u83
Def. relay B
* Status on relay for heat function
u84
Heat relay
* Readout of the actual rail heat effect in %
u85
Rail DutyC %
Readout of which thermostat used for regulation: 1= Thermostat 1,
2= Thermostat 2
u86
Ther. band
Status on input DI3 (on/1 = 230 V)
u87
DI3 status
Readout of the actual cutin value for the thermostat
u90
Cutin temp.
Readout of the actual cut out value for the thermostat
u91
Cutout temp.