Danfoss AK-CC 550 Instructions Manual Download Page 7

 AK-CC 550 

Instructions  RI8LN802  ©  Danfoss  2/2012 

7

Light-emitting diodes (LED) on front panel

The LED’s on the front panel will light up when the relevant relay 
is activated.

 = Refrigeration

 = Defrost
 = Fan running

The light-emitting diodes will flash when there is an alarm.
In this situation you can download the error code to the display 
and cancel/sign for the alarm by giving the top button a brief 
push.

The buttons

When you want to change a setting, the upper and the lower 
buttons will give you a higher or lower value depending on the 
button you are pushing. But before you change the value, you 
must have access to the menu. You obtain this by pushing the 
upper button for a couple of seconds - you will then enter the col-
umn with parameter codes. Find the parameter code you want to 
change and push the middle buttons until value for the parameter 
is shown. When you have changed the value, save the new value 
by once more pushing the middle button.

Examples

Set menu

1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you 

want to change

3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.

Cutout alarm relay / receipt alarm/see alarm code 

• A short press of the upper button

If there are several alarm codes they are found in a rolling stack. 
Push the uppermost or lowermost button to scan the rolling 
stack.

Set temperature

1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.

Reading the temperature at defrost sensor (Or product sensor, if 
selected in o92.) 

• A short press of the lower button

Manuel start or stop of a defrost

• Push the lower button for four seconds.

Display

The values will be shown with three digits, and with a setting you 
can determine whether the temperature is to be shown in °C or in 
°F.

Operation

Get a good start

With the following procedure you can start regulation very quick-
ly:

1

 Open parameter r12 and stop the regulation (in a new and not 

previously set unit, r12 will already be set to 0 which means 
stopped regulation.)

2

 Select electrical connection based on the drawings on page 2 

and 3

3

 Open parameter o61 and set the electric connection number in 

it

4

 Now select one of the preset settings from the table

Auxiliary schedule for 

settings (quick-setup)

Case

Room

Defrost stop on

Defrost  stop on

time

S5

time

S5

Preset settings

 (o62)

1

2

3

4

5

6

Temperature (SP)

2°C

-2°C

-28°C

4°C

0°C

-22°C

Max. temp. setting (r02)

6°C

4°C

-22°C

8°C

5°C

-20°C

Min. temp. setting (r03)

0°C

-4°C

-30°C

0°C

-2°C

-24°C

Sensor signal for thermo-
stat. S4% (r15)

100%

0%

Alarm limit high (A13)

8°C

6°C

-15°C

10°C

8°C

-15°C

Alarm limit low (A14)

-5°C

-5°C

-30°C

0°C

0°C

-30°C

Sensor signal for alarm 
funct.S4% (A36)

0%

100%

0%

Interval between defrost 
(d03)

6 h

6h

12h

8h

8h

6h

Defrost sensor: 0=time, 
1=S5, 2=S4 (d10)

0

1

1

0

1

1

DI1 config. (o02)

Case cleaning (=10)

Door function (=2)

Sensor signal for display 
view S4% (017)

0%

Note: For applications 9 and 10 the sensor weighting for the S3/S4 sensors is not used for the 
thermostat, alarm thermostat and display readings as the sensor uses are predefined.

5

 Open parameter o62 and set the number for the array of preset-

tings. The few selected settings will now be transferred to the 
menu.

Open parameter n57 and select method for measuring  of 

evaporator pressure Pe or S1 (factory setting is Pe pressure 
transmitter)

If pressure transmitter Pe is used you must select refrigerant via 

parameter o30

8

 Open parameter r12 and start the regulation

9

 Go through the survey of factory settings. The values in the grey 

cells are changed according to your choice of settings. Make any 
necessary changes in the respective parameters.

10

 For network. Set the address in o03

11

 Send address to system unit:

• MODBUS: Activate scan function in system unit
• If another data communication card is used in the controller:

- LON RS485: Activate the function o04

Summary of Contents for AK-CC 550

Page 1: ...l overhedningsm ling Tryktransmitter eller temperaturf ler S1 Selection of signal to superheat measurement Pressure transmitter or temperature sensor S1 Wahl des Signal f r berhitzungsmessung Druckmes...

Page 2: ...ing application 1 If you employ another use signs are provided so that you can mount the relevant one Werkseitig wird der Regler mit Schildern geliefert die Anwendung 1 angeben Wenn Sie eine andere An...

Page 3: ...AK CC 550 Instructions RI8LN802 Danfoss 2 2012 3 5 6 7 9 10 8 9 10...

Page 4: ...cation MODBUS and RS 485 must comply with the requirements for data communication cables See literature RC8AC Wichtig Alle Anschl sse an die Datenkommunikation MODBUS und RS 485 m ssen die Anforderung...

Page 5: ...which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data comm...

Page 6: ...the hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail hea...

Page 7: ...s and with a setting you can determine whether the temperature is to be shown in C or in F Operation Get a good start With the following procedure you can start regulation very quick ly 1 Open paramet...

Page 8: ...1 1 1 1 1 0 min 240 min 30 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermos...

Page 9: ...0 75 30 Injection algorithm Only for trained personnel n17 1 1 1 1 1 1 1 1 1 1 5 70 30 Injection algorithm Only for trained personnel n18 1 1 1 1 1 1 1 1 1 1 0 10 4 Injection algorithm Only for traine...

Page 10: ...me during day operations o41 1 1 1 1 1 1 1 0 100 100 Rail heat On time during night operations o42 1 1 1 1 1 1 1 0 100 100 Rail heat period time On time Off time o43 1 1 1 1 1 1 1 6 min 60 min 10 Case...

Page 11: ...1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po relative u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature...

Page 12: ...Additional information Manual RS8EN Data communication The importance of individual alarms can be defined with a setting The setting must be carried out in the group Alarm destinations Emergency cooli...

Reviews: