*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
1
2
3
4
5
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01-t06
0 hours 23 hours 0 hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11-t16
0 min.
59 min.
0 min.
Clock - Setting of hours
***
t07
0 hours 23 hours 0 hours
Clock - Setting of minutes
***
t08
0 min.
59 min.
0 min.
Clock - Setting of date
***
t45
1
31
1
Clock - Setting of month
***
t46
1
12
1
Clock - Setting of year
***
t47
0
99
0
Miscellaneous
Delay of output signals after start-up
o01
0 s
600 s
5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when
open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation. 7=change
reference (activate r40). 8=alarm function when closed. 9=alarm function when open.
10=case cleaning (pulse signal).
o02
0
10
0
Network address
o03
0
240
0
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
o04
OFF
ON
OFF
Access code 1 (all settings)
o05
0
100
0
Used sensor type (Pt /PTC/NTC)
o06
Pt
ntc
Pt
Readout of software version
o08
Display step = 0.5 (normal 0.1 at Pt sensor)
o15
no
yes
no
Max. hold time after coordinated defrost
o16
0 min.
60 min.
20 min.
Input signal on DI2. Function:
0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext. main switch. 6=night operation.
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function
when open. 10=case cleaning (pulse signal). 11=not used. 12=defrost coordination.
o37
0
12
0
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows
the DI-function, when DI is selected to door function or to door alarm
o38
1
3
1
Activation of light relay (only if o38=2)
o39
OFF
ON
OFF
Rail heat On time during day operations
o41
0%
100%
100%
Rail heat On time during night operations
o42
0%
100%
100%
Rail heat period time (On time + Off time)
o43
6 min.
60 min.
10 min.
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.
***
o46
0
2
0
Selection of EL diagram. See overview page 2
*
o61*
1
5
1
Download a set of predetermined settings. See overview previous page.
*
o62*
0
2
0
Access code 2 (partly access)
***
o64
0
100
0
Replace the controllers factory settings with the present settings
o67
OFF
On
OFF
Readout of Unit runtime in days
*
P48
0 days
999 days
0 days
Service Alarm request.
Days of operation (Unit runtime) before Service request alarm
Value = 0 disables function
P91
0 days
960 days
0 days
Defines action when Condenser blocked alarm activates:
0=Function disabled. 1=Turn off Light, 2=Stop compressor. 3=Light and comp off,
4=Stop comp, Rail heat and light off. 5=Comp, Light and RH off
P92
0
5
0
Period for counting condenser events before permanent stop
P93
0 hours 96 hours 0 hours
Number of condenser events within period before permanent stop
Value = 0 disables function
P94
0
50
0
Service
Status codes are shown on page 5
S0-S34
Temperature measured with Sair sensor
u01
Temperature measured with S5 sensor
***
u09
Status on DI1 input. on/1=closed
u10
Status on night operation (on or off) 1=closed
***
u13
Read the present regulation reference
u28
Status on DI2 output. on/1=closed
u37
Temperature measured with Sc sensor
U09
Temperature shown on display
u56
Status on relay for cooling
**
u58
Status on relay for fan
**
u59
Status on relay for defrost
**
u60
Status on relay for rail heat
**
u61
Status on relay for alarm
**
u62
Status on relay for light
**
u63
Status on relay for compressor 2
**
u67
Status on relay for condenser fan
**
u71