Flow
m³/h
Pres-
sure Pa
Measured
at
Frequency band [Hz], sound power Lw (A) [dB(A)]
Sound pressure
Lp(A) (standard*
room) [dB(A)]
63
125
250
500
1000
2000
4000
8000
126
70
Supply air
duct
20
30
41
42
38
30
19
18
Extract air
duct
18
30
41
41
30
26
18
18
Cabinet
47
126
100
Supply air
duct
22
32
46
45
39
32
21
18
Extract air
duct
22
33
43
42
32
27
19
18
Cabinet
50
162
70
Supply air
duct
23
31
43
46
41
33
22
18
Extract air
duct
26
31
42
43
33
29
21
18
Cabinet
53
162
100
Supply air
duct
28
33
44
48
43
35
23
18
Extract air
duct
29
34
44
51
37
31
23
18
Cabinet
55
216
70
Supply air
duct
28
33
44
54
46
37
28
18
Extract air
duct
27
33
43
52
39
33
27
18
Cabinet
57
216
100
Supply air
duct
28
35
45
55
46
38
29
18
Extract air
duct
32
34
44
52
40
34
28
18
Cabinet
56
* Values for sound pressure calculated for a standard room with A = 10 m², H = 2.4m and mean absorption 0.2.
Tab. 11: Sound data for the w¹ unit
Installation Guide
Danfoss Air Units
VIEWB302
Danfoss Heating Solutions