AHF terminal connections
440–480 V
60 Hz
Enclosure
size
type
Terminals X1 and X2
Terminals X3 and X4
Terminals A and B
PE
AHF
005
[A]
AHF
010
[A]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Type
Torque
[Nm (in-
lb)]
10
14
10
14
X1
0.5–10
(20–8)
Cable
end
sleeve
1.6 (14.2)
±
10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±
10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±
10%
M6
4.5 (40)
±
10%
19
25
19
25
X2
1.5–16
(16–6)
2.4 (21.2)
±
10%
0.5–4
(20–12)
0.8
(7.1)
±
10
%
M6
4.5 (40)
±
10%
31
36
48
31
36
48
X3
1.5–25
(16–4)
3.5 (31)
±
10%
1.5–16
(16–6)
2.4 (21.2)
±
10%
M8
10 (88.5)
±
10%
60
73
60
73
X4
1.5–50
(16–
1-1/0)
4 (35.4)
±
10%
1.5–25
(16–4)
3.5 (31)
±
10%
M8
10 (88.5)
±
10%
95
118
95
118
X5
10–70
(8–2/0)
5 (44.3)
±
10%
1.5–25
(16–4)
3.5 (31)
±
10%
M8
10 (88.5)
±
10%
154
183
154
183
X6
2.5–95
(14–3/0)
Cable lug
M8
10 (88.5)
±
10%
1.5–50
(16–
1-1/0)
4 (35.4)
±
10%
M8
10 (88.5)
±
10%
231
231
291
355
380
X7
25–300
(4–600)
Cable lug
M16
50
(442.5)
±
10%
16–150
(6–300)
18
(159.3)
±
10%
M12
40 (354)
±
10%
291
355
380
436
436
X8
25–300
(4–600)
Cable lug
M16
50
(442.5)
±
10%
16–150
(6–300)
18
(159.3)
±
10%
M12
40 (354)
±
10%
Table 7.21 Terminal Specifications, 480–480 V, 60 Hz
Specifications
VLT
®
Advanced Harmonic Filter AHF 005/AHF 010
62
Danfoss A/S © 05/2019 All rights reserved.