Safety Notes

Prior to assembly and commissioning to 
avoid injury of persons and damages of 

the devices, it is absolutely necessary to 
carefully read and observe these instructions.

Necessary assembly, start-up, and maintenance 
work must be performed only by qualified, 
trained and authorized personnel.

Prior to assembly and maintenance work on the 
controller, the system must be:

- depressurized,
-  cooled down,
-  emptied and
- cleaned.

Please comply with the instructions of the 
system manufacturer or system operator.

Disposal instruction

 This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal.

Always follow the local disposal regulations.

Definition of Application

The actuator AFT.. is used in combination with 
Danfoss valves for temperature control of water, 
water-glycol mixtures, and steam for heating, 
district heating, and cooling systems.

The technical data on the rating plates 
determine the use.

Permissible Pressures and 

Temperatures 

Mounting 

Permissible Installation Positions

 

For valves VFG 2., VFG 3., VFU 2

 

DN 15-80 
media temperatures up to120 °C

 

For valves VFG 2., VFG 3., VFU 2

 

DN 100-125 and for DN 15-80,  
media temperatu res > 120 °C

   and

 for valves VFGS 2

Installation Scheme

Valves VFG 2(1), VFGS 2, VFU

 ❸

Can be installed in both flow or the return pipe.

Mixing valve VFG 33 

  Mixing valve in the supply 

flow heating

  Mixing valve in the supply 

flow cooling

Valve Installation 

1.  Install strainer in front of valve.
2.  Rinse system before installing valve.
3.  Observe flow direction 

 on the valve body.

 Flanges 

 in the pipeline system must 

be in parallel direction, the sealing 
surfaces must be clean and undamaged.

4.  Install valve.
5.  Tighten screws crosswise in 3 steps up to the 

maximum torque.

Actuator and Valve Mounting 

1.  Place actuator at the valve and align.
2.  Tighten union nut 

, torque 100 Nm

Temperature Sensor Installation 

-  The temperature sensor may be installed in 

any position

-  The capillary tube may not be twisted or 

buckled. The minimum bending radius is  
50 mm.

-   The temperature of the media has to be 

taken directly without any delay.

-  Care for sufficient cross section of flow

 

.

Filling the system and First Start-up 

When filling the system, the temperature 
control valve must be open. Alternatively, the 
filling can be carried out from all sides.

To ensure that the temperature control valve is 
open, the following must be observed:

The stem of the actuator:

is extended 

 

if the temperature at the sensor 

 is 

higher than the setpoint 

.

is retracted

 

 

if the temperature at the sensor 

 is lower 

than the setpoint 

.

In order to open the temperature control valve, 
the setpoint at the setpoint adjuster 

 is to be 

increased or reduced, depending on the valve 
designs 

-

.

The pressure 

 behind the valve may exceed 

the pressure 

 in front of the valve only 

insignificantly.

Non-compliance may cause damages at the 
valve.

Pressure test 

 Carry out pressure tests only with the 
actuator mounted.  
Without actuator, the valve is open 

the seal is in the actuator.

 It is absolutely necessary to constantly 
increase pressure from all sides.  
Non-compliance may cause damages 
at the controller. 

Observe nominal pressure 

 of the valve. 

Max. test pressure is 1.5 x PN

Setpoint Adjustment 

Thermostats are proportional controllers, 
thus certain deviation from set point can be 
expected and varies from valve DN.

The setpoint range is indicated on the rating 
plate.

 

Adjustment

When the water temperature reaches 

the set temperature, 

VFG will be fully 

closed, VFU will start opening.

1.  Observe temperature indicator 

.

2.  Adjust setpoint by turning the setpoint 

adjuster (observe the scale for relevant valve 
VFG2/VFU2) 

 increases the setpoint 

 reduces the setpoint

If the temperature at the indicator

 

 

is noticeably higher than the setpoint 
temperature, then:
-  return setpoint adjuster only in increments 

of max. 10 °C and 

-  wait until the temperature at the sensor 

drops.

After having adjusted the setpoint, wait until 
the temperature indication 

 shows its final 

value.

 Scale on the setting knob is only the 
indication of the set temperature. 
Temperature setting need to be done 
based on the temperature reading from 
the thermometer.

Dismounting of Valve  

and Actuator 

 

Danger of injury by steam or hot 
water!

.

Valve without actuator is open 

, sealing 

 is 

in the actuator.

It is absolutely necessary to depressurize system 
prior to dismounting.

Dimensions 

Summary of Contents for AFT 06

Page 1: ...nfoss com Page 5 FRANCAIS Guide d utilisation T te thermostatique pour r gulation de temp rature AFT 06 17 www danfoss com Page 6 POLSKI Instrukcja obs ugi Nap d do regulacji temperaturyAFT 06 17 www...

Page 2: ...AFT 06 17 VFG 33 B AB A MAINTENANCE FREE VFG VFU 2 VFG VFU 2 VFGS 2 Type VFG 21 33 VFU 2 VFG 2 VFGS 2 ZF 6 ZF 6 ZF 4 Tmax media C 150 150 200 200 200 300 Max operating pressure bar 14 PN 14 PN 14 PN...

Page 3: ...Danfoss 2017 07 3 VI GA N6 81 AFT 06 17 10 C 5 10 50 C VFG 2 VFG 21 VFGS 2 VFU 2 46 mm VFG 33 B A AB 380 401 AFT 06 AFT 17...

Page 4: ...perature of the media has to be taken directly without any delay Care for sufficient cross section of flow Filling the system and First Start up When filling the system the temperature control valve m...

Page 5: ...ie Temperatur des Mediums muss direkt ohne Verz gerung erfasst werden Auf ausreichenden Durchflussquerschnitt achten F llung der Anlage Inbetriebnahme Bei der F llung der Anlage muss das Temperatur re...

Page 6: ...ature du fluide doit tre saisie directement sans retard Respecter une section de d bit suffisante Remplissage de l installation mise en service Lors du remplissage de l installation la vanne thermosta...

Page 7: ...jnika by a w kontakcie z przep ywaj cym media Zadba o dostateczny przekr j poprzeczny przep ywu Nape nianie uk adu i rozruch Kiedy nape niamy uk ad zaw r regulatora temperatury musi by otwarty W innym...

Page 8: ...oravnajte ga 2 Zategnite navojnu spojnicu momentom od 100 Nm Ugradnja osjetnika temperature Osjetnik temperature mo e se ugraditi u proizvoljnom polo aju Kapilarna cijev ne smije biti omotana ili savi...

Reviews: