background image

AK-PC 

572 

User 

Guide RS8KH202 © Danfoss 2019-03 

13

Vhp Easy PI

Set how quickly the PI regulation must react here: 1 = slowly, 10 = very quickly.
(For setting 0 "User def." the special settings options will open. Kp, Tn. These options are only for 
trained staff.)

Min: 0 (User def.)
Max: 10
Fac: 5

Vhp Kp

Amplification factor for PI regulation 

  (can be viewed and configured only when the previous 

menu has been set to "0"). 

If the Kp value is lowered, regulation runs more smoothly 

Min: 0,5
Max: 10
Fac: 2,0

Vhp Tn

Integration time for PI regulation (see above)
If the Tn value is increased, regulation will run more smoothly

Min: 30
Max: 300
Fac: 75

Vhp min OD

Limitation of the valve's degree of closing

Min: 0%
Max: 15%
Fac: 0%

Averange OD

Readout of  the average opening degree of the valve

Min: 0%
Max: 100%
Fac: 35%

Fan control mode

Regulation type
The regulation is normally set to “Auto”, but it can be changed to “Manual”. 

MAN / OFF / AUTO
Fac: AUTO

Fan manual capacity

When setting to “Manual”, capacity can then be forced set in %.

Min: 0 %
Max: 100%

Fan Easy PI

Set how quickly the PI regulation must react here: 1 = slowly, 10 = very quickly.
(For setting 0 "User def." the special settings options will open. Kp, Tn. These options are only for 
trained staff.)

Min: 0 (User def.)
Max: 10
Fac: 5

Fan Kp

Amplification factor for PI regulation

   (can be viewed and configured only when the previous 

menu has been set to "0")

If the Kp value is lowered, regulation runs more smoothly 

Min: 0,5
Max: 50 
Fac: 10

Fan Tn

Integration time for PI regulation

  

 (can be viewed and configured only when the previous 

menu has been set to "0")

If the Tn value is increased, regulation will run more smoothly

Min: 10 s
Max: 900 s
Fac: 180 s

dt subcool

Here you can set the desired sub-cooling

Min: 1,0 K
Max: 30,0 K
Fac: 4,0 K

Heat recovery

Define whether a heat recovery cycle should be started with a signal on a DI input here.
• No: No function

• DI only: 

A DI input is reserved. When a signal is registered, the heat recovery function refer-

ence will become active. 

 

• DI and DO: Choose this setting if you are also activating a potential relay output (HR on the 

receiver module).

Fac: No

Heat reclaim mode

Here you configure the controller for when a signal is received for heat recovery.
You can choose between raising the temperature to achieve maximum heat recovery or 
maintain temperature at the level with the highest efficiency. 

High effect /
Max. recovery
Fac: High effect

Heat recovery SP

Here you can set the reference that the controller will switch to when heat recovery is desi-
red.

Min: 70 bar
Max: 100 bar
Fac: 80 bar

 Fan configuration

Configuration of fans

EC Start

Here you can configure the controller capacity at which the fans will start. 
(With a setting of 5% the fans will start when the desired controller capacity exceeds 5% of the 
EC Min. setting)

Min: 0%
Max: 20% 
Fac: 5%

EC Min.

Here you configure the lowest permitted speed for the fans in % (% of output signal)

If lower capacity is required, this minimum speed should be maintained all the way down to 
0% capacity. At 0% capacity, the system stops completely.

Min: 0%
Max: 30% 
Fac: 20%

EC Max.

Here you configure the fan speed in % when regulating at 100% capacity. (Typically 80% of the 
output signal).

Min: 30%
Max: 100% 
Fac: 80%

EC abs max Sgc

Here you configure the Sgc temperature at which the fan speed is raised to the absolute maxi-
mum (100% of the output signal)

Min: 20°C
Max: 60°C
Fac: 60°C

 Fan status

Fan status

Fan speed

Here a reading of the desired condenser fan capacity is provided in % 

EC start/stop

Fan operation status can be read here

Reset runtime cycl.

Here the two counters "run time" and "couplings" can be reset 

EC Runtime total

Here you can see how many hours the fans have been operational for since the last reset

EC Cycl. total

Here you can see how many fan starts there have been since the last reset

Summary of Contents for ADAP-KOOL AK-PC 572

Page 1: ...Capacity controller for CO2 mini pack AK PC 572 User Guide ADAP KOOL Refrigeration Control System...

Page 2: ...t available This could for example be used as an alarm input If the compressor used is not a Bitzer CRII a solid state output can be used for oil management If heat recovery is not used the AUX3 funct...

Page 3: ...point Based on the configured reference the controller will permit an offset of up to 8K depending on the other control parameters For example Night time increase Fixed 5 K on the MT circuit only Po o...

Page 4: ...in the transcritical area Reference It is controlled using variable references An outdoor temperature sensor Sc3 must be installed The sensor must be positioned so that it registers the correct out d...

Page 5: ...overy has been reached and the DI signal disappears the reference will drop once again though it will do so over the course of a few minutes to prevent abrupt changes in the reference A potential rela...

Page 6: ...UX2 DI It can then be used as an alarm input AUX2 DO The potential relay output can be freely used for liquid injection DE SH or hot gas dumping AUX3 DI This function shares an input with the heat rec...

Page 7: ...et capacity in night operation e g 25 but with a minimum of one step In the event of a Pgc error the fan capacity that corresponds to how much compressor capacity is connected will cut in Compressor r...

Page 8: ...will depend on how the set up is made They will illustrate what is regulated Click on the Right Arrow to view e g the following images When an alarm is sent from the con troller you must advance to t...

Page 9: ...ined on the pages that follow Start screen upon delivery Set up overview There are 2 ways in which the controller can be set up Select the one that is easiest for you either Wizard or a review of all...

Page 10: ...read as a of total capacity No of running comp The number of compressors in operation can be read here MC PoMT offset The size of a reference displacement on PoMT required from the system unit suction...

Page 11: ...under Compressor mode Min 1 m3h Max 20 m3h Fac 1 m3h Comp 2 size Set the nominal compressor capacity for compressor 2 Min 1 m3h Max 20 m3h Fac 1 m3h Comp 3 size Set the nominal compressor capacity fo...

Page 12: ...lation Yes Regulating is carried out without this compressor and no alarms are generated by it Yes No Fac No Comp 2 The same function for the remaining compressors Suction LT Suction group LT Please s...

Page 13: ...e should be started with a signal on a DI input here No No function DI only A DI input is reserved When a signal is registered the heat recovery function refer ence will become active DI and DO Choose...

Page 14: ...you can override the hot gas valve Only if hot gas dump is defined in the AUX section Auto Man on Man off Oil Control Limitation It is only possible to use oil management if the solid state outputs DO...

Page 15: ...be used for an optional function You can choose between the functions Fan error or Alarm D demand DI AUX2 If level signals are not desired for oil management the DI on the high pressure module input w...

Page 16: ...clock Date and time Used by weekly plan and alarm function Year month date Hours minutes Network Network Modbus Address Set the address of the controller here if it is connected to a system device vi...

Page 17: ...e MT circuit Once a signal is received the circuit will cut out 6 Signal from the high pressure switch in the LT circuit Once a signal is received the circuit will cut out 7 Signal from compressor 1 i...

Page 18: ...tch to Auto when the override is to be completed Auto Man 0 100 Expansion modules Manual control of a connection in the HP module and receiver module During normal regulation the function of the outpu...

Page 19: ...imit for SdMT discharge temperature has been exceeded 10K below safety limit High disch temp SdMT Critical Comp 1MT High disch temp Safety limit for discharge gas temperature has been exceeded Compres...

Page 20: ...rsion must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until the Bios menu appea...

Page 21: ...e HP module 97 for the receiver module The addresses will only be used internally between the three modules If anything has gone wrong the two valve modules will have acti vated the function EXD reset...

Page 22: ...cation and display must be kept separate from high voltage 230 V electric cables Use separate cable trays Keep a distance between high voltage and signal cables of at least 10 cm Cables longer than 3...

Page 23: ...10 volts from terminals Com AO1 N AO3 and N AO4 PAY ATTENTION TO THE POLARITY of N AO3 and AO4 are galvanically isolated AO1 is not AI Analog inputs Pressure transmitters 4 pcs AI1 AI4 Temperature sen...

Page 24: ...rnal display If an external display is connected it must be connected to the controller using a wire with a plug See order Communication will take place via Canbus The Canbus termination must be moved...

Page 25: ...rting As a result the evaporators will not be filled with fluid that can be led to a compressor when the regulation process restarts This function can be achieved through data communication Alternativ...

Page 26: ...mm2 multi core Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested acc EN 60730 1 and EN 60730 2 9 EMC tested acc EN61000 6 2 and 3 UL approval Data Pressure tra...

Page 27: ...G0320 EXD 316 Valve driver Operation from AK PC 572 24 V 084B8042 MMIGRS2 Display unit With buttons and display 080G0294 Wire for display unit L 1 5 m 1 pcs 080G0075 L 3 m 1 pcs 080G0076 List of liter...

Page 28: ...forbeholder sig ret til uden forudg ende varsel at foretage ndringer i sine produkter herunder i produkter som allerede er i ordre s fremt dette kan ske uden at ndre allerede aftalte specifikationer...

Reviews: