Normal operation
Temperature (setpoint)
***
- - -
1
1
1
1
1
1
1
1
-50°C
50°C
2
Thermostat
r-
Differential
r01
1
1
1
1
1
1
1
1
0.1 K
20 K
2
Max. limitation of setpoint setting
r02
1
1
1
1
1
1
1
1
-49°C
50°C
50
Min. limitation of setpoint setting
r03
1
1
1
1
1
1
1
1
-50°C
49°C
-50
Adjustment of temperature indication
r04
1
1
1
1
1
1
1
1
-10
10
0
Temperature unit (°C/°F)
r05
1
1
1
1
1
1
1
1
0/°C
1/F
0/°C
Correction of the signal from S4
r09
1
1
1
1
1
1
1
1
-10 K
10 K
0
Correction of the signal from S3 and S3B
r10
1
1
1
1
1
1
1
1
-10 K
10 K
0
Manual service, stop regulation, start regulation (-1, 0, 1)
***
r12
1
1
1
1
1
1
1
1
-1
1
0
Displacement of reference during night operation
r13
1
1
1
1
1
1
1
1
-50 K
50 K
0
Define thermostat function
1=ON/OFF, 2=Modulating
r14
1
1
1
1
1
1
1
1
1
2
1
Definition and weighting, if applicable, of thermostat sensors -
S4% (100%=S4, 0%=S3)
r15
1
1
1
1
1
1
1
1
0 %
100 %
100
Time between melt periods
r16
1
1
1
1
1
1
1
1
0 hrs
10 hrs
1
Duration of melt periods
r17
1
1
1
1
1
1
1
1
0 min.
30 min.
5
Temperature setting for thermostat band 2 . As differential use
r01
***
r21
1
1
1
1
1
1
1
1
-50°C
50°C
2
Correction of the signal from S6
r59
1
1
1
1
1
1
1
1
-10 K
10 K
0
Correction of the signal from S6B
r60
1
1
1
1
-10 K
10 K
0
Definition and weighting, if applicable, of thermostat sensors
when night cover is on. (100%=S4, 0%=S3)
r61
1
1
1
1
1
1
1
1
0 %
100 %
100
Heat function
Neutral zone between refrigeration and heat function
r62
1
1
1
1
1
1
1
1
0 K
50 K
5
Time delay at switch between refrigeration and heat function.
For setting = after 240 min. the heating function is deactivated
r63
1
1
1
1
1
1
1
1
0 min.
240 min.
240
Product type: use settings listed in table.
***
r89
1
1
1
1
1
1
1
1
0
5
0
Alarms
A-
Delay for temperature alarm
A03
1
1
1
1
1
1
1
1
0 min.
240 min.
30
Delay for door alarm
A04
1
1
1
1
1
1
1
1
0 min.
240 min.
60
Delay for temperature alarm after defrost
A12
1
1
1
1
1
1
1
1
0 min.
240 min.
90
High alarm limit for thermostat 1
A13
1
1
1
1
1
1
1
1
-50°C
50°C
8
Low alarm limit for thermostat 1
A14
1
1
1
1
1
1
1
1
-50°C
50°C
-30
High alarm limit for thermostat 2
A20
1
1
1
1
1
1
1
1
-50°C
50°C
8
Low alarm limit for thermostat 2
A21
1
1
1
1
1
1
1
1
-50°C
50°C
-30
High alarm limit for sensor S6 at thermostat 1
A22
1
1
1
1
1
1
1
1
-50°C
50°C
8
Low alarm limit for sensor S6 at thermostat 1
A23
1
1
1
1
1
1
1
1
-50°C
50°C
-30
High alarm limit for sensor S6 at thermostat 2
A24
1
1
1
1
1
1
1
1
-50°C
50°C
8
Low alarm limit for sensor S6 at thermostat 2
A25
1
1
1
1
1
1
1
1
-50°C
50°C
-30
S6 alarm time delay
With setting = 240 the S6 alarm will be omitted
A26
1
1
1
1
1
1
1
1
0 min.
240 min.
240
Alarm time delay or signal on the DI1 input
A27
1
1
1
1
1
1
1
1
0 min.
240 min.
30
Alarm time delay or signal on the DI2 input
A28
1
1
1
1
1
1
1
1
0 min.
240 min.
30
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
1
1
1
1
1
1
1
1
0 %
100 %
100
Delay for S6 (product sensor alarm) after defrost
A52
1
1
1
1
1
1
1
1
0 min.
240 min.
90
Delay for temperature alarm S3B
A53
1
1
1
1
0 min.
240 min.
90
Compressor
c-
Min. ON-time
c01
1
1
1
1
1
1
1
0 min.
30 min.
0
Min. OFF-time
c02
1
1
1
1
1
1
1
0 min.
30 min.
0
Time delay for cutin of comp.2
c05
1
0 sec
999 sec
5
Defrost
d-
Defrost method: 0=none, 1= EL, 2= Gas, 3=Brine, 4=Air
d01
1
1
1
1
1
1
1
1
0/No
4/Air
1/EL
Defrost stop temperature
d02
1
1
1
1
1
1
1
1
0°C
50°C
6
Interval between defrost starts
d03
1
1
1
1
1
1
1
1
0 hrs/Off
240 hrs
8
Max. defrost duration
d04
1
1
1
1
1
1
1
1
0 min.
360 min.
45