Danfoss AB-PM DN 100 Datasheet Download Page 6

Data sheet 

AB-PM DN 40-100

6 | VD.HR.D1.02

© Danfoss | 2018.01

Fig. 6

Fig. 5

DN 40

Flow limitation on Δp factory setting

Factory

setting

∆p setting [kPa]

Δp

r

 

[kPa]

40%

50%

60%

70%

80%

90%

100%

/0 turns

5 turns 10 turns 15 turns 20 turns

Q [l/h]

10

4600

5520

6348

7084

7728

8280

9200

15

4000

4800

5520

6160

6720

7200

8000

20

3300

3960

4554

5082

5544

5940

6600

9200

25

2500

3000

3450

3850

4200

4500

5000

8000

10200

30

2070

2310

2520

2700

3000

6600

9200

11100

35

5000

8000

10200

11900

40

3000

6600

9200

11100

45

5000

8000

10200

50

3150

6600

9200

55

5000

8000

60

3150

6600

 Table 1

Example 1

Given :

 Design flow to zone 

4200 l/h, pressure drop over 

the zone at design flow 25 kPa.

Solution:

 AB-PM DN 40 is 

selected. Δp setting is kept 

at factory setting and flow 

limitation is changed to 80 %. 

AB-PM will control differential  

pressure of 25 kPa when 

design flow is achieved and 

the flow to the zone will be 

limited to 4200 l/h

2000

3000

4000

5000

6000

7000

8000

9000

10000

11000

12000

13000

10

15

20

25

30

35

40

45

50

55

60

[l/h

]

∆p

r

[kPa]

Example 1

40 %

50 %

60 %

70 %

80 %

90 %

100 %

5 turns

10 turns

15 turns

20 turns

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

55000

10

15

20

25

30

35

40

45

50

55

60

FL

OW

 [L

/H

]

ΔP

r

 [kPa ]

DN 100

DN 80

DN 65

DN 50

DN 40

AB-PM HP DN 10-32 

1)

1)

 See datasheet AB-PM

DN 10-32

DN 40

Sizing

Sizing graph - ΔP/ max. flow

Summary of Contents for AB-PM DN 100

Page 1: ...oor designed executed user installations Unoccupied zones do not impact other users Flow verification and easy troubleshooting Description Ordering AB PM valve including 2 5 m impulse tube G 1 16 A br...

Page 2: ...pr 25 kPa l h 5000 6500 16800 19600 21000 Min differential pressure pa Factory setting 1 kPa 42 60 Setting range 2 3 Flow 40 100 p setting 0 20 turns 0 40 turns Nominal maximal pressure bar 16 PN16 Ma...

Page 3: ...with adapter 003Z0691 In that case the AB PM will function as a pressure independent control valve with 100 authority 1 For information on partner valve see ASV and MSV F2 datasheet Service and troub...

Page 4: ...lation of backbone piping without terminal units AB PM is used as DPCV with flow limitation ensuring the specified design pressure and flow to each zone The 2nd stage is then the installation of termi...

Page 5: ...ross the control valve Pcv p1 p2 To calculate the flow below formulas are used DPCV pr p0 p1 Q kvcv pr PIBCV pCv P1 P2 Q kvcv pcv For kvcv values see datasheet AB QM flow checker DN 40 250 For trouble...

Page 6: ...1 Example 1 Given Design flow to zone 4200 l h pressure drop over the zone at design flow 25 kPa Solution AB PM DN 40 is selected p setting is kept at factory setting and flow limitation is changed t...

Page 7: ...1400 14155 45 6305 9880 12825 50 3977 8075 11400 55 6175 9880 60 3895 8075 Table 2 Fig 8 DN 65 Flow limitation on p factory setting Factory setting p setting kPa pr kPa 40 50 60 70 80 90 100 0 turns 1...

Page 8: ...0 40600 48000 40 14000 27000 36600 44400 45 21000 32200 40600 50 14000 27000 36600 55 21000 32200 60 14000 27000 Table 5 Sizing Fig 9 DN 80 Flow limitation on p factory setting Factory setting p setti...

Page 9: ...increases the setting turning it counter clockwise reduces the setting If the setting is not known turn the spindle fully clockwise With this the setting on AB PM is at maximum value within setting ra...

Page 10: ...ing it full authority Higher pressure acts on the lower side of the control membrane 3 via an impulse tube 12 while the lower pressure in the return pipe acts on the upper side of the membrane use eit...

Page 11: ...AME 435 QM Dimensions Type L1 H1 H2 H3 a EN 1092 2 Weight kg mm DN 65 290 218 388 330 185 41 DN 80 310 223 393 335 200 46 DN 100 350 239 451 350 220 64 H 1 L1 b H 2 AB PM DN 40 50 H 3 AB PM AME 435 QM...

Page 12: ...have possibility to mount actuator without effecting presetting Valve should have variable setting Setting value should allow to set a combination of needed differential pressure and flow for zone Set...

Reviews: