Danfoss AB-PM DN 100 Datasheet Download Page 10

Data sheet 

AB-PM DN 40-100

10 | VD.HR.D1.02

© Danfoss | 2018.01

Fig. 14   AB-PM DN 65-100

DPCV

PIBCV

Design 

 

1.

  Shut off knob

 

2.

  Differential pressure setting 

spindle 

 

3.

 Membrane

 

4.

  DP cone

 

5.

 Seat

 

6.

  Valve body

 

7.

  Control valve cone

 

8.

  Locking screw

 

9.

 Scale

 

10.

  Stuffing box

 

11.

 Spindle

12.

   Impulse  tube

 

13.

  Brass handle

n

Δp setting

(turns)

0

Min. setting (factory 

setting)

40

Max. setting

Factory presetting

DN 65-100

Δp setting 

min. setting (0 turns)

Flow %

100%

AB-PM is a combined automatic balancing valve. 

It works as differential pressure controller (DPCV) 

or pressure independent control valve (PIBCV), 

flow limiter and zone controller/control valve. 

As DPCV it keeps a constant differential pressure 

over the control loop and when installed as a 

PIBCV it keeps the pressure constant over the 

control valve ensuring it full authority.

Higher pressure acts on the lower side of the 

control membrane (3) via an impulse tube (12) 

while the lower pressure in the return pipe acts 

on the upper side of the membrane (use either 

membrane or diaphragm. Do not mix these 

two, it will help clarity). When available pressure 

increases at partial loads, the membrane closes 

and thus keeps the differential pressure stable. 

The control part of AB-PM is working as a 

flow limiter. This enables to set a required 

combination of the design flow as well as the 

needed Δp. By presetting the AB-PM, the flow 

rate is defined based on the pressure demand of 

the loop or terminal unit. 

With an actuator mounted on the valve, AB-PM 

can be used as a zone valve. When the AB-PM is 

converted to a PICV it can be used, together with 

an actuator, as a full authority control valve with 

either a linear or a logarithmic characteristic.

DN  65

80 100 DN 65

80 100

42

13

23

Do not turn the spindle more than 40 turns as it will become disengaged. 

Summary of Contents for AB-PM DN 100

Page 1: ...oor designed executed user installations Unoccupied zones do not impact other users Flow verification and easy troubleshooting Description Ordering AB PM valve including 2 5 m impulse tube G 1 16 A br...

Page 2: ...pr 25 kPa l h 5000 6500 16800 19600 21000 Min differential pressure pa Factory setting 1 kPa 42 60 Setting range 2 3 Flow 40 100 p setting 0 20 turns 0 40 turns Nominal maximal pressure bar 16 PN16 Ma...

Page 3: ...with adapter 003Z0691 In that case the AB PM will function as a pressure independent control valve with 100 authority 1 For information on partner valve see ASV and MSV F2 datasheet Service and troub...

Page 4: ...lation of backbone piping without terminal units AB PM is used as DPCV with flow limitation ensuring the specified design pressure and flow to each zone The 2nd stage is then the installation of termi...

Page 5: ...ross the control valve Pcv p1 p2 To calculate the flow below formulas are used DPCV pr p0 p1 Q kvcv pr PIBCV pCv P1 P2 Q kvcv pcv For kvcv values see datasheet AB QM flow checker DN 40 250 For trouble...

Page 6: ...1 Example 1 Given Design flow to zone 4200 l h pressure drop over the zone at design flow 25 kPa Solution AB PM DN 40 is selected p setting is kept at factory setting and flow limitation is changed t...

Page 7: ...1400 14155 45 6305 9880 12825 50 3977 8075 11400 55 6175 9880 60 3895 8075 Table 2 Fig 8 DN 65 Flow limitation on p factory setting Factory setting p setting kPa pr kPa 40 50 60 70 80 90 100 0 turns 1...

Page 8: ...0 40600 48000 40 14000 27000 36600 44400 45 21000 32200 40600 50 14000 27000 36600 55 21000 32200 60 14000 27000 Table 5 Sizing Fig 9 DN 80 Flow limitation on p factory setting Factory setting p setti...

Page 9: ...increases the setting turning it counter clockwise reduces the setting If the setting is not known turn the spindle fully clockwise With this the setting on AB PM is at maximum value within setting ra...

Page 10: ...ing it full authority Higher pressure acts on the lower side of the control membrane 3 via an impulse tube 12 while the lower pressure in the return pipe acts on the upper side of the membrane use eit...

Page 11: ...AME 435 QM Dimensions Type L1 H1 H2 H3 a EN 1092 2 Weight kg mm DN 65 290 218 388 330 185 41 DN 80 310 223 393 335 200 46 DN 100 350 239 451 350 220 64 H 1 L1 b H 2 AB PM DN 40 50 H 3 AB PM AME 435 QM...

Page 12: ...have possibility to mount actuator without effecting presetting Valve should have variable setting Setting value should allow to set a combination of needed differential pressure and flow for zone Set...

Reviews: