background image

Lifting the Unit

WARNING

RISK OF INJURY OR DEATH

Follow local safety regulations for lifting heavy weights.
Failure to follow recommendations and local safety
regulations can result in death or serious injury.

Ensure that the lifting equipment is in proper
working condition.

Always lift the drive using the dedicated lifting
eyes. To avoid bending the lifting holes, use a bar.
Maximum diameter of bar: 20 mm (0.8 in).

The angle from the top of the drive to the lifting
cable: 60

°

 or greater.

Test lift the drive approximately 610 mm (24 in) to
verify proper center of gravity lift point. To avoid
dropping the unit, reposition the lifting point if the
unit is not level.

See the 

operating guide

 for the weight of the

drives.

Illustration 1.2 Recommended Lifting Method

Securing the Pedestal to the Floor

The pedestal must be secured to the floor using 6 bolts before
installing the enclosure.

1.

Determine proper placement of the unit, concerning
operating conditions and cable access.

2.

Access the mounting holes by removing the front
panel of the pedestal.

3.

Set the pedestal on the floor and secure using 6
bolts through the mounting holes. Refer to the
circled areas in 

Illustration 1.3

.

Illustration 1.3 Pedestal-to-Floor Mounting Points

Attaching the E1h/E2h to the Pedestal

1.

Lift the drive and position it on the pedestal. There
are 2 bolts in the rear of the pedestal that slide into
the 2 slotted holes in the rear of the enclosure.
Position the drive by adjusting the bolts up or down.
Loosely secure with 2 M10 nylon-insert lock nuts and
locking brackets. See 

Illustration 1.4

.

2.

Verify that there is 225 mm (9 in) top clearance for
air exhaust.

3.

Verify that the air intake at the bottom front of the
unit is not obstructed.

4.

Around the top of the pedestal, secure the enclosure
using 6 M10x22 screws. Refer to 

Illustration 1.5

.

Loosely tighten each fastener until all are installed.

5.

Torque each fastener to 19 Nm (169 in-lb).

Installation Instructions

Tall Pedestal Kit for E1h/E2h Drives
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

MI35V102

Danfoss A/S © 03/2018 All rights reserved.

3

Summary of Contents for 176F6764

Page 1: ...n and installing or servicing with power connected can cause death serious injury or equipment failure To avoid death serious injury or equipment failure Only use qualified electricians for the instal...

Page 2: ...15 7 in and features a front grill to allow the airflow necessary to cool the drive components The gland plate ships with the drive and is necessary to maintain the IP21 Type 1 or IP54 Type 12 protect...

Page 3: ...ating conditions and cable access 2 Access the mounting holes by removing the front panel of the pedestal 3 Set the pedestal on the floor and secure using 6 bolts through the mounting holes Refer to t...

Page 4: ...lustration 1 7 and Illustration 1 9 1 Enclosure 4 M10 nylon insert lock nut 2 Pedestal 5 Locking bracket 3 Bolt at rear of pedestal 6 Slotted hole in enclosure Illustration 1 4 Pedestal to Enclosure B...

Page 5: ...rsunk screws securing the pedestal front plate 3 Insert the gland plate using 1 of the following methods 3a To insert the gland plate through the pedestal slide the gland plate through the slot in the...

Page 6: ...of E1h Drive with Tall Pedestal Illustration 1 8 Side View of E1h Drive with Tall Pedestal Installation Instructions Tall Pedestal Kit for E1h E2h Drives VLT FC Series FC 102 FC 103 FC 202 and FC 302...

Page 7: ...of E2h Drive with Tall Pedestal Illustration 1 10 Side View of E2h Drive with Tall Pedestal Installation Instructions Tall Pedestal Kit for E1h E2h Drives VLT FC Series FC 102 FC 103 FC 202 and FC 302...

Page 8: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Reviews: