Lifting the Unit
WARNING
RISK OF INJURY OR DEATH
Follow local safety regulations for lifting heavy weights.
Failure to follow recommendations and local safety
regulations can result in death or serious injury.
•
Ensure that the lifting equipment is in proper
working condition.
•
Always lift the drive using the dedicated lifting
eyes. To avoid bending the lifting holes, use a bar.
Maximum diameter of bar: 20 mm (0.8 in).
•
The angle from the top of the drive to the lifting
cable: 60
°
or greater.
•
Test lift the drive approximately 610 mm (24 in) to
verify proper center of gravity lift point. To avoid
dropping the unit, reposition the lifting point if the
unit is not level.
•
See the
operating guide
for the weight of the
drives.
Illustration 1.2 Recommended Lifting Method
Securing the Pedestal to the Floor
The pedestal must be secured to the floor using 6 bolts before
installing the enclosure.
1.
Determine proper placement of the unit, concerning
operating conditions and cable access.
2.
Access the mounting holes by removing the front
panel of the pedestal.
3.
Set the pedestal on the floor and secure using 6
bolts through the mounting holes. Refer to the
circled areas in
Illustration 1.3
.
Illustration 1.3 Pedestal-to-Floor Mounting Points
Attaching the E1h/E2h to the Pedestal
1.
Lift the drive and position it on the pedestal. There
are 2 bolts in the rear of the pedestal that slide into
the 2 slotted holes in the rear of the enclosure.
Position the drive by adjusting the bolts up or down.
Loosely secure with 2 M10 nylon-insert lock nuts and
locking brackets. See
Illustration 1.4
.
2.
Verify that there is 225 mm (9 in) top clearance for
air exhaust.
3.
Verify that the air intake at the bottom front of the
unit is not obstructed.
4.
Around the top of the pedestal, secure the enclosure
using 6 M10x22 screws. Refer to
Illustration 1.5
.
Loosely tighten each fastener until all are installed.
5.
Torque each fastener to 19 Nm (169 in-lb).
Installation Instructions
Tall Pedestal Kit for E1h/E2h Drives
VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
MI35V102
Danfoss A/S © 03/2018 All rights reserved.
3