background image

Description

The cable clamp kit is an option available for E3h and E4h
drives. The kit includes all parts required to install cable
clamps for mains, motor, and control wiring. E3h and E4h
drives with an RFI filter option (H4) include cable clamps as
standard equipment.

Kit Ordering Numbers

Kit number

Kit description

176F6746

Cable clamp kit for E3h

176F6747

Cable clamp kit for E4h

Table 1.1 Numbers for the Cable Clamp Kit

Items Supplied

The cable clamp kit contains the following items. Refer to

Illustration 1.2

.

Item

Quantity

Cable clamp, 60 mm

6

Cable clamp, 16 mm

1

Cable bracket

1

Extension bracket

1

M6 hex nut

4

M8 hex nut

4

Table 1.2 Items Supplied in Cable Clamp Kit

Only qualified, Danfoss authorized personnel are allowed to
install the parts described in these installation instructions.
Handling of the drive and its parts must be done in
accordance with the corresponding 

operating guide

.

WARNING

ELECTRICAL SHOCK HAZARD

VLT

®

 FC series drives contain dangerous voltages when

connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.

To avoid death, serious injury, or equipment failure:

Only use qualified electricians for the installation.

Disconnect the drive from all power sources before
installation or service.

Treat the drive as live whenever the mains voltage
is connected.

Follow the guidelines in these instructions and local
electrical safety codes.

WARNING

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.

Disconnect or lock PM motor.

Wait 40 minutes for capacitors to discharge fully.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Installation Instructions

Cable Clamp Kit for E3h/E4h Drives
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

Danfoss A/S © 04/2018 All rights reserved.

MI35U102

Summary of Contents for 176F6746

Page 1: ...icing with power connected can cause death serious injury or equipment failure To avoid death serious injury or equipment failure Only use qualified electricians for the installation Disconnect the drive from all power sources before installation or service Treat the drive as live whenever the mains voltage is connected Follow the guidelines in these instructions and local electrical safety codes ...

Page 2: ... remove the lower cover panel from the drive 2 Unfasten 5 screws T20 securing the terminal cover and remove the cover 1 Lower cover panel 5 Slotted drive bracket 2 Terminal cover 6 Plastic gland plate 3 Grommet access hole for control wiring 7 Fastener point 4 Track guide 8 Keyhole opening Illustration 1 1 Terminal Cover Disassembly Assembly Installation Instructions Cable Clamp Kit for E3h E4h Dr...

Page 3: ... the front of the extension bracket 4 Fasten 4 M6 hex nuts T25 securing the cable bracket to the studs 5 Tilt each cable clamp at a 45º angle and insert the hooks through any 2 holes in the bracket Lower to a horizontal position 6 Insert a cable into each clamp and tighten the cable adjustment screw to secure the cable 1 M8 hex nut 6 Clamp adjustment screw 2 Threaded stud 7 Cable clamp 60 mm 3 Ext...

Page 4: ...inal cover until it is positioned against the slotted drive bracket 4 Tilt the front of the terminal cover upward until the fastener hole in the drive aligns with the keyhole opening in the terminal cover 5 Secure the terminal cover with 2 screws T20 Torque to 2 3 Nm 20 in lb 6 Replace the lower cover panel and fasten with 4 screws T25 Torque to 2 3 Nm 20 in lb Illustration 1 3 E3h Drive with Cabl...

Page 5: ...or E3h Illustration 1 4 Front and Side Views of E3h with Cable Clamp Kit Installation Instructions Cable Clamp Kit for E3h E4h Drives VLT FC Series FC 102 FC 103 FC 202 and FC 302 MI35U102 Danfoss A S 04 2018 All rights reserved 5 ...

Page 6: ...ts products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S Ulsnaes 1 DK 6300 Graasten vlt drive...

Reviews: