Safety Instructions
Refer to
VLT
®
DriveMotor FCP 106 and FCM 106 Operating
Instructions
for detailed information about safety precautions
for installation.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.
1.
Stop the motor.
2.
Disconnect AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.
3.
Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in
Voltage
[V]
Power Range
1)
[kW]
Minimum waiting
time
(min)
3x400
0.55–7.5
4
Table 1.1 Discharge Time
1) Power ratings relate to NO, see VLT
®
DriveMotor FCP 106 and FCM 106
Operating Instructions.
Connection to FCP 106 or FCM 106
1.
Connect the LOP as shown in
and
2.
After completing connections, cut off or isolate
excess wire.
3.
Connect terminal 27 V to +24 V or set
parameter 5-12 Terminal 27 Digital Input
to
[0] No
operation
.
Terminal
Dual-speed
operation
Dual-mode
operation
Dual-direction
operation
18
Purple
Gray
19
–
27
Brown
29
Green
12
Red
50
Yellow
55
Blue
Table 1.2 Electrical Connections
Illustration 1.3 LOP Connections to FCP 106 or FCM 106
Installation Instructions
LOP Connection and Set-up
VLT
®
DriveMotor FCP/FCM 106
2
Danfoss A/S © 09/2015 All rights reserved.
MI03L202