background image

 

AK-CC 

210A 

Instructions RI8RE3ML © Danfoss 10/2016 

7

*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***)  With access code 2 the access to these menus will be limited

SW = 1.1x

1

2

3

4

5

HACCP

Actual temperature measurement for the HACCP function

h01

Last registered peak temperature

h10

Selection of function and sensor for the HACCP function. 0 = no HACCP function. 1 = S4 
used (maybe also S3). 2 = S5 used

h11

0

2

0

Alarm limit for the HACCP function

h12

-50.0°C

50.0°C

8.0°C

Time delay for the HACCP alarm

h13

0 min.

240 min. 30 min.

Select signal for the HACCP function. S4% (100% = S4, 0% = S3)

h14

0%

100%

100%

Real time clock

Six start times for defrost. 
Setting of hours. 
0=OFF

t01-t06

0 hours 23 hours 0 hours

Six start times for defrost.
Setting of minutes.
0=OFF

t11-t16

0 min

59 min

0 min

Clock - Setting of hours

***

t07

0 hours 23 hours 0 hours

Clock - Setting of minute

***

t08

0 min

59 min

0 min

Clock - Setting of date

***

t45

1

31

1

Clock - Setting of month

***

t46

1

12

1

Clock - Setting of year

***

t47

0

99

0

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm 
when open. 4=defrost start (pulse-signal).  5=ext.main switch. 6=night operation 
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function 
when open. 10=case cleaning (pulse signal).

o02

1

10

0

Network address

o03

0

240

0

On/Off switch (Service Pin message)
IMPORTANT! o61 

must

 be set prior to o04

o04

OFF

ON

OFF

Access code 1 (all settings)

o05

0

100

0

Readout of Software version

o06

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Max hold time after coordinated defrost

o16

0 min

60 min

20

Select signal for display view.  S4% (100%=S4, 0%=S3)

o17

0%

100%

100%

Input signal on DI2. Function: 
(0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm 
when open. 4=defrost start (pulse-signal).  5=ext. main switch 6=night operation 
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function 
when open. 10=case cleaning (pulse signal).

o37

0

10

0

Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-
function, when DI is selected to door function or to door alarm

o38

1

3

1

Activation of light relay (only if o38=2)

o39

OFF

ON

OFF

Rail heat On time during day operations

o41

0%

100%

100

Rail heat On time during night operations

o42

0%

100%

100

Rail heat period time (On time + Off time)

o43

6 min

60 min

10 min

Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.

***

o46

0

2

0

Selection of  EL diagram. See overview page 2

*

o61*

1

5

1

Download a  set of predetermined settings. See overview previous page. 

*

o62*

0

3

0

Access code 2 (partly access)

***

o64

0

100

0

Save the controllers present settings to the programming key. Select your own number. 

o65

0

25

0

Load a set of settings from the programming key (previously saved via o65 function)

o66*

0

25

0

Replace the controllers factory settings with the present settings

o67

OFF

On

OFF

Service

Status codes are shown on page 5

S0-S32

Temperature measured with S5 sensor

***

u09

Status on DI1 input. on/1=closed

u10

Temperature measured with S3 sensor

***

u12

Status on night operation (on or off) 1=closed

***

u13

Temperature measured with S4 sensor

***

u16

Thermostat temperature

u17

Read the present regulation reference

u28

Status on DI2 output. on/1=closed

u37

Temperature shown on display

u56

Measured temperature for alarm thermostat

u57

Status on relay for cooling

**

u58

Status on relay for fan

**

u59

Status on relay for defrost

**

u60

Status on relay for railheat

**

u61

Status on relay for alarm

**

u62

Status on relay for light

**

u63

Status on relay for compressor 2

**

u67

Status on relay for compressor fan

**

u71

Summary of Contents for 084B8530

Page 1: ... 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 8 6 A 10 A Resistive 5FLA 30LRA DO3 Refrigeration 2 6 3 A 6 A Resistive 3FLA 18LRA 131 VA Pilot duty DO4 Alarm light rail heat fan or comp fan 4 1 A Min 100 mA 4 A Resistive 131 VA Pilot duty DO1 and DO2 are 16 A relays DO3 and DO4 are 8 A relays Max load must be kept Gold plating ensures make function with small contact loads UL approval based on 30000 c...

Page 2: ...2 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A 1 2 3 4 5 o61 Electrical connections Conexão elétrica DI1 DI2 AU Guld Gold Or Oro l max 15 m ...

Page 3: ...ermostatfølere S4 100 S4 0 S3 r15 0 100 100 Aktivering af referenceforskydning r40 r39 OFF ON OFF Værdi for referenceforskydning aktiveres via r39 eller DI r40 50 0 K 50 0 K 0 0 K Alarm Forsinkelse på temperaturalarm A03 0 min 240 min 30 min Forsinkelse på døralarm A04 0 min 240 min 60 min Forsinkelse på temperaturalarm efter afrimning A12 0 min 240 min 90 min Høj alarmgrænse A13 50 0 C 50 0 C 8 0...

Page 4: ...ngen S4 100 S4 0 S3 o17 0 100 100 Indgangssignal på DI2 Funktion 0 ikke anvendt 1 status på DI2 2 dørfunktion med alarm ved åben 3 døralarm ved åben 4 afrimningsstart pulssignal 5 ekstern hovedafbryder 6 natdrift 7 skift reference r40 aktiveres 8 alarmfunktion ved sluttet 9 alarmfunktion ved åben 10 møbelrengøring pulssignal o37 0 10 0 Konfiguration af lysfunktionen relæ 4 1 ON under dagdrift 2 ON...

Page 5: ...eter 2 Tryk på øverste eller nederste knap og find hen til den parameter du vil indstille 3 Tryk på den midterste knap indtil vær dien for parameteren vises 4 Tryk på øverste eller nederste knap og find den nye værdi 5 Tryk igen på den midterste knap for at fastlåse værdien Udkoble alarmrelæ se alarmkode Kort tryk på den øverste knap Indstille temperaturen 1 Tryk på den midterste knap til tempera ...

Page 6: ...efrost A12 0 min 240 min 90 min High alarm limit A13 50 0 C 50 0 C 8 0 C Low alarm limit A14 50 0 C 50 0 C 30 0 C Alarm delay DI1 A27 0 min 240 min 30 min Alarm delay DI2 A28 0 min 240 min 30 min Signal for alarm thermostat S4 100 S4 0 S3 A36 0 100 100 Compressor Min ON time c01 0 min 30 min 0 min Min OFF time c02 0 min 30 min 0 min Time delay for cutin of comp 2 c05 0 sec 900 sec 5 sec Compressor...

Page 7: ... 100 Input signal on DI2 Function 0 not used 1 status on DI2 2 door function with alarm when open 3 door alarm when open 4 defrost start pulse signal 5 ext main switch 6 night operation 7 change reference activate r40 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal o37 0 10 0 Configuration of light function relay 4 1 ON during day operation 2 ON OFF via data c...

Page 8: ...arameter r01 is shown 2 Push the upper or the lower button and find that parameter you want to change 3 Push the middle button until the parameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to enter the value Cutout alarm relay receipt alarm see alarm code Push short the upper button Set temperature 1 Push the middle button until the...

Page 9: ...e alarme DI1 A27 0 min 240 min 30 min Atraso de alarme DI2 A28 0 min 240 min 30 min Sinal do termostato do alarme S4 100 S4 0 S3 A36 0 100 100 Compressor Tempo mínimo LIGADO c01 0 min 30 min 0 min Tempo mínimo DESLIGADO c02 0 min 30 min 0 min Tempo de atraso de ativação do comp 2 c05 0 sec 900 sec 5 sec O relé do compressor 1 deve ativar e desativar inversamente função NC c30 0 OFF 1 ON 0 OFF Temp...

Page 10: ...ando fe chado 9 função de alarme quando aberto 10 limpeza do expositor pressão de pulso o37 0 10 0 Configuração da função de luz relé 4 1 LIGADO durante a operação diurna 2 LIGADO DESLIGADO via comunicação de dados 3 segue a função de DI quando DI estiver selecionado para função de porta ou alarme da porta o38 1 3 1 Ativação do relé de luz somente se o38 2 o39 OFF ON OFF Tempo de aquecimento do tr...

Page 11: ... Há parada baseada no tempo d Degelo em andamento Primeiro resfria mento após degelo PS Senha requerida Configurar senha Os botões Programar menu 1 Pressione o botão superior até ser mos trado um parâmetro r01 2 Pressione o botão superior ou inferior e localize o parâmetro que deseja alterar 3 Pressione o botão intermediário até o valor de parâmetro ser mostrado 4 Pressione o botão superior ou inf...

Page 12: ...12 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A ...

Reviews: