Defrost method: 0=No, 1= EL, 2= gAs. 3=brine, 4=air
1-3
d01
1
1
1
1
1
1
1
1
1 0/No
4/Air
1/EL
Defrost stop temperature
1-2
d02
1
1
1
1
1
1
1
1
1 0°C
50°C
6
Interval between defrost starts
1-2
d03
1
1
1
1
1
1
1
1
1 0 hrs/Off 240 hrs
8
Max. defrost duration
1-2
d04
1
1
1
1
1
1
1
1
1 0 min.
360 min.
45
Displacement of time on cut-in of defrost at start-up
1-2
d05
1
1
1
1
1
1
1
1
1 0 min.
240 min.
0
Drip off time
1-2
d06
1
1
1
1
1
1
1
1
1 0 min.
60 min.
0
Delay for fan start after defrost
1-2
d07
1
1
1
1
1
1
1
1
1 0 min.
60 min.
0
Fan start temperature
1-2
d08
1
1
1
1
1
1
1
1
1 -50°C
10°C
-5
Fan cut-in during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
3: Running but stops at the temperature set in d41
1-2
d09
1
1
1
1
1
1
1
1
1 0
3
1
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4
1-2
d10
1
1
1
1
1
1
1
1
1 0
2
0
Pump down delay
1-2
d16
1
1
1
1
1
1
1
1
1 0 min.
60 min.
0
Max. aggregate refrigeration time between two
defrosts
1-2
d18
1
1
1
1
1
1
1
1
1 0 hrs
240 hrs
0/OFF
Rail heat during defrost
0=off. 1=on. 2=Pulsating
1-2
d27
1
1
1
1
1
1
1
1
1 0
2
1
Max. duration of -d- in display
1-2
d40
1
1
1
1
1
1
1
1
1 5 min.
240 min.
30 min.
Temperature limit for fan stop during defrost when
d09 is set to 3
1-2
d41
1
1
1
1
1
1
1
1
1 -20°C
20°C
0
Injection control function
Max. value of superheat reference
1-2
n09
1
1
1
1
1 "n10"
20°C
12
Min. value of superheat reference
1-2
n10
1
1
1
1
1 2°C
"n09"
3
MOP temperature. Off if MOP temp. = 15.0 °C
1-2
n11
1
1
1
1
1 -50°C
15°C
15
Cycle time of AKV pulsation
Only for trained personnel
1-2*
n13
1
1
1
1
1 3 sec
6 sec
6
Cycle time at PWM pulse width modulating
1-2
n63
1
1
1
1
30 sec
900 sec
300
Max. opening degree at PWM
1-2
n64
1
1
1
1
"n65"
100 %
100
Min. opening degree at PWM
1-2
n65
1
1
1
1
0 %
"n64"
0
Expert setting. Wind up at PWM
1-2
n66
1
1
1
1
0.2
1.0
1.0
Expert setting. Kp at PWM
1-2
n67
1
1
1
1
0.5
10.0
4.0
Expert setting. Tn at PWM
1-2
n68
1
1
1
1
60 sec
1800 sec
300
Fan
Fan stop temperature (S5)
1-2
F04
1
1
1
1
1
1
1
1
1 -50°C
50°C
50
Pulse operation on fans: 0=No pulse operation, 1=At
thermostat cut-outs only, 2= Only at thermostat
cut-outs during night operation
1-2
F05
1
1
1
1
1
1
1
1
1 0
2
0
Cycle time for fan pulsation (on-time + off-time)
1-2
F06
1
1
1
1
1
1
1
1
1 1 min.
30 min.
5
On-time in % of cycle time
1-2
F07
1
1
1
1
1
1
1
1
1 0 %
100 %
100
Real time clock
Defrost start via defrost schedule: 0/off=no.
1/on=yes
1-2
t00
1
1
1
1
1
1
1
1
1 0/off
1/on
0/off
Six start times for defrost.
Setting of hours.
0=OFF
1-2
t01 -
t06
1
1
1
1
1
1
1
1
1 0 hrs
23 hrs
0
Six start times for defrost.
Setting of minutes.
0=OFF
1-2
t11 -
t16
1
1
1
1
1
1
1
1
1 0 min.
59 min.
0
Clock - Setting of hours
0-1
t07
1
1
1
1
1
1
1
1
1 0 hrs
23 hrs
0
Clock - Setting of minutes
0-1
t08
1
1
1
1
1
1
1
1
1 0 min.
59 min.
0
Clock - Setting of date
0-1
t45
1
1
1
1
1
1
1
1
1 1 day
31 days
1
Clock - Setting of month
0-1
t46
1
1
1
1
1
1
1
1
1 1 mon.
12 mon.
1
Clock - Setting of year
0-1
t47
1
1
1
1
1
1
1
1
1 0 years
99 years
0
Defrost schedule for Mondays is active at On/1
1-2
t51
1
1
1
1
1
1
1
1
1 0/Off
1/On
1/On
Defrost schedule for Tuesdays is active at On/1
1-2
t52
1
1
1
1
1
1
1
1
1 0/Off
1/On
1/On
Defrost schedule for Wednesdays is active at On/1
1-2
t53
1
1
1
1
1
1
1
1
1 0/Off
1/On
1/On
Defrost schedule for Thursdays is active at On/1
1-2
t54
1
1
1
1
1
1
1
1
1 0/Off
1/On
1/On
Defrost schedule for Fridays is active at On/1
1-2
t55
1
1
1
1
1
1
1
1
1 0/Off
1/On
1/On
Compact - continued
R-W Code 1 2 3
4
5 6 7
8
9
Min.
Max.
Fac.
Actual
© Danfoss | DCS (vt) | 2019.10
AN300028324304en-000401 | 11