Menu survey
SW = 2.0x
Menu set via display
R-W
If the operation is limited by a setting of one or more passwords, reading and setting the parameter will be limited to:
R: This setting can be seen with password no. _ or higher.
W: This setting can be performed with password no. _ or higher (3 is the highest level).
*) In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
**) In order to change this parameter the parameter r12 Main switch must be set in position "SEr" allowing manual control of outputs.
Parameters
Wiring diagram pages 2-4
Min. value Max. value
Factory
setting
Actual
setting
Function
R-W
Code
1 2
3
4
5 6
7
8
9
Normal operation
Temperature (setpoint)
0-0
r00
1
1
1
1
1
1
1
1
1 "r03"
"r02"
2
Thermostat
Differential
1-2
r01
1
1
1
1
1
1
1
1
1 0.1 K
20 K
2
Max. limitation of setpoint setting
0-2
r02
1
1
1
1
1
1
1
1
1 "r03"
50°C
50
Min. limitation of setpoint setting
0-2
r03
1
1
1
1
1
1
1
1
1 -50°C
"r02"
-50
Temperature unit (°C/°F)
1-2
r05
1
1
1
1
1
1
1
1
1 0/°C
1/F
0/°C
Correction of the signal from S4
1-2
r09
1
1
1
1
1
1
1
1
1 -10 K
10 K
0
Correction of the signal from S3
1-2
r10
1
1
1
1
1
1
1
1
1 -10 K
10 K
0
SEr: Manual control (-1), OFF: Stop control (0), ON:
Sta<rt control (1)
0-2
r12
1
1
1
1
1
1
1
1
1 -1
1
0
Displacement of reference during night operation
1-2
r13
1
1
1
1
1
1
1
1
1 -50 K
50 K
0
Define thermostat function
1=ON/OFF, 2=Modulating
1-2
r14
1
1
1
1
1
1
1
1
1 1
2
1
Definition and weighting, if applicable, of thermostat
sensors - S4% (100%=S4, 0%=S3)
1-2
r15
1
1
1
1
1
1
1
1
1 0 %
100 %
100
Time between melt periods
1-2
r16
1
1
1
1
1
1
1
1
1 0 hrs
10 hrs
1
Duration of melt periods
1-2
r17
1
1
1
1
1
1
1
1
1 0 min.
30 min.
5
Temperature setting for thermostat band 2.
As differential use r01
0-2
r21
1
1
1
1
1
1
1
1
1 -50°C
50°C
2
Definition and weighting, if applicable, of thermostat
sensors when night cover is on (100%=S4, 0%=S3)
1-2
r61
1
1
1
1
1
1
1
1
1 0 %
100 %
100
Heat function
Neutral zone between refrigeration and heat function
1-2
r62
1
1 0 K
50 K
5
Time delay when switching from refrigeration to heat
function
1-2
r63
1
1 0 min.
240 min.
240
Food type: use settings listed in table
1-2*
r89
1
1
1
1
1
1
1
1
1 0
5
0
Min. limit for S4 temperature
1-2
r98
1
1
1
1
1
1
1
1
1 -50°C
50°C
-50
Alarms
Delay for temperature alarm
1-2
A03
1
1
1
1
1
1
1
1
1 0 min.
240 min.
30
Delay for door alarm
1-2
A04
1
1
1
1
1
1
1
1
1 0 min.
240 min.
60
Delay for temperature alarm after defrost
1-2
A12
1
1
1
1
1
1
1
1
1 0 min.
240 min.
90
High alarm limit for thermostat 1
1-2
A13
1
1
1
1
1
1
1
1
1 -50°C
50°C
8
Low alarm limit for thermostat 1
1-2
A14
1
1
1
1
1
1
1
1
1 -50°C
50°C
-30
High alarm limit for thermostat 2
1-2
A20
1
1
1
1
1
1
1
1
1 -50°C
50°C
8
Low alarm limit for thermostat 2
1-2
A21
1
1
1
1
1
1
1
1
1 -50°C
50°C
-30
Alarm time delay or signal on the DI1 input
1-2
A27
1
1
1
1
0 min.
240 min.
30
Alarm time delay or signal on the DI2 input
1-2
A28
1
1
1
1
1
1
1
1
1 0 min.
240 min.
30
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
1-2
A36
1
1
1
1
1
1
1
1
1 0 %
100 %
100
Compressor
Min. ON-time
1-2
c01
1
1
1
1
1
1 0 min.
30 min.
0
Min. OFF-time
1-2
c02
1
1
1
1
1
1 0 min.
30 min.
0
Time delay for cut-in of comp. 2
1-2
c05
1
1 0 sec
999 sec
5
Switch mode for 2 compressor operation.
= 1 sequentially. = Cyclic 2
1-2
c08
1
1 1
2
2
Defrost
© Danfoss | DCS (vt) | 2019.10
10 | AN300028324304en-000401