AK-PC 572 

Instructions RI8SR1ML © Danfoss 01/2019 

3

AKS 32R /
AKS 2050 /
MBS 8250

10-90% ratiometric

HIGH PRESSURE MODULE  

Address = 96

Supply voltage to high pressure module

The power supply can be taken from the main module. It is 
important that + is connected to +.

Battery

Ensure that the valve closes if there is no supply voltage.

Stepper valve 

FX ventil type CCMT. 
Connector:
5: WHITE
6: BLACK
7: RED
8: GREEN

Canbus

Data communication to the main module.

Sensor inputs

• Pt 1000 ohm, AKS 11 or  AKS 21.

Contact input AUX 2

Signal from oil level, 
or input for fan alarm or another alarm.

Relay output AUX 2

Activation of de-superheating or hot gas dump.

RECEIVER MODULE    

Address  = 97

Supply voltage to high pressure module

The power supply can be taken from the main module. It is 
important that + is connected to +.

Battery

Ensure that the valve closes if there is no supply voltage.

Stepper valve 

FX valve type CCMT. 
Connector:
5: WHITE
6: BLACK
7: RED
8: GREEN

Canbus

Data communication to the main module.
The section must be terminated using a 120 ohm resistor.

Contact input AUX 3

Signal from heat recovery, 
or input for fan alarm or another alarm.

Relay output AUX 3

Activation of heat recovery, 
or AUX 3 output for de-superheating or hot gas dump.

MAIN MODULE

AO - Analog output, 3 pcs. AO1, AO3, AO4

Must be used if using frequency converters or EC motors. 
Connect 24 V on N and L (separate power supply) Avoid earth 
fault current.
 - Use double-insulated transformer. The secondary side must 
not be earthed. 
Obtain 0-10 volts from terminals Com-AO1, N-AO3 and N-AO4. 
PAY ATTENTION TO THE POLARITY of N.
(AO3 and AO4 are galvanically isolated. AO1 is not).

AI - Analog inputs, 

Pressure transmitters, 4 pcs. AI1 - AI4

Temperature sensors, 4 pcs. AI5 - AI8

• Pt 1000 ohm, AKS 11 or AKS 21.

DI - Digital switch inputs, 8 pcs. DI1 - DI8

The connection may be a shut-down or interruption function. 
Select what is to be activated during configuration.
(DI3 can be used as an AUX1 input, but only if regulated with 2 
MT compressors).

Supply

24 V a.c. or d.c. Class II is required.

AK-PC 572 

17 VA

EXD 316, HP 

10 VA

EXD 316,  rec 

10 VA

Stepper valve, HP  _ _VA
Stepper valve rec.  _ _VA

Canbus

Communication to the high pressure module and to the receiver 
module
"L" to "L" and "H" to "H" 
A jumper must be connected between "H" and "R".
Terminate on the receiver module with a resistance of 120 ohm. 
If mounting an external display, the termination must be done 
differently. See next page.

Important!
In order to set the addresses 96 and 97, you must follow the re-
commended procedure. See next page.

Modbus

It is important that the installation of the data communication 
cable is carried out correctly. See separate literature, no. RC8AC.
Remember termination at the termination points.

DO - Digital outputs, 8 pcs.  DO1-DO8

DO5 and DO6 are solid state relays. The outputs are used for 
connecting a Bitzer CRII. If a Bitzer CRII is not being connected, 
output DO6 can be used for activation of an oil valve.
The relays are de-rated to the specified values.
The alarm relay will be driven under normal operation and 
will drop in the event of alarms and insufficient voltage to the 
controller.  
(DO3 can be used as an AUX1 output, but only if regulated with 
2 MT compressors).

Summary of Contents for 080G0294

Page 1: ...80G0320 24 V a c d c 17 VA EXD 316 084B8042 24 V a c d c 10 VA 1 5 m 080G0075 3 0 m 080G0076 MMIGRS2 080G0294 RI8SR1ML 2019 01 IP 20 20 60 C 0 140 F RH max 90 non condensing AK PC 572 17 VA EXD 316 HP...

Page 2: ...cm Cables longer than 3 m at the DI input should be avoided Connections DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5...

Page 3: ...10 volts from terminals Com AO1 N AO3 and N AO4 PAY ATTENTION TO THE POLARITY of N AO3 and AO4 are galvanically isolated AO1 is not AI Analog inputs Pressure transmitters 4 pcs AI1 AI4 Temperature se...

Page 4: ...5 Wait 5 seconds 6 Receiver module Mount the terminal with power supply Wait 5 seconds All modules now have power supply and the two modules each have their own address 96 for the HP module 97 for th...

Page 5: ...cm Cabos de extens o superior a 3 m na entrada DI devem ser evitados Conex es DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Iof...

Page 6: ...dor com isolamento duplo O lado se cund rio n o deve ser aterrado Obtenha 0 10 volts dos terminais Com AO1 N AO3 eN AO4 PRESTE ATEN O POLARIDADE de N AO3 e AO4 s o isolados galvanicamente AO1 n o AI E...

Page 7: ...te de alimenta o 5 Aguarde 5 segundos 6 M dulo receptor Monte o terminal com a fonte de alimen ta o Aguarde 5 segundos Agora todos os m dulos t m uma fonte de alimenta o e cada um dos dois m dulos tem...

Page 8: ...halten Bei DI Eing ngen Kabel l nger als 3 m vermeiden Anschluss DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5 mA 6 A...

Page 9: ...Versorgungsspannung an Vermeiden Sie einen Erdschlussstrom Verwenden Sie doppelt isolierte Transformatoren Die se kund re Seite darf nicht geerdet werden 0 10 Volt erhalten Sie von den Klemmen Com AO...

Page 10: ...mit der Ver sorgungsspannung an 5 Warten Sie 5 Sekunden 6 Empf ngermodul Schlie en Sie die Klemme mit der Ver sorgungsspannung an Warten Sie 5 Sekunden Alle Module werden jetzt mit Spannung versorgt u...

Page 11: ...aute tension et de signal C bles sup rieurs 3 m l entr e DI doivent tre vit s Raccordements DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A...

Page 12: ...ation Le c t secon daire ne doit pas tre mis la terre Obtenir 0 10 V des bornes Com AO1 N AO3 et N AO4 VEILLER LA POLARIT DE N AO3 et AO4 sont isol s galvaniquement pas AO1 AI Entr es analogiques 4 tr...

Page 13: ...al est bien teint 4 HP module Monter la borne avec alimentation lectrique 5 Attendre 5 secondes 6 Module r cepteur Monter la borne avec l alimentation Attendre 5 secondes Tous les modules sont mainten...

Page 14: ...se al Cables de m s de 3 m en la entrada DI deben evitarse Conexiones DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5 mA...

Page 15: ...independiente Evite la corriente de fallo a tierra Utilice un transformador con aislamiento doble El lado secun dario no debe conectarse a tierra Obtenga 0 10 V de los terminales Com AO1 N AO3 y N AO4...

Page 16: ...limentaci n 3 Compruebe que el interruptor principal est en la posici n de desconexi n 4 M dulo HP monte el terminal con alimentaci n el ctrica 5 Espere cinco segundos 6 M dulo receptor monte el termi...

Reviews: