19
INSTALLATION INSTRUCTIONS
Step 3: Flare pipe ends
Proper fl aring is essential to achieve an airtight seal.
1. After removing burrs from the cut pipe, seal the ends with PVC tape to prevent foreign materials from
entering the pipe.
2. Sheath the pipe with insulating material.
3. Place fl are nuts on both ends of the pipe. Make sure they are facing in the right direction as they can-
not be removed or adjusted after fl aring.
4. Remove the PVC tape from the ends of the pipe when ready to perform fl aring work.
5. Clamp fl are form on the end of the pipe. The end of the pipe must extend beyond the edge of the fl are
form in accordance with the dimensions shown in the table and image below.
6. Place fl aring tool onto the form.
7. Turn the handle of the fl aring tool clockwise until the pipe is fully fl ared.
8. Remove the fl aring tool and fl are form and then inspect the end of the pipe for cracks and even fl aring.
PIPING EXTENSION BEYOND FLARE FORM
Outer Pipe Diameter (mm)
Dimension A Minimum (mm)
Dimension A Maximum (mm)
Ø 6.35 (Ø 0.25 in)
0.7 (0.0275 in)
1.3 (0.05 in)
Ø 9.52 (Ø 0.375 in)
1.0 (0.04 in)
1.6 (0.063 in)
Ø 12.7 (Ø 0.5 in)
1.0 (0.04 in)
1.8 (0.07 in)
Ø 16 (Ø 0.63 in)
2.0 (0.078 in)
2.2 (0.086 in)
Summary of Contents for DAS120GBHWDB
Page 4: ...3 INSTALLATION INSTRUCTIONS INSTALLATION SUMMARY INDOOR UNIT ...
Page 5: ...4 INSTALLATION INSTRUCTIONS INSTALLATION SUMMARY INDOOR UNIT L1 L2 S ...
Page 30: ...29 RÉSUMÉ DE L INSTALLATION UNITÉ INTÉRIEURE INSTRUCTIONS D INSTALLATION ...
Page 31: ...30 RÉSUMÉ DE L INSTALLATION UNITÉ INTÉRIEURE INSTRUCTIONS D INSTALLATION ...
Page 56: ...55 RESUMEN DE LA INSTALACIÓN UNIDAD INTERIOR INSTRUCCIONES DE INSTALACIÓN ...
Page 57: ...56 RESUMEN DE LA INSTALACIÓN UNIDAD INTERIOR INSTRUCCIONES DE INSTALACIÓN ...