Important Safety Information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS!

Information on servicing
1.  Checks to the area: 

Prior to beginning work on systems containing fl ammable refrigerants, safety 

checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating 
system, the following precautions shall be complied with prior to conducting work on the system.

2. Work procedure: 

Work shall be undertaken under a controlled procedure so as to minimize the risk of 

a fl ammable gas or vapour being present while the work is being performed.

3.  General work area: 

All maintenance staff and others working in the local area shall be instructed on 

the nature of work being carried out. Work in confi ned spaces shall be avoided. The area around the 
work space shall be sectioned off. Ensure that the conditions within the work area have been made safe 
by removing all fl ammable material.

4.  Checking for the presence of refrigerant:

 The area shall be checked with an appropriate refrigerant 

detector prior to and during work to ensure the technician is aware of potentially fl ammable 
atmospheres. Ensure that the leak detection equipment being used is suitable for use with fl ammable 
refrigerants, i.e. non-sparking, adequately sealed and intrinsically safe.

5.  Presence of fi re extinguisher:

 If any hot work is to be conducted on the refrigeration equipment or 

any associated parts, appropriate fi re extinguishing equipment shall be available to hand. Have a dry 
powder or C0

2

 fi re extinguisher adjacent to the work area.

6.  No ignition sources: 

No person carrying out work in relation to a refrigeration system which involves 

exposing any pipe work that contains or has contained fl ammable refrigerant shall use any sources 
of ignition in such a manner that it may lead to risk of fi re or explosion. All possible ignition sources 
including cigarette smoking, should be kept suffi ciently far away from the site of installation, repairing, 
removing and disposal during which fl ammable refrigerant can possibly be released to the surrounding 
space. Prior to work taking place, the area around the equipment is to be surveyed to make sure there 
are no fl ammable hazards or ignition risks. No smoking signs shall be displayed.

7. Ventilated area: 

Ensure that the area is in the open or that it is adequately ventilated before breaking 

into the system or conducting any hot work. A degree of ventilation shall continue during the period 
that the work is carried out. The ventilation should safely disperse any released refrigerant and 
preferable expel it externally into the atmosphere.

8.  Checks to the refrigeration equipment: 

Where electrical components are being changed, they shall 

be fi t for the purpose and to the correct specifi cation. At all times the manufacturer’s maintenance and 
service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for 
assistance. The following checks shall be applied to installations using fl ammable refrigerants:
•  The charge size is in accordance with the room size within which the refrigerant containing parts 

are installed. 

•  The ventilation machinery and outlets are operating adequately and are not obstructed.
•  If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the 

presence of refrigerant.

•  Marking to the equipment continues to be visible and legible. Markings and signs that become 

illegible must be corrected.

•  Refrigeration pipe or components are installed in a position where they are unlikely to be exposed 

to any substance which may corrode refrigerant containing components, unless the components are 
constructed of materials which are inherently resistant to being corroded or are suitable protected 
against being corroded.

9.  Checks to electrical devices: 

Repair and maintenance to electrical components shall include initial 

safety checks and component inspection procedures. If a fault exists that could compromise safety, then 
no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot 
be corrected immediately but it is necessary to continue operation, an adequate temporary solution 
shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial 
safety checks shall include:
•  That capacitors are discharged. This shall be done in a safe manner to avoid possibility of sparking.
•  That no live electrical components and wiring are exposed while charging, recovering or purging 

the system.

•  That there is continuity of earth bonding.

Summary of Contents for DAC060EB6WDB

Page 1: ...Marca comerciales de Danby Products Danby Products Limited Guelph Ontario Canada N1H 6Z9 Danby Products Inc Findlay Ohio U S A 45840 www Danby com 2023 01 18 MODEL MOD LE MODELO DAC060EB6WDB AIR CONDI...

Page 2: ...TH WARRANTY EXTENSION after lling out a product survey at www danby com support product registration Need Help 1 Read your Owner s Manual for installation help troubleshooting and maintenance assistan...

Page 3: ...t If the refrigerant leaks and is exposed to an external ignition source there is a risk of re CAUTION Shows that the operation manual should be read carefully CAUTION Shows that service personnel sho...

Page 4: ...uch as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit Do not install the unit in a location that may be exposed to combustible fas as this could...

Page 5: ...ditioner with any solid state speed control device The appliance shall be installed in accordance with national wiring regulations Contact the authorized service technician for repair or maintenance o...

Page 6: ...zes their competence to handle refrigerants safely in accordance with an industry recognized assessment speci cation Servicing shall only be performed as recommended by the manufacturer Maintenance an...

Page 7: ...ards or ignition risks No smoking signs shall be displayed 7 Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any h...

Page 8: ...ect rating Replace components only with parts speci ed by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak Cabling Check that cabling will not be su...

Page 9: ...complete if not already labeled Extreme care shall be taken not to over ll the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested...

Page 10: ...g the equipment that is at hand and shall be suitable for the recovery of ammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall...

Page 11: ...re condensation cannot drip on pedestrians or neighboring properties Provide suf cient clearance around the appliance to allow ample air circulation The rear of the appliance should be outdoors it sho...

Page 12: ...dow sash down until it rests just behind the front ange of the L shaped mounting bracket Expand the side curtains on each side and secure the top of the frames to the window sash using one 13 mm 1 2 s...

Page 13: ...s up to 10 hours and then in 1 hour increments up to 24 hours 6 Display Panel Displays the set temperature the ambient temperature and the timer settings To change the temperature scale being displaye...

Page 14: ...ck the remote control and prevent the settings from being inadvertently changed TEMP 1 2 3 4 5 6 7 8 9 10 11 12 13 REMOTE CONTROL BATTERIES The remote control requires two AAA alkaline batteries inclu...

Page 15: ...n between the equipment and receiver 3 Connect the equipment into an outlet on a circuit different from that to which the receiver is connected 4 Consult the dealer or an experienced radio TV technici...

Page 16: ...ndicate that it has received a signal from the remote If the appliance does not receive a signal from the remote during any 7 minute interval it will beep to indicate that the follow me mode has ended...

Page 17: ...ws to select the desired amount of time before the appliance should turn off The appliance will run in the currently selected mode 3 The time selected will appear on the display panel and will count d...

Page 18: ...error ES Evaporator temperature sensor error E4 Display board communication error Lo Room temperature is lower than 0 C 32 F HI Room temperature is higher than 37 C 99 F CLEANING To avoid possible el...

Page 19: ...utdoor temperatures are below 18 3 C 65 F frost may form when the air conditioner is in cooling mode Switch the air conditioner to fan only mode until the frost melts Air conditioner will not operate...

Page 20: ...669 Findlay Ohio U S A 45840 Telephone 419 425 8627 FAX 419 425 8629 04 09 1 800 263 2629 Warranty Service In home Transportation charges to and from the service location are not protected by this war...

Page 21: ...rempli une enqu te sur les produits l adresse www danby com support product registration Besoin d assistance 1 Lisez votre manuel du propri taire pour obtenir de l aide l installation au d pannage et...

Page 22: ...ne source d allumage externe il existe un risque d incendie MISE EN GARDE Indique que le manuel d utilisation doit tre lu attentivement MISE EN GARDE Indique que le personnel de service doit manipuler...

Page 23: ...elle qu une salle de bain ou une buanderie Une exposition excessive l eau peut provoquer un court circuit des composants lectriques N installez pas l unit dans un endroit qui pourrait tre expos des fa...

Page 24: ...contr le de vitesse semi conducteurs L appareil doit tre install conform ment aux r glementations nationales en mati re de c blage Contactez le technicien de service agr pour la r paration ou l entret...

Page 25: ...rig rants en toute s curit conform ment une sp ci cation d valuation reconnue par l industrie L entretien ne doit tre effectu que selon les recommandations du fabricant La maintenance et les r paratio...

Page 26: ...lit ou de risque d in ammation Aucun signe de fumer ne doit tre af ch 7 Zone ventil e Assurez vous que la zone est l air libre ou qu elle est correctement ventil e avant de p n trer dans le syst me ou...

Page 27: ...es par le fabricant D autres pi ces peuvent provoquer l in ammation de r frig rant dans l atmosph re par une fuite Le c blage V ri ez que le c blage ne sera pas soumis l usure la corrosion une pressio...

Page 28: ...st me de r frig ration Avant de recharger le syst me il doit tre test sous pression avec OFN Le syst me doit tre soumis un test d tanch it la n du chargement mais avant la mise en service Un contr le...

Page 29: ...ipement disponible et doit tre adapt la r cup ration des r frig rants in ammables En outre un jeu de balances talonn es doit tre disponible et en bon tat de fonctionnement Les exibles doivent tre comp...

Page 30: ...s le mur Assurez vous que la fen tre et le cadre sont structurellement sains et exempts de bois sec ou pourri Installez le climatiseur dans une fen tre sur un c t du b timent qui favorise plus d ombre...

Page 31: ...up rieure jusqu ce qu il repose juste derri re la bride avant du support de montage en forme de L D veloppez les rideaux lat raux de chaque c t et xez le haut des cadres au ch ssis de fen tre l aide d...

Page 32: ...ments de 30 minutes jusqu 10 heures puis en incr ments de 1 heure jusqu 24 heures 6 Panneau d af chage Af che la temp rature r gl e la temp rature ambiante et les r glages de la minuterie Pour changer...

Page 33: ...e 13 Bouton de verrouillage Appuyez simultan ment sur les touches C F et la minuterie pour verrouiller la t l commande et viter que les r glages ne soient modi s par inadvertance PILES DE LA T L COMMA...

Page 34: ...r 3 Connectez l quipement une prise sur un circuit diff rent de celui auquel le r cepteur est connect 4 Consultez le revendeur ou un technicien radio TV exp riment pour obtenir de l aide Les changemen...

Page 35: ...e oit pas de signal de la t l commande pendant un intervalle de 7 minutes il mettra un bip pour indiquer que le mode suivez moi est termin La distance maximale pour la fonction suivez moi est de 8 m t...

Page 36: ...u panneau de commande 2 Utilisez les ches vers le haut et vers le bas pour s lectionner la dur e souhait e avant l extinction de l appareil L appliance fonctionnera dans le mode actuellement s lection...

Page 37: ...rateur E4 Erreur de communication de la carte d af chage Lo La temp rature ambiante est inf rieure 0 C 32 F HI La temp rature ambiante est sup rieure 37 C 99 F NETTOYAGE Pour viter tout risque d lectr...

Page 38: ...se former lorsque le climatiseur est en mode refroidissement Mettez le climatiseur en mode ventilateur uniquement jusqu ce que le givre fonde Le climatiseur ne fonctionnera pas La che n est pas compl...

Page 39: ...rts par la pr sente garantie et doivent tre acquitt s par l acheteur Pendant les premiers vingt quatre 24 mois toutes les pi ces fonctionnelles de ce produit qui s av rent d fectueuses seront r par es...

Page 40: ...MESES despu s de completar una encuesta sobre el producto en www danby com support product registration Necesitas ayuda 1 Lea el manual del propietario para obtener ayuda con la instalaci n resoluci...

Page 41: ...l de servicio debe manipular este equipo con referencia al manual de instalaci n PRECAUCI N Muestra que la informaci n est disponible como el manual de operaci n o el manual de instalaci n PRECAUCI N...

Page 42: ...a o o un lavadero Demasiada exposici n al agua puede provocar un cortocircuito en los componentes el ctricos No instale la unidad en un lugar que pueda estar expuesto a combustibles ya que esto podr a...

Page 43: ...ontrol de velocidad de estado s lido El aparato debe instalarse de acuerdo con las regulaciones nacionales de cableado Comun quese con el t cnico de servicio autorizado para la reparaci n o el manteni...

Page 44: ...eci caci n de evaluaci n reconocida por la industria El servicio solo se realizar seg n lo recomendado por el fabricante El mantenimiento y las reparaciones que requieran la asistencia de otro persona...

Page 45: ...riesgos de ignici n Se exhibir n carteles de no fumar 7 rea ventilada aseg rese de que el rea est al aire libre o que est adecuadamente ventilada antes de ingresar al sistema o realizar cualquier tra...

Page 46: ...solo con piezas especi cadas por el fabricante Otras partes pueden provocar la ignici n del refrigerante en la atm sfera debido a una fuga Cableado Compruebe que el cableado no est sujeto a desgaste...

Page 47: ...tado Se debe tener mucho cuidado de no sobrecargar el sistema de refrigeraci n Antes de recargar el sistema se someter a prueba de presi n con OFN El sistema debe ser probado contra fugas al nalizar l...

Page 48: ...ue se encuentra a mano y debe ser adecuado para la recuperaci n de refrigerantes in amables Adem s un conjunto de balanzas calibradas estar disponible y en buen estado de funcionamiento Las mangueras...

Page 49: ...Aseg rese de que la ventana y el marco est n estructuralmente rmes y libres de madera seca o podrida Instale el aire acondicionado en una ventana en un costado del edi cio que favorezca m s sombra que...

Page 50: ...hasta que descanse justo detr s de la brida delantera del soporte de montaje en forma de L Expanda las cortinas laterales en cada lado y asegure la parte superior de los marcos al marco de la ventana...

Page 51: ...o en incrementos de 1 hora hasta 24 horas 6 Panel de visualizaci n Muestra la temperatura ajustada la temperatura ambiente y los ajustes del temporizador Para cambiar la escala de temperatura que se e...

Page 52: ...Se utiliza para con gurar la funci n de ahorro de energ a 13 Bot n de bloqueo Presione el bot n C F y el bot n del temporizador al mismo tiempo para bloquear el control remoto y evitar que la con gura...

Page 53: ...una toma de un circuito diferente al que est conectado el receptor 4 Consulte al distribuidor o a un t cnico de radio TV experimentado para obtener ayuda Los cambios o modi caciones no aprobados por l...

Page 54: ...puede utilizar para conservar energ a durante las horas de dormir Cuando se selecciona la temperatura establecida aumentar en 1 C 2 F cada media hora durante una hora completa El aparato mantendr la...

Page 55: ...arriba y hacia abajo para seleccionar la cantidad de tiempo deseada antes de que el aparato se apague El dispositivo se ejecutar en el modo seleccionado actualmente 3 El tiempo seleccionado aparecer...

Page 56: ...temperatura ambiente ES Error del sensor de temperatura del evaporador E4 Error de comunicaci n de la placa de visualizaci n Lo la temperatura ambiente es inferior a 0 C 32 F HI la temperatura ambien...

Page 57: ...onador de aire est en modo de refrigeraci n Cambie el aire acondicionado al modo de solo ventilador hasta que la escarcha se derrita El aire acondicionado no funcionar El enchufe no est completamente...

Page 58: ...sulte defectuosa incluyendo cualquier sistema sellado ser reparado o reemplazado a opci n del fabricante sin cargo para el comprador original P ngase en contacto con el distribuidor donde adquiri el e...

Page 59: ...___________________ __________________________________________________________________________________________ _________________________________________________________________________________________...

Page 60: ...___________________ __________________________________________________________________________________________ _________________________________________________________________________________________...

Reviews: