Important Safety Information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Decommissioning

Before carrying out this procedure, it is essential 

that the technician is completely familiar with the 

equipment in all its detail. It is recommended good 

practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and 

refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It 

is essential that electrical power is available before 

the task is commenced.

A.  Become familiar with the equipment and its 

operation.

B.  Isolate system electrically.

C.  Before attempting the procedure ensure that:

•  Mechanical handling equipment is available 

if required for handling refrigerant cylinders.

•  All personal protective equipment is 

available and being used correctly.

•  The recovery process is supervised at all 

times by a competent person.

•  Recovery equipment and cylinders conform 

to the appropriate standards.

D.  Pump down refrigerant system, if possible.

E.  If a vacuum is not possible, make a manifold so 

that refrigerant can be removed from various 

parts of the system.

F.  Make sure that cylinder is situated on the scales 

before recovery takes place.

G.  Start the recovery machine and operate in 

accordance with the manufacturer’s instructions.

H.  Do not overfi ll cylinders. No more than 80% 

volume liquid charge.

I.  Do not exceed the maximum working pressure 

of the cylinder, even temporarily.

J.  When the cylinders have been fi lled correctly 

and the process is completed, make sure that the 

cylinders and the equipment are removed from 

the site promptly and all isolation valves on the 

equipment are closed off.

K.  Recovered refrigerant shall not be charged into 

another refrigeration system unless it has been 

cleaned and checked.

Labeling

Equipment shall be labeled stating that it has been 

decommissioned and emptied of refrigerant. The 

label shall be dated and signed. Ensure that there 

are labels on the equipment stating the equipment 

contains fl ammable refrigerant.

Recovery

When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended 

good practice that all refrigerants are removed 

safely.

When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovers cylinders 

are employed. Ensure that the correct number of 

cylinders for holding the total system charge are 

available. All cylinders to be used are designed 

for the recovered refrigerant and labeled for that 

refrigerant, i.e. special cylinders for the recovery 

of refrigerant. Cylinders shall be complete with 

pressure relief valve and associated shut-off valves 

in good working order. Empty recovery cylinders 

are evacuated and, if possible, cooled before 

recovery occurs.

The recovery equipment shall be in good working 

order with a set of instructions concerning the 

equipment that is at hand and shall be suitable for 

the recovery of fl ammable refrigerants. In addition, 

a set of calibrated weighing scales shall be 

available and in good working order. Hoses shall 

be complete with leak-free disconnect couplings 

and in good condition. Before using the recovery 

machine, check that is it in satisfactory working 

order, has been properly maintained and that any 

associated electrical components are sealed to 

prevent ignition in the event of a refrigerant leak. 

Consult the manufacturer if in doubt.

The recovered refrigerant shall be returned to the 

refrigerant supplier in the correct recovery cylinder 

and the relevant waste transfer note shall be 

arranged. Do not mix refrigerants in recovery units 

and especially not in cylinders. If compressors or 

compressor oils are to be removed, ensure that they 

have been evacuated to an acceptable level to make 

certain that fl ammable refrigerant does not remain 

within the lubricant. The evacuation process shall be 

carried out prior to returning the compressor to the 

suppliers. Only electric heating to the compressor 

body shall be employed to accelerate this process. 

When oil is drained form a system, it shall be 

carried out safely.

6

Summary of Contents for DAC050ME1WDB

Page 1: ...INDLAY OHIO USA 45840 OWNER S MANUAL MANUEL DU PROPRI TAIRE MANUAL DEL PROPIETARIO www Danby com AIR CONDITIONER Owner s Manual 1 14 CLIMATISEUR Manuel du propri taire 15 28 AIRE ACONDICIONADO Manual...

Page 2: ...TH WARRANTY EXTENSION after lling out a product survey at www danby com support product registration Need Help 1 Read your Owner s Manual for installation help troubleshooting and maintenance assistan...

Page 3: ...bove the power cord contains electrical and other technical data This appliance is not intended for use by persons including children whose physical sensory or mental capabilities may be different or...

Page 4: ...ant detector prior to and during work to ensure the technician is aware of potentially ammable atmospheres Ensure that the leak detection equipment being used is suitable for use with ammable refriger...

Page 5: ...recovering or purging the system That there is continuity of earth bonding Repairs to sealed components 1 During repairs to sealed components all electrical supplies shall be disconnected from the equ...

Page 6: ...d Extreme care shall be taken not to over ll the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but...

Page 7: ...hat there are labels on the equipment stating the equipment contains ammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good...

Page 8: ...f cient functioning Do not install the appliance where leakage of combustible gas is suspected This air conditioner is designed to evaporate condensation under normal conditions Under extremely hot or...

Page 9: ...om the carton containing the installation hardware kit necessary for the installation of your air conditioner Please check the contents of the hardware kit against the corresponding model check list p...

Page 10: ...nto the window Close the window securely The upper window should slide into the top mounting rail The air conditioner should be tiled by 1 4 to the outside to allow water to drain out the back of the...

Page 11: ...of cooling The lower numbers indicate warmer settings The higher numbers indicate colder settings 2 Program selector dial Used to select which program the appliance will run 3 OFF This setting will t...

Page 12: ...cloth if necessary Do not use gasoline benzene thinner or any other chemicals to clean this appliance as these substances can cause damage to the nish and deformation of plastic parts Never pour water...

Page 13: ...r will drain out of the unit and onto the ground and is why the unit should be installed on a slight downward tilt How much does it cost to run the unit Please refer to the energy guide Odors Odour is...

Page 14: ...e Inadequate support in window installation Water dripping inside Appliance is not properly angled to allow water to drain to the outside Water dripping outside On very hot or humid days dripping wate...

Page 15: ...669 Findlay Ohio U S A 45840 Telephone 419 425 8627 FAX 419 425 8629 04 09 1 800 263 2629 Warranty Service In home Transportation charges to and from the service location are not protected by this war...

Page 16: ...rempli une enqu te sur les produits l adresse www danby com support product registration Besoin d assistance 1 Lisez votre manuel du propri taire pour obtenir de l aide l installation au d pannage et...

Page 17: ...plosion Fluide frigorig ne in ammable utilis Ne pas endommager le circuit de r frig rant Assurez vous que les r parations sont effectu es par du personnel autoris par l usine a n de minimiser les domm...

Page 18: ...que le technicien est conscient des atmosph res potentiellement in ammables Assurez vous que l quipement de d tection des fuites utilis convient aux uides frigorig nes in ammables c est dire qu il ne...

Page 19: ...mise la terre R paration de composants scell s 1 Lors de la r paration de composants scell s toutes les alimentations lectriques doivent tre d branch es de l quipement utilis avant toute d pose de co...

Page 20: ...r me doit tre pris pour ne pas trop remplir le syst me de r frig ration Avant de recharger le syst me il doit tre test sous pression avec OFN Le syst me doit tre soumis un test d tanch it la n du char...

Page 21: ...sur l quipement indiquant que celui ci contient du r frig rant in ammable R cup ration Lorsque vous retirez du uide frigorig ne d un syst me que ce soit pour un entretien ou une mise hors service il e...

Page 22: ...pour assurer un fonctionnement ef cace N installez pas l appareil l o une fuite de gaz combustible est suspect e Ce climatiseur est con u pour vaporer la condensation dans des conditions normales Dans...

Page 23: ...tirez le sac en plastique du carton contenant le mat riel n cessaire l installation de votre climatiseur Veuillez v ri er le contenu du kit mat riel par rapport la liste de v ri cation du mod le corre...

Page 24: ...fen tre en toute s curit La fen tre sup rieure doit glisser dans le rail de montage sup rieur Le climatiseur doit tre carrel de 1 4 vers l ext rieur pour permettre l eau de s couler par l arri re de...

Page 25: ...auds Les nombres plus lev s indiquent des r glages plus froids 2 Molette de s lection de programme Utilis e pour s lectionner le programme que l appareil ex cutera 3 OFF Ce r glage teindra l appareil...

Page 26: ...ou de tout autre produit chimique pour nettoyer cet appareil car ces substances peuvent endommager la nition et la d formation des pi ces en plastique Ne versez jamais d eau directement sur l appareil...

Page 27: ...sur le sol et c est pourquoi l unit doit tre install e avec une l g re inclinaison vers le bas Combien cela co te t il de faire fonctionner l unit Veuillez vous r f rer au guide nerg tique Les odeurs...

Page 28: ...de fen tres L eau d gouline l int rieur L appareil n est pas correctement inclin pour permettre l eau de s couler vers l ext rieur L eau d gouline l ext rieur Les jours tr s chauds ou humides il est...

Page 29: ...rts par la pr sente garantie et doivent tre acquitt s par l acheteur Pendant les premiers vingt quatre 24 mois toutes les pi ces fonctionnelles de ce produit qui s av rent d fectueuses seront r par es...

Page 30: ...MESES despu s de completar una encuesta sobre el producto en www danby com support product registration Necesitas ayuda 1 Lea el manual del propietario para obtener ayuda con la instalaci n resoluci...

Page 31: ...STRUCCIONES DE SEGURIDAD REQUERIMIENTOS DE SEGURIDAD PELIGRO Riesgo de incendio o explosi n Refrigerante in amable utilizado No da e el circuito de refrigerante Aseg rese de que el servicio sea realiz...

Page 32: ...nte el trabajo para garantizar que el t cnico tenga conocimiento de las atm sferas potencialmente in amables Aseg rese de que el equipo de detecci n de fugas que se est utilizando sea adecuado para el...

Page 33: ...ientras se est cargando recuperando o purgando el sistema Que hay continuidad de la uni n de la tierra Reparaciones a componentes sellados 1 Durante las reparaciones de componentes sellados todos los...

Page 34: ...ener mucho cuidado de no sobrecargar el sistema de refrigeraci n Antes de recargar el sistema se someter a prueba de presi n con OFN El sistema debe ser probado contra fugas al nalizar la carga pero a...

Page 35: ...o que indiquen que el equipo contiene refrigerante in amable Recuperaci n Cuando se retira refrigerante de un sistema ya sea para servicio o cierre se recomienda que todos los refrigerantes se elimine...

Page 36: ...a la luz solar directa es aconsejable proporcionar un toldo de sombra para garantizar un funcionamiento e ciente No instale el aparato donde se sospeche una fuga de gas combustible Este acondicionado...

Page 37: ...stico de la caja que contiene el kit de hardware de instalaci n necesario para la instalaci n de su aire acondicionado Veri que el contenido del kit de hardware con la lista de veri caci n del modelo...

Page 38: ...a ventana superior debe deslizarse dentro del riel de montaje superior El acondicionador de aire debe tener una baldosa de 1 4 hacia el exterior para permitir que el agua se drene por la parte posteri...

Page 39: ...eros m s bajos indican ambientes m s c lidos Los n meros m s altos indican entornos m s fr os 2 Dial selector de programa se utiliza para seleccionar el programa que ejecutar el aparato 3 OFF Esta con...

Page 40: ...o No utilice gasolina benceno diluyente o cualquier otro producto qu mico para limpiar este aparato ya que estas sustancias pueden da ar el acabado y la deformaci n de las piezas de pl stico Nunca vie...

Page 41: ...o Esta agua se drenar fuera de la unidad y caer al suelo y es por eso que la unidad debe instalarse con una ligera inclinaci n hacia abajo Cu nto cuesta hacer funcionar la unidad Consulte la gu a de e...

Page 42: ...ado en la instalaci n de ventanas Agua goteando por dentro El electrodom stico no tiene un ngulo adecuado para permitir que el agua se drene hacia el exterior Agua goteando afuera En d as muy caluroso...

Page 43: ...sulte defectuosa incluyendo cualquier sistema sellado ser reparado o reemplazado a opci n del fabricante sin cargo para el comprador original P ngase en contacto con el distribuidor donde adquiri el e...

Page 44: ...mited Guelph ON Canada N1H 6Z9 Danby Products Inc Findlay Ohio USA 45840 Trademarks of Danby Products Limited and or its subsidiaries Marques de commerce de Danby Products Limited et ou de ses filiale...

Reviews: