background image

Important Safeguards

When using electrical equipment, basic safety precau-

tions should always be followed including the 
following:

READ AND FOLLOW ALL
SAFETY INSTRUCTIONS

All servicing should be performed by qualified personnel only.
To prevent high voltage from being on red & yellow output
leads prior to installation, battery connector must be open. Do
not join battery connector until installation is complete and AC
power is supplied to the emergency ballast.
Do not use this equipment outdoors.
This product is designed for use in UL Listed indoor fixtures
except in air handling, heated air outlet or hazardous locations.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Do not mount near open flames or sparks.
Do not install equipment in areas of excessive moisture.
Do not use this equipment for other than intended use.  
Do not attempt to service battery. Contact manufacturer for
information on service.

This product is for use with most 20W through 40W single pin
or bipin fluorescent lamps, including standard, energy saving,
circline, U-shaped, and most 26W-39W rapid-start (4pin), long
compact fluorescent lamps.
An unswitched AC power source is required. (120 or 277 VAC)
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
This emergency ballast is for factory or field installation in
either the ballast channel or on top of the fixture.
To reduce the risk of electrical shock, disconnect both normal
and emergency power supplies before servicing by discon-
necting all AC inputs to the fixture and by disconnecting the
battery.

SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

WARNING

To prevent high voltage from being present on red and

yellow output leads prior to installation, battery connector must

be open.  Do not join battery connector until installation is

complete and AC power is supplied to the emergency ballast.

NOTE

: Make sure that the necessary branch circuit

wiring is available.  An unswitched source of power is required.

The emergency ballast must be fed from the same branch cir-

cuit as the AC ballast.

1. Disconnect AC power from the fixture.  Remove the

ballast channel cover and install the emergency ballast either

in the ballast channel (see illustrations 1&2) or on top of the fix-

ture. *(See illustration 3).

2. Select the appropriate wiring diagram to

connect the emergency ballast to the AC ballast and lamp.

Make sure all connections are in accordance with the National

Electrical Code and any local regula

tions.

EMERGENCY FLUORESCENT

LIGHTING BALLAST

INSTALLATION AND OPERATING

INSTRUCTIONS

CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR

DISPOSED OF PROPERLY

.

U

L

LISTED

LISTED

Ni - Cd

 BALLAST CHANNEL

COVER

TEST SWITCH

CHARGING INDICATOR

LIGHT

EMERGENCY

BALLAST

ILLUSTRATION 1

PAGE 1

Item No. 00418I

®

Worldwide 4 LLC

D450

BY

Summary of Contents for D450

Page 1: ...cy ballast is for factory or field installation in either the ballast channel or on top of the fixture To reduce the risk of electrical shock disconnect both normal and emergency power supplies before servicing by discon necting all AC inputs to the fixture and by disconnecting the battery SAVE THESE INSTRUCTIONS INSTALLATION INSTRUCTIONS WARNING To prevent high voltage from being present on red a...

Page 2: ...Connection Point To Reduce The Risk Of Electric Shock Disconnect Both The Branch Circuit Or Fuses And Emergency Power Supplies Before Servicing TROFFER STYLE FIXTURE EMERGENCY BALLAST BALLAST CHANNEL COVER 7 8 PUNCH PLASTIC TUBING PLEASE CUT TO NECESSARY LENGTH CHARGING INDICATOR LIGHT FIXTURE LENS LEADS TO CHARGING INDICATOR LIGHT 7 8 BUSHING INSERTED INTO BALLAST CHANNEL COVER 1 2 WHITE BUSHING ...

Page 3: ...s rec ommended 1 Visually inspect the charging indicator light monthly It should be illuminated 2 Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds One lamp should operate at reduced illumination 3 Conduct a 90 minute dischare test once a year either on or two lamps should operate at reduced illumination for at least 90 minutes D450 EMERGENCY FLUORESCENT L...

Page 4: ... YELLOW RED RED ORANGE BLACK WHITE VIOLET BROWN RED WHITE BATTERY CONNECTOR 277V 120V COM INDICATOR LIGHT EMERGENCY BALLAST AC BALLAST LAMP 1 LAMP 2 EMERGENCY TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS D TWO 2 LAMP LEAD LAG INSTANT START SLIMLINE BALLAST LINE BLACK WHITE BLUE BLUE BLUE WHITE YEL GREEN YELLOW RED RED ORANGE BLACK WHITE VIOLET BROWN RED WHITE BATTERY CONNECTOR 277V 120V COM...

Page 5: ...WHITE YEL GREEN YELLOW RED RED RED ORANGE BLACK WHITE VIOLET BROWN RED WHITE BATTERY CONNECTOR 277V 120V COM INDICATOR LIGHT EMERGENCY BALLAST AC BALLAST LAMP TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS G ONE 1 LAMP CIRCLINE RAPID START BALLAST LINE BLACK BLUE WHITE BLUE BLUE BLUE WHITE YEL GREEN YELLOW RED RED RED ORANGE BLACK WHITE VIOLET BROWN RED WHITE BATTERY CONNECTOR 277V 120V COM I...

Page 6: ... LINE BLACK WHITE BLUE BLUE BLUE WHITE YEL GREEN YELLOW RED BLUE RED RED ORANGE BLACK WHITE VIOLET BROWN RED WHITE BATTERY CONNECTOR 277V 120V COM INDICATOR LIGHT EMERGENCY BALLAST AC BALLAST LAMP TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS J FOUR 4 LAMP INSTANT START ELECTRONIC BALLAST LAMP LAMP LAMP EMERGENCY YELLOW YELLOW BLUE BLUE WHITE YEL GREEN YELLOW RED ORANGE BLACK WHITE VIOLET BR...