Electrical Installation
17
Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article 250-32 of the
National Electrical Code. If the installation in question meets all of the requirements of article 250-32,
the following guidelines must be observed:
Connect the grounding electrode cable at the local disconnect, never at the sign panel board.
A disconnect that opens all of the ungrounded phase conductors should be used.
The neutral and the ground conductors should be bonded in the sign panel board.
Refer to
Figure 18
below for installation details.
Power Connection
Incoming power is connected within the power termination enclosure. Complete the following steps to
terminate the hot and neutral wires at the termination block within the enclosure. Refer to
Drawing A-
154965
and the appropriate schematic for your display size.
1.
Access the enclosure by removing the left bottom two modules as described in
Section 3.5
.
2.
Route the power cables through the power conduit in the rear of the sign and to the enclosure.
3.
Connect the white neutral wire to neutral bus.
4.
If one power line is being terminated (120VAC), connect the black “hot” wire to L1. Install
jumper per Note 1 on
Drawing A-154965
.
5.
If two power lines are being terminated (120/240VAC). Connect the second “hot” wire to L2.
6.
Connect the green grounding wire to the grounding bus L1. Refer to
Figure 20
above.
Main Disconnect
The National Electrical Code requires the use of a lockable power disconnect near the display. Provide
a lockable disconnect switch (knife switch) at the display location so that all power lines can be
completely disconnected. Use a 3-conductor disconnect so that both hot lines and the neutral can all be
disconnected. The main disconnect should be mounted at or near the point of power supply connection
to the display. A main disconnect is to be provided for each supply circuit to the display.
The disconnecting means must be located in a direct line of sight from the display or outline lighting
that it controls. This requirement provides protection by enabling a worker to keep the disconnecting
means within view while working on the display.
Exception:
Disconnecting means that are capable of being locked in the open position may be located
elsewhere.
Figure 18:
Installation with only Neutral Conductor Provided
Summary of Contents for Galaxy AF-3165
Page 30: ...Electrical Installation 26 Figure 30 Signal Term Panel...
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......