Daitsu DOS-12KIDT Service Manual Download Page 9

      

 Air Conditioner Service Manual

7

seconds since the stop of compressor. 

2)  Auto fan control (heating) 

In heating mode (include in “I feel” mode) , fan speed is determined by 

į

t

 as the following: 

 

 

(3)  4-way valve control 

In heating mode, 4-way valve will power on ahead of compressor for 5 seconds, and cut off 

for 2 minutes  later than  compressor.  4-way  valve  will not  power off  unless the  machine to  be 

switched off, mode changed or on the process of defrosting. 

(4)  Defrosting 

Defrosting is controlled by the microprocessor. 

When one of the following conditions is satisfied, unit comes into defrosting: 

a.  Outdoor heat exchanger Temperature (OPT) is continuously less than 3

  while the unit runs 

for more than 40 minutes, and OPT is keeping under -6

  for more than 3 minutes. 

b.  Outdoor heat exchanger  Temperature  (OPT) is  continuously  less  than 3

  meanwhile  the 

unit  runs  for  more  than  80  minutes,  and  OPT  is  keeping  under  -4

  for  more  than  3 

minutes. 

c.  Outdoor heat exchanger Temperature (OPT) is continuously less than 3

  while the unit runs 

for  more  than  120  minutes,  and  OPT  is  keeping  below  -2

  for  more  than  3  minutes. 

Before  the  air  con  comes  into  defrosting,  compressor  running  frequency  drop  down  to  a 

lower frequency firstly, then the compressor shuts down. 

In defrosting, the  max. frequency of  compressor  is  F9  (a  little less    than  the  highest 

frequency ). In this period all protection function are available.

 

 

   

 
In defrosting, LED showing by winking. 

No matter what AC come into or out of defrosting, indoor fan motor speed is the same as Cold 

Air  Prevention  Control. 

While one  of  the  following  conditions  is  satisfied,  unit  comes  out  of  defrosting  and  shifts  to   

heating  mode: 

a.  Outdoor coil Temperature (OPT) 

ı

15

 

b.  The time of defrosting keeps for more than 10 minutes. 

(5) Indoor exchanger overheat protection 

When Indoor exchanger Temperature (IPT) is higher than 55

 

unit comes into indoor  exchanger 

RT

Ͳ

ST

į

t come down

 

į

t come up

 

High fan

 

Min fan

 

Low fan

 

Compressor   

ON   

OFF   
ON   
OFF   

ON   

OFF   

NORMAL   

800   

4-way valve   

Expansion valve   

Outdoor fan motor   

50S 

'HIURVWLQJWLPH ื

10Mins 

15S    15S   

10S 

Summary of Contents for DOS-12KIDT

Page 1: ...6 4 26 4 6 4 26 4 6 4 26 4 6 4 26 4 CONTENTS 1 Important Notice 2 Product Dimensions 3 Refrigeration cycle diagram 4 Operation details 5 Wiring diagram 6 Explosion view and parts 7 Precaution 8 Names...

Page 2: ...le for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modificatio...

Page 3: ...LU RQGLWLRQHU 6HUYLFH 0DQXDO 2 Product Dimensions Indoor Unit Outdoor Unit 0RGHO QGRRU XQLW 2XWGRRU XQLW 6 7 26 7 6 7 26 7 6 7 26 7 6 7 26 7 6 4 26 4 6 4 26 4 6 4 26 4 6 4 26 4...

Page 4: ...mm 4 0 75mm 4 0 75mm Capillary Capillary Electronic expansion valve Electronic expansion valve Gas Inches 3 8 3 8 3 8 1 2 Liquid Inches 1 4 1 4 1 4 1 4 Others m 9 16 15 23 20 35 27 45 m 25 25 25 25 m...

Page 5: ...y Compressor Accumulator Heat exchange condenser Heat exchange Evaporator 2 way valve Liquid side 3 way valve Gas side Cooling Heating Gas side 3 way valve Liquid side 2 way valve Heat exchange Evapor...

Page 6: ...in 10 seconds the remote controller is preset as Heat Pump automatically LOCK UNLOCK When you press the buttons MODE and TIMER at the same time the remote controller will be locked all buttons of the...

Page 7: ...r or load of compressor is abnormity the air conditioner will shut down and show error code 7 IPM module protection IPM module has high temperature over current protection itself if there is signal fe...

Page 8: ...it operates in cooling mode the set temperature ST is RT 2 After that t he system will operate in cooling mode with lowest fan speed for 30 minutes and then change to middle speed for 30seconds as a c...

Page 9: ...s c Outdoor heat exchanger Temperature OPT is continuously less than 3 while the unit runs for more than 120 minutes and OPT is keeping below 2 for more than 3 minutes Before the air con comes into de...

Page 10: ...indoor unit for function test NOTE Do not press the EMERGEMCY Operation switch during normal operation 8 AUTO RESTART Function Option While air conditioner is operating in one mode all of its operatio...

Page 11: ...z Outdoor failure display There is a LED on outdoor power board it blinks 1s ON and 1s OFF while compressor standby and it always light ON while compressor running If there is failure happened on ODU...

Page 12: ...pressor overheat fault compressor top switch 9 Short circuit open circuit fault of outdoor temperature sensor 10 Short circuit open circuit fault of outdoor heat exchanger temperature sensor 11 Short...

Page 13: ...on under over voltage category III conditions and these means must be incorporated in the fixed wiring in accordance with the wiring rules z The air conditioner must be installed by professional or qu...

Page 14: ...e an excessive accumulation of dust or waste on the inner parts of the device with possible subsequent failures z The user is responsible for having the appliance installed by a qualified technician w...

Page 15: ...r could contain gas oil or sulphur or near sources of heat z This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experi...

Page 16: ...2 Air filter 3 Special filter option 4 Display PCB 5 Vertical vane 6 Horizontal vane 7 Remote controller 8 Names of parts Outdoor unit No Name 8 Air outlet grille 9 Electronic box cover 10 2 way valve...

Page 17: ...J 0D OHQJWK P GGLWLRQDO UHIULJHUDQW DOFXODWLRQ J J P P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P Connecting cables 7KH SRZHU FRUG VKRXOG EH VHOHFWHG DFFRU...

Page 18: ...HVVLEOH OUTDOOR UNIT l R QRW LQVWDOO WKH RXWGRRU XQLW QHDU VRXUFHV RI KHDW VWHDP RU IODPPDEOH JDV l R QRW LQVWDOO WKH XQLW LQ WRR ZLQG RU GXVW SODFHV l R QRW LQVWDOO WKH XQLW ZKHUH SHRSOH RIWHQ SDVV 6...

Page 19: ...e flange through the hole in the wall to keep the latter intact and clean The hole must slope downwards towards the exterior Note Keep the drain pipe down towards the direction of the wall hole otherw...

Page 20: ...not bend the pipe more than three times at one point z When extending the rolled pipe straighten the pipe by unwinding it gently as shown in the picture 9 2 6Connections to the indoor unit 1 Remove th...

Page 21: ...ening procedures described for the indoor unit Note If the tightening torque is not sufficient there will probably be some leakage With excessive tightening torque there will also be some leakage as t...

Page 22: ...intaining or scrapping an air conditioner l When filling the combustible refrigerant any of your rude operations may cause serious injury or injuries to human body or bodies and object or objects l A...

Page 23: ...auge used for Refrigerant 22 can be used for Refrigerants R290 and R161 the pressure gauge used for R410A can be used for Refrigerant 32 Fire Extinguisher It is necessary to carry fire extinguisher s...

Page 24: ...ring the maintenance it is a must to immediately take forced ventilation and plug up the leak source l If the product is damaged to the extent that it is a must to open the refrigerating system for ma...

Page 25: ...it is a must to confirm that the refrigerating system has been drained and the system has been cleaned and ensure that there has been no refrigerant in the outdoor unit l It is necessary to close the...

Page 26: ...vacuating the affected personnel urgently from the location l It is necessary to inform near residents of evacuating for over 20 meters from the location make an alarm call set the emergency area and...

Reviews: