Daitsu DOS-12KIDT Service Manual Download Page 7

      

 Air Conditioner Service Manual

5

 

Electronic Controller 

1. 

Safety Protection

 

(1)  Time Delay for Safety protection 

z

 

3  minutes  delay  for  compressor  ---The  compressor  is  ceased  for  3minutes  before  restarting to 

balance  the  pressure  in  the  refrigeration  cycle  in  order  to  protect  the  compressor. 

z

 

2 minutes delay for 4-way valve---The 4-way valve will be ceased for 2 minutes late  after 

compressor to prevent the refrigerant-gas abnormal noise when the HEATING operation is 

OFF or switch to the other operation mode. 

(2)  Discharge temperature protection 

There is a temperature sensor on top of compressor, when temperature on top of  compressor 

exceeded  the  limit,  system  control  will  shut  down  the  compressor  and  the  display board will 

show the error code. 

(3)  Lower voltage protection 

When AC voltage 

”

158V and keep it for 10 seconds, unit will be shut down for protection. 

(4)  Over voltage protection 

When AC voltage 

•

260V, unit will be shut down and recover while AC

”

255V. 

(5)  Over current protection 

When the current of outdoor unit is overload, controller shut down the unit immediately and show 

error code. 

(6)  Compressor abnormity protection 

When compressor start on or in the process of  running, if there is no feedback to controller  or 

load  of  compressor  is  abnormity,  the  air  conditioner  will  shut  down,  and  show  error  code. 

(7) 

IPM 

module protection 

IPM module has high temperature & over current protection itself, if there is signal  feedback to 

IPM, the outdoor unit will shut down, LED on outdoor PCB will show the error  code. 

2. 

“Feel” Mode Operation 

(1)  When  the  “Feel”  mode  is  selected,  the  operation  mode  and  initial  temperature  set  are 

determined by the initial room temperature at start-up of the operation except to turn off the  air 

conditioner and operates it again. 

(2)  If the mode is change to “Feel” from other mode, the “Feel” mode doesn’t operate until 

compressor stop for more than 3 minutes. 

Mode

 

Initial Room Temperature

Initial Set Temperature

COOLING 

RT=26

 

23

 

DRY 

26

ഒ!

RT

•

20

 

           

  RT-2

 

HEATING for Heat Pump/ 

FAN for Cooling Only 

RT<20

 

                 

-

 

z

 

In the “Feel” mode, when the controller receives the up or down signal of temperature,  the  set 

temperature  can adjust by 1

  upper or lower. The biggest you can adjust by  2

  upper or lower. 

3. “COOLING” Mode Operation 

(1)  Compressor  frequency  control 

     

According to difference room temperature and set temperature (

¥

t = RT-ST

), running  frequency of 

compressor  is  controlled  by  electronic  controller.  When  room  temperature  is  much  higher  than  set 
temperature, the compressor will start at a high frequency, and as room temperature  goes down, the 
compressor running frequency will go down. When room temperature is lower than set temperature, 

Summary of Contents for DOS-12KIDT

Page 1: ...6 4 26 4 6 4 26 4 6 4 26 4 6 4 26 4 CONTENTS 1 Important Notice 2 Product Dimensions 3 Refrigeration cycle diagram 4 Operation details 5 Wiring diagram 6 Explosion view and parts 7 Precaution 8 Names...

Page 2: ...le for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modificatio...

Page 3: ...LU RQGLWLRQHU 6HUYLFH 0DQXDO 2 Product Dimensions Indoor Unit Outdoor Unit 0RGHO QGRRU XQLW 2XWGRRU XQLW 6 7 26 7 6 7 26 7 6 7 26 7 6 7 26 7 6 4 26 4 6 4 26 4 6 4 26 4 6 4 26 4...

Page 4: ...mm 4 0 75mm 4 0 75mm Capillary Capillary Electronic expansion valve Electronic expansion valve Gas Inches 3 8 3 8 3 8 1 2 Liquid Inches 1 4 1 4 1 4 1 4 Others m 9 16 15 23 20 35 27 45 m 25 25 25 25 m...

Page 5: ...y Compressor Accumulator Heat exchange condenser Heat exchange Evaporator 2 way valve Liquid side 3 way valve Gas side Cooling Heating Gas side 3 way valve Liquid side 2 way valve Heat exchange Evapor...

Page 6: ...in 10 seconds the remote controller is preset as Heat Pump automatically LOCK UNLOCK When you press the buttons MODE and TIMER at the same time the remote controller will be locked all buttons of the...

Page 7: ...r or load of compressor is abnormity the air conditioner will shut down and show error code 7 IPM module protection IPM module has high temperature over current protection itself if there is signal fe...

Page 8: ...it operates in cooling mode the set temperature ST is RT 2 After that t he system will operate in cooling mode with lowest fan speed for 30 minutes and then change to middle speed for 30seconds as a c...

Page 9: ...s c Outdoor heat exchanger Temperature OPT is continuously less than 3 while the unit runs for more than 120 minutes and OPT is keeping below 2 for more than 3 minutes Before the air con comes into de...

Page 10: ...indoor unit for function test NOTE Do not press the EMERGEMCY Operation switch during normal operation 8 AUTO RESTART Function Option While air conditioner is operating in one mode all of its operatio...

Page 11: ...z Outdoor failure display There is a LED on outdoor power board it blinks 1s ON and 1s OFF while compressor standby and it always light ON while compressor running If there is failure happened on ODU...

Page 12: ...pressor overheat fault compressor top switch 9 Short circuit open circuit fault of outdoor temperature sensor 10 Short circuit open circuit fault of outdoor heat exchanger temperature sensor 11 Short...

Page 13: ...on under over voltage category III conditions and these means must be incorporated in the fixed wiring in accordance with the wiring rules z The air conditioner must be installed by professional or qu...

Page 14: ...e an excessive accumulation of dust or waste on the inner parts of the device with possible subsequent failures z The user is responsible for having the appliance installed by a qualified technician w...

Page 15: ...r could contain gas oil or sulphur or near sources of heat z This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experi...

Page 16: ...2 Air filter 3 Special filter option 4 Display PCB 5 Vertical vane 6 Horizontal vane 7 Remote controller 8 Names of parts Outdoor unit No Name 8 Air outlet grille 9 Electronic box cover 10 2 way valve...

Page 17: ...J 0D OHQJWK P GGLWLRQDO UHIULJHUDQW DOFXODWLRQ J J P P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P 6 7 26 7 6 4 26 4 J P Connecting cables 7KH SRZHU FRUG VKRXOG EH VHOHFWHG DFFRU...

Page 18: ...HVVLEOH OUTDOOR UNIT l R QRW LQVWDOO WKH RXWGRRU XQLW QHDU VRXUFHV RI KHDW VWHDP RU IODPPDEOH JDV l R QRW LQVWDOO WKH XQLW LQ WRR ZLQG RU GXVW SODFHV l R QRW LQVWDOO WKH XQLW ZKHUH SHRSOH RIWHQ SDVV 6...

Page 19: ...e flange through the hole in the wall to keep the latter intact and clean The hole must slope downwards towards the exterior Note Keep the drain pipe down towards the direction of the wall hole otherw...

Page 20: ...not bend the pipe more than three times at one point z When extending the rolled pipe straighten the pipe by unwinding it gently as shown in the picture 9 2 6Connections to the indoor unit 1 Remove th...

Page 21: ...ening procedures described for the indoor unit Note If the tightening torque is not sufficient there will probably be some leakage With excessive tightening torque there will also be some leakage as t...

Page 22: ...intaining or scrapping an air conditioner l When filling the combustible refrigerant any of your rude operations may cause serious injury or injuries to human body or bodies and object or objects l A...

Page 23: ...auge used for Refrigerant 22 can be used for Refrigerants R290 and R161 the pressure gauge used for R410A can be used for Refrigerant 32 Fire Extinguisher It is necessary to carry fire extinguisher s...

Page 24: ...ring the maintenance it is a must to immediately take forced ventilation and plug up the leak source l If the product is damaged to the extent that it is a must to open the refrigerating system for ma...

Page 25: ...it is a must to confirm that the refrigerating system has been drained and the system has been cleaned and ensure that there has been no refrigerant in the outdoor unit l It is necessary to close the...

Page 26: ...vacuating the affected personnel urgently from the location l It is necessary to inform near residents of evacuating for over 20 meters from the location make an alarm call set the emergency area and...