background image

Page 26 of 44 

Water to Water Source Heat Pumps 

IM 1072-1

Control

Compressor Control Module Functional 

Operation – 208-230/60/3, Unit Sizes 120, 

150, 180, 240 and 300

Power:

For proper operation there must always be 18 to 30 volts AC 

present at the R and C terminals.

Time Delays:

1.

  

Anti-short cycle: 

provides the compressor with short 

cycle protection for a selectable time of 10 seconds (for 

servicing only) or 5 minutes (normal operationalsetting). 

This feature is enabled upon power loss to the circuit 

board, loss of the Y signal, or the opening of a switch 

connected to the HPS or LPS terminals. If the selecto 

shunt is not in place, the circuit will default to a 5 minute 

anti short-cycle delay.

2.   Delay on make:

 Delays the turning on of the compres

-

sor contactor for a selectable time of 3 or 6 seconds 

every time the Y signal coalls. If the selector shunit is not 

in place, the circuit will default to a 6 second delay on 

make.

3.     Low Pressure Bypass:

 Allows time for the low side 

pressure to build up enough pressure at start up for the 60 

psig low pressure switch to close. The circuit will offer a 

selectable timing range of 90, 120, 180, or 300 seconds. 

This time delay will start upon a Y call from the thermo

-

stat. Should the 60 psig low pressure switch still be open 

after the selected delay expires, the compressor will de-

energize and the alarm will energize. This will be defined 

as an LPS fault, (factory set for 90 seconds). If neces

-

sary to increase the delay, select the smallest amount of 

bypass time delay that allows the compressor to start and 

operate.

Note: 

The 60 psig low pressure switch is jumpered out in low 

temperature closed loop system applications using 

antifreeze solution. 

Also note tht the 35 psig low pressure switch is con-

nected in series with the high pressure switch to the 

HPS terminals and is never bypassed.

Operation Of The HPS Terminals

Switches connected to the HPS terminals are connected in 

series with the Y signal through the circuit board. These switches 

are also connected in series witht the T1 output in order to 

provide an immediate response if a switch were to open. If a 

switch conncecte to the HPS terminal should open, the status 

LED will blink once.

Operation Of The LPS Terminals

The 60 psig low pressure switch (brown leads) is connected 

to the LPS terminals in series with the Y signal through the 

circuit board. The 60 psig low pressure switch is connected in 

series with the Y signal to the processor only. This will allow 

the control to monitor the low pressure switch status and initi

-

ate the bypass delay. If the 60 psig low pressure switch should 

open, the status LED will blink twice.

Normal Cycle

A normal cycle will begin with 24 VAC applied to the R and 

C terminals on the circuit board. Once the control is powered up, 

the processor will read the Y signal to determine if it is calling. 

If it is calling and the switches connected to the HPS terminals 

are closed, the delay on make and low pressure bypass timers 

will initiate.

If a switch connected to the HPS terminals is open, the con

-

trol will enter the lockout mode. After the delay on make time 

expires, the compressor contactor will energize. It will remain 

energized as the low pressure bypass timer counts down.

If the 60 psig low pressure switch is closed after the timer 

expires, the compressor will remain energized. If it is still open, 

the control will enter the lockout mode.

If power is lost, or the Y signal is removed, or an HPS or LPS 

terminal switch fault is detected while the compressor contac

-

tor is energized, the unit will initiate the anti short-cycle delay.

Alarm/Lockout

The alarm terminal will output the R signal and will only be 

energized as a result of an HPS or LPS fault. An HPS fault is de

-

fined as the opening of a switch connected to the HPS terminals 

for any amount of time. An LPS fault is defined as the 60 psig 

low pressure switch open after the bypass time. If any of these 

conditions are true, the unit will de-energize the compressor and 

energize the alarm. This will be defined as a lockout condition. 

To reset a lockout condition, the pressure fault  must be corrected 

and the Y signal from the thermostat must be cycled.

Figure 9: Compressor control module functional operation

LPS

Y

HPS

T1

T

C

R

X

P

10

P

11

P

12

10

S

E

C

5

M

IN

P

7

P

8

P

9

3

S

E

C

6

S

E

C

P

5

P

4

P

3

P

2

P

1

30

0

18

0

12

0

90

LP

S

B

Y

P

A

S

S

S

E

C

O

N

D

S

D

O

M

A

S

C

R

LE

D

:

O

FF

=

N

O

Y

S

IG

N

A

L

P

R

E

S

E

N

T

O

N

=

Y

S

IG

N

A

L

P

R

E

S

E

N

T

1

B

LIN

K

=

FA

U

LT

O

N

H

P

S

TE

R

M

IN

A

LS

2

B

LIN

K

S

=

FA

U

LT

O

N

LP

S

TE

R

M

IN

A

LS

LP

R

-A

L1

70

1

To prevent both compressors from

starting at the same time (resulting in

extremely high inrush current): The 

delay on make timer for CCM1 is factory

set to 3 seconds. The delay on make timer

for CCM2 is factory set to 6 seconds.

Status LED

Disconnect power to

WW* unit before moving

jumpers! 

Use lowest LPS bypass time

setting which allow unit to start and

operate. Do not set the jumper any

higher than necessary.

10 SEC jumper is for servicing unit only.

Do not operate unit unattended with

jumper in the 10 second position!

Summary of Contents for WRA

Page 1: ...Group WSHP Part Number 667691802 Date October 2013 Daikin Water to Water Source Heat Pumps 3 to 35 Tons with R 410A WRA Heating and Cooling Models WHA Heating Only Models WCA Cooling Only Models 2013...

Page 2: ...LTC 208 230 60 3 Unit Sizes 036 048 060 and 072 20 Compressor Control Module Functional Operation 208 230 60 3 Unit Sizes 036 048 060 and 072 21 Wiring Diagram 22 208 230 60 3 Unit Sizes 120 150 180 2...

Page 3: ...ooling 300 300 000 Btuh Nominal Cooling 360 360 000 Btuh Nominal Cooling 420 420 000 Btuh Nominal Cooling Water Piping Location F Front T Top L Left Hand Side R Right Hand Side Status Lights YY None S...

Page 4: ...nly used on product labels to signify an immedi ate hazard The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the produc...

Page 5: ...0 15 4 517 632 9 6 15 15 120 208 230 60 1 2 23 1 134 0 46 2 197 253 52 0 70 70 208 230 60 3 16 1 91 0 32 2 187 253 36 2 50 50 460 60 3 7 1 46 0 14 2 414 506 16 0 20 20 575 60 3 5 6 37 0 11 2 517 632 1...

Page 6: ...ter pressure and sized for proper flow rate The supply and the discharge pipes should be insulated to prevent condensation damage caused by low water temperature in the pipes If water hammer should oc...

Page 7: ...rejected from the unit into the source water loop To reject excess heat from the water loop the use of a closed circuit evaporative cooler or an open type cooling tower with a secondary heat exchange...

Page 8: ...the tables 11 Check for vibrations noise water leaks etc 12 Adjust thermostat to correct mode and set to maintain desired temperature 13 Instruct the equipment owner operator of correct thermostat an...

Page 9: ...3 4 KO 1 2 KO 3 4 FPT 1 2 FPT Dimensions Size 048 060 Dimensions in Pipe Size FPT Connection Size A B C D E F G H J K L M N P Control Electric Auxiliary Electric Load Source Domestic Hot Water 28 28...

Page 10: ...ions Size 120 150 Dimensions in Water Connection Size A B C D E F G H K L M N P Q R S Load Source FPT 26 19 12 4 8 22 4 18 41 22 34 1 113 16 37 29 42 1 Dimensions Size 180 Dimensions in Water Connecti...

Page 11: ...Source Heat Pumps Page 11 of 44 Dimensional Data WRA WCA WHA Size 240 420 Dimensions Size 240 420 Dimensions in Water Connection Size A B C D E F K L M N P Q R S Load Source FPT 31 20 16 4 22 27 63 2...

Page 12: ...00 50 00 63 125 1130 1230 16 0 16 0 2 00 360 34 00 50 00 63 125 1420 1540 17 5 17 5 2 00 420 34 00 50 00 63 125 1620 1750 20 0 20 0 2 00 Operating Pressures PSIG Cooling Mode Table 4 Models WRA and W...

Page 13: ...813 0 829 0 937 1 614 50 0 922 0 770 0 789 0 922 1 816 Methanol 10 0 986 0 957 0 961 0 986 1 127 20 0 970 0 924 0 928 0 970 1 197 30 0 951 0 895 0 897 0 951 1 235 40 0 936 0 863 0 865 0 936 1 323 50 0...

Page 14: ...C P5 P4 P3 P2 P1 300 180 120 90 LPS BYPASS SECONDS DOM ASC R LED OFF NO Y SIGNAL PRESENT ON Y SIGNAL PRESENT 1 BLINK FAULT ON HPS TERMINALS 2 BLINKS FAULT ON LPS TERMINALS LPR AL1701 PK CC Y W OPTIONA...

Page 15: ...H UNITS 17 14 WHEN FS L AND FS S ARE NOT USED THIS WIRE CONNECTS DIRECTLY TO TERMINAL Y OF CCM WHEN PM IS NOT USED THIS WIRE CONNECTS DIRECTLY TO TERMINAL R ON TB1 4 THIS WIRE CONNECTS DIRECTLY FROM T...

Page 16: ...ature drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t...

Page 17: ...es with the Y signal through the circuit board The 60 psig low pressure switch is connected in series with the Y signal to the processor only This will allow the control to monitor the low pressure sw...

Page 18: ...ASS SECONDS DOM ASC R LED OFF NO Y SIGNAL PRESENT ON Y SIGNAL PRESENT 1 BLINK FAULT ON HPS TERMINALS 2 BLINKS FAULT ON LPS TERMINALS LPR AL1701 PK CC Y W OPTIONAL HP BK BL BK PR W 24 VAC LTC OPTIONAL...

Page 19: ...K 12 AWG WIRE NO NUMBER AFTER COLOR CODE INDICATES 18 AWG WIRE FOR EXAMPLE BK IS A BLACK 18 AWG WIRE ASTERISK AFTER DASH FOLLOWING COLOR CODE INDICATES REFERRAL TO COMPRESSOR WIRE SIZE TABLE 8 CHR IS...

Page 20: ...ature drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t...

Page 21: ...es with the Y signal through the circuit board The 60 psig low pressure switch is connected in series with the Y signal to the processor only This will allow the control to monitor the low pressure sw...

Page 22: ...L HP1 BK BL R FL PR W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8 P9 3 SEC 6 SEC P5 P4 P3 P2 P1 300 180 120 90 LPS...

Page 23: ...4 6 CR1 4 6 PR PR PR PR TS C TS H 23 63 34 64 52 CHR 1 3 WHEN USED 21 20 BR BR WHEN REQ D SPLICE 12 CHR 4 2 WHEN REQ D SPLICE BR CLASS 2 60 HZ TR1 24V WHEN USED R R R O C O 16 TB1 TB2 A1 A2 24 COM TC...

Page 24: ...30 VOLTS AC MAXIMUM EXTERNAL LOAD CHARACTERISTICS MUST NOT EXCEED 10 AMPS MAKE 1 AMP BREAK MAINTAIN SEPARATION BETWEEN CLASS 2 CIRCUITS OF DIFFERENT SOURCES PROVIDE DISCONNECTING MEANS EQUIPMENT GROU...

Page 25: ...drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken...

Page 26: ...nnected in series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should...

Page 27: ...W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8 P9 3 SEC 6 SEC P5 P4 P3 P2 P1 300 180 120 90 LPS BYPASS SECONDS DOM...

Page 28: ...64 52 CHR 1 3 11 WHEN USED 19 18 BR BR WHEN REQ D SPLICE 10 CHR 4 2 WHEN REQ D SPLICE BR 96 VA CLASS 2 60 HZ TR1 24V WHEN USED R R R O C Y O 14 TB1 TB2 A1 A2 OPTIONAL 208 230V 4 0A 24 COM TC OPTIONAL...

Page 29: ...WITH THE COMPRESSORS AN EXTERNAL LOAD POWERED BY TRANSFORMER TR1 IN THE WW UNIT MUST NOT EXCEED 12 VA SEALED 96 VA INRUSH 24 VOLTS AC EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO CLAS...

Page 30: ...elow 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken or sho...

Page 31: ...n series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should open the...

Page 32: ...S R Y PR O OPTIONAL OPTIONAL 5 CC1 Y W OPTIONAL HP1 BK BL BK R FL PR W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8...

Page 33: ...BK BK CR2 4 6 CR1 4 6 PR PR PR PR TS C TS H 23 63 34 64 52 CHR 1 3 11 WHEN USED 19 18 BR BR WHEN REQ D SPLICE 10 CHR 4 2 WHEN REQ D SPLICE BR CLASS 2 60 HZ TR1 24V WHEN USED R R R O C O 14 TB1 TB2 A1...

Page 34: ...COMPRESSORS AN EXTERNAL LOAD POWERED BY TRANSFORMER TR1 IN THE WW UNIT MUST NOT EXCEED 12 VA SEALED 96 VA INRUSH 24 VOLTS AC EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO CLASS 2 CIRCU...

Page 35: ...below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken or s...

Page 36: ...d in series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should open...

Page 37: ...IM 1072 1 Water to Water Source Heat Pumps Page 37 of 44 WHA Circuit Diagram WHA Load Coil Heater Condenser Source Coil Evaporator...

Page 38: ...Page 38 of 44 Water to Water Source Heat Pumps IM 1072 1 WRA Circuit Diagram WRA Reverse Cycle No Domestic Hot Water WRA Reverse Cycle With Domestic Hot Water H R Coil...

Page 39: ...ter Source Heat Pumps Page 39 of 44 WCA Circuit Diagram WCA Load Coil Chiller Evaporator Source Coil Condenser No Domestic Hot Water WCA Load Coil Chiller Evaporator Source Coil Condenser With Domesti...

Page 40: ...erage____________________ Phase____________________ Transformer Volts__________________ Unit Function Heating WRA WHA Entering Leaving Diff TD Load Liquid Temperature F From fan coil unit radiant coil...

Page 41: ...tor points etc won t start 3 Compressor starts but a Run capacitor could be bad a Check capacitor hums and trips out on overload b Voltage may be low b Check it c Seized bearings on compressor c Repla...

Page 42: ...tch HP 7 Low Pressure 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 Switch LP1 8 Fluid Refrigerant 512 200 512 201 512 201 512 259 512 201 512 202 512 200 512...

Page 43: ...This page intentionally left blank...

Page 44: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin...

Reviews: