1-1 TECHNICAL SPECIFICATIONS
BSVQ100PV18
BSVQ160PV18
BSVQ250PV18
Power input
(nominal)
Cooling
kW
0.005
0.005
0.005
Heating
kW
0.005
0.005
0.005
Casing
Material
Galvanised steel
Dimensions
Unit
Height
mm
207
207
207
Width
mm
388
388
388
Depth
mm
326
326
326
Weight
Unit
kg
14.0
14.0
15.0
Outdoor Unit
Liquid (OD)
Type
Brazing connection
Diameter
mm
9.5
9.5
9.5
Gas
Type
Brazing connection
Diameter
mm
15.9
15.9
22.2
Discharge Gas
Type
Brazing connection
Diameter
mm
12.7
12.7
19.1
Indoor Units
Liquid (OD)
Type
Brazing connection
Diameter
mm
9.5
9.5
9.5
Gas
Type
Brazing connection
Diameter
mm
15.9
15.9
22.2
Sound absorbing thermal insulation material
Foamed polyurethane, Frame resisting needle felt
Standard
Accessories
Item
Installation manual
Attached piping
Insulation pipe cover
Clamps
Notes
In case of connection with a
20~50 type indoor unit, match
to the size of the field pipe
using the attached pipe.
Connection between the
attached pipe and the field pipe
must be brazed.
In case of connecting with
indoor unit capaicty index 150
or more and 160 or less, match
to the size of the field pipe
using the attached pipe.
Connection between the
attached pipe and the field pipe
must be brazed.
In case of connecting with a
200 type indoor unit or capacity
index more than 160 and less
than 200, match to the size of
the field pipe using the
attached pipe. Connection
between the attached pipe and
the field pipe must be brazed.
1-2 ELECTRICAL SPECIFICATIONS
BSVQ100PV18
BSVQ160PV18
BSVQ250PV18
Power Supply
Phase
1~
Frequency
Hz
50
50
50
Voltage
V
220-240
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Total circuit
Minimum circuit amps (MCA)
A
0.1
0.1
0.1
Maximum Fuse Amps
A
15
15
15
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit
terminal is not below or above listed range limits
Maximum allowable voltage range variation between phases is 2%
MCA / MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on MCA