SiME341909EA
Address Setting for Wireless Remote Controller
Part 3 Remote Controller
45
4.2 Setting for BRC4M Series
The address for the wireless remote controller is set to 1 at the factory. To change the setting,
proceed as follows:
1. Hold down the
FILTER SIGN RESET
button and the
INSPECTION
button for at least 4
seconds to get the Field Setting mode.
(Indicated in the display area in the figure.)
2. Press the
SELECT
button and select a multiple setting (
A/b
). Each time the button is
pressed the display switches between
A
and
b
.
3. Press the
TEMP
buttons to set the address.
Address can be set from 1 to 6, but set it to 1-3 and to same address as the receiver. (The
receiver does not work with address 4-6.)
4. When the
RESERVE
button is pressed, the setting is confirmed and the usual display
returns.
Address
Multiple setting
1
4
2
3