Stop Control
SiME341909EA
58
Part 4 Functions and Control
2. Stop Control
2.1 Abnormal Shutdown
If abnormal situation occurs to protect the compressor, initial thermostat OFF stops the
outdoor unit.
Outdoor control will perform a retry start.
When the retry attempts reach a certain number, system will stop and error code is
displayed on the remote control.
BRC1E series remote controller stores the last 10 error codes for remote controller and the
last 5 error codes for indoor unit. You can check the
Error History
in
Service Settings
.
Consult the troubleshooting chart on the displayed error code to define cause of abnormal
stop.
2.2 Slave Unit Stops during Master Unit Operation
When slave unit is stopped (because of low demand), conditions for this units are set same as
system stop. System stop until this unit is required to operate (increase of load).