Field Settings for Outdoor Unit
SiME341909EA
108
Part 5 Field Settings and Test Operation
2.3 Settings by BS Buttons
The following settings can be made using the BS buttons on the PCB.
In case of a multi outdoor system, make these settings with the master outdoor unit (settings
made with a slave unit are disabled).
Normal mode:
Blank: If no abnormality is detected and initialization of communication was completed.
Flashing combination of letter and number (4 digits): Error code detected by outdoor
control or trouble by communication.
Setting mode: Used to make changes to operating status, performance settings or address
setting.
Monitor mode: Used to verify contents of settings, quantity of units, current value of some
parameters during operation of outdoor unit.
Mode changing procedure can be selected using the MODE (BS1) button as shown
below:
MODE
BS1
SET
(TEST)
BS2
RETURN
(RESET)
BS3
Used to make
setting mode
changes.
Used to make
field settings.
7 segment display (SEG1-3)
BS buttons
Normal mode
Setting mode
Monitor mode
SEG1 SEG2 SEG3
Monitor mode
Press the
MODE
(BS1)
button once
Setting mode
Press and hold the
MODE (BS1)
button
for 5 seconds or more
Press the
MODE
(BS1)
button once
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
Normal mode
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...