10T7Y1B
VRV-W IV System Air Conditioner
4P347465-1A – 2013.04
Installation and operation manual
31
15.2.2
Operating the DIP switches
By operating the DIP switches it is possible to
15.3. Connecting the PC configurator to the outdoor
unit
Connection of the optional PC configurator cable to the outdoor unit
has to be done on A1P. Connect the EKPCCAB* cable to the 5-pin
blue connector X27A.
1
PC
2
Cable (EKPCCAB*)
3
Outdoor unit main PCB
16. Charging refrigerant
16.1. Precautions
To avoid compressor breakdown, do not charge the refrigerant
more than the specified amount.
This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths, some systems
require additional charging of refrigerant (see
"16.3. Calculating
the additional refrigerant charge" on page 32
).
16.2. Important information regarding the refrigerant
used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:
R410A
GWP
(1)
value:
1975
(1)
GWP=global warming potential
Please fill in with indelible ink:
a the factory refrigerant charge of the product,
b the additional refrigerant amount charged in the field and,
a+b the total refrigerant charge
on the fluorinated greenhouse gases label supplied with the product.
The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g., on the inside of the
service cover).
1
Factory refrigerant charge of the product: see unit name
plate
2
Additional refrigerant amount charged in the field
3
Total refrigerant charge
4
Contains fluorinated greenhouse gases covered by the
Kyoto protocol
5
Outdoor unit
6
Refrigerant cylinder and manifold for charging
What to do with DIP switch DS1
1
COOL/HEAT selector (refer to the manual of the cool/heat
selector switch)
OFF=not installed=factory setting
2-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2/DS3
1-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
INFORMATION
For details on how to operate or connect the COOL/HEAT
selector: see installation manual of the COOL/HEAT
selector and the wiring diagram.
COOL/HEAT selector function should only be used in case
the unit is used as heat pump system.
CAUTION
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
A1P
X32A
1
2
3
2
3
4
5
H JST
X32A
NOTICE
Refrigerant cannot be charged until field wiring has
been completed.
Refrigerant may only be charged after performing the
leak test and the vacuum drying.
When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.
Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes
when charging refrigerant.
When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable
legislation.
DANGER: ELECTRICAL SHOCK
See
page 2
.
3
5
6
2
1
4