8 Troubleshooting

Installation and operation manual

12

RYYQ+RYMQ+RXYQ8~20U7Y1B

VRV IV+ heat pump

4P546220-1C – 2020.10

7.2

After-sales service and warranty

7.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

7.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do  NOT  modify,  disassemble,  remove,  reinstall  or

repair  the  unit  yourself  as  incorrect  dismantling  or
installation may cause an electric shock or fire. Contact
your dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.

Turn OFF the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does NOT work
well.

Turn OFF the power
supply.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the user interface display shows

 (time to clean the air filter). (Refer to

"7  Maintenance  and  service"

  [

4

  11]  and

"Maintenance" in the indoor unit manual.)

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

8.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

Main code

Contents

External protection device was activated

EEPROM failure (indoor)

Drain system malfunction (indoor)

Fan motor malfunction (indoor)

Swing flap motor malfunction (indoor)

Expansion valve malfunction (indoor)

Summary of Contents for VRV IV+

Page 1: ...ration manual VRV IV heat pump RYYQ8U7Y1B RYYQ10U7Y1B RYYQ12U7Y1B RYYQ14U7Y1B RYYQ16U7Y1B RYYQ18U7Y1B RYYQ20U7Y1B RYMQ8U7Y1B RYMQ10U7Y1B RYMQ12U7Y1B RYMQ14U7Y1B RYMQ16U7Y1B RYMQ18U7Y1B RYMQ20U7Y1B RXY...

Page 2: ...n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direk...

Page 3: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 4: ...8 2 15 Symptom The display shows 88 14 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 14 8 2 17 Symptom The inside of an outdoor unit is warm even whe...

Page 5: ...ust read before installing Format Paper in the box of the outdoor unit Outdoor unit installation and operation manual Installation and operation instructions Format Paper in the box of the outdoor uni...

Page 6: ...e side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor...

Page 7: ...nsuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health For more information contact your installer or local authori...

Page 8: ...he point of leakage has been repaired or corrected before resuming operation WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Leaving the unit running under...

Page 9: ...cannot be made with a user interface whose display shows change over under centralised control refer to installation and operation manual of the user interface When the display change over under centr...

Page 10: ...ration if the room temperature is low 20 C 6 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interface sev...

Page 11: ...the user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically follow the operation mode dire...

Page 12: ...F the power supply If the user interface display indicates the unit number the operation lamp flashes and the malfunction code appears Notify your installer and report the malfunction code If the syst...

Page 13: ...ndoor outdoor Abnormal user interface indoor communication Faulty wiring to outdoor outdoor Abnormal main sub user interface communication System mismatch Wrong type of indoor units combined Indoor un...

Page 14: ...hile the indoor unit is stopped When another indoor unit is in operation this noise is heard In order to prevent oil and refrigerant from remaining in the system a small amount of refrigerant is kept...

Page 15: ...9 TOTAL LENGTH OF LIQUID PIPE SIZE O6 4 x 0 022 105 CR 130 50 CR 105 50 CR 70 70 CR 85 85 CR 105 105 CR 130 8HP Total indoor unit capacity connection ratio CR 10 12HP 14 16HP 18 20HP 2 0 1 5 1 5 1 2 1...

Page 16: ...wireless dedicated depending on indoor unit type i Cool heat changeover remote control switch 13 Unit installation 13 1 Preparing the installation site 13 1 1 Installation site requirements of the ou...

Page 17: ...to prevent vibration and noise NOTICE When the installation height of the unit needs to be increased do NOT use stands to only support the corners Stands under the unit must be at least 100 mm wide 10...

Page 18: ...8 19 1 9 5 10 22 2 9 5 12 16 28 6 12 7 18 22 28 6 15 9 24 34 9 15 9 Outdoor unit capacity type HP Piping outer diameter size mm Gas pipe Liquid pipe 26 34 34 9 19 1 36 54 41 3 19 1 D Piping between r...

Page 19: ...pipe Liquid pipe 20 25 30 9 5 6 4 50 12 7 60 9 5 71 15 9 14 1 3 To select refrigerant branch kits Refrigerant refnets For piping example refer to To select the piping size 418 When using refnet joint...

Page 20: ...s to the outmost outdoor unit when the system stops NOT allowed oil remains in piping Allowed If the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line...

Page 21: ...tion label a attached to the joint comes to the top Do not tilt the joint more than 7 5 see view A Do not install the joint vertically see view B a a A B 7 5 7 5 a Caution label NOT allowed Allowed Ma...

Page 22: ...the service port make sure to tighten the service port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cover Tightening...

Page 23: ...ait to apply setting 2 21 until the outdoor unit has finished the initialisation Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant pipin...

Page 24: ...proceed as follows 1 Evacuate the system for at least 2 hours to a target vacuum of 100 7 kPa 1 007 bar 5 Torr absolute 2 Check that with the vacuum pump turned off the target vacuum is maintained for...

Page 25: ...pre charge a portion of refrigerant through the liquid line before proceeding with the actual automatic or manual charging This step is included in below procedure see To charge refrigerant 428 It can...

Page 26: ...it capacity class 550 CR 100 2 Determine parameter C N 5 8 HP N 4 C1 N 0 1 5 0 1 kg 12 HP N 6 C2 0 kg C C1 C2 0 5 kg Metric piping When using metric piping replace the weight factors in the formula by...

Page 27: ...onal refrigerant amount via setting 2 14 Go to test run Step 4b Close valves D and B R Q R Q R Q Continued on next page p p R410A N2 C D A B Charging refrigerant Step 6 Proceed with automatic or manua...

Page 28: ...pear e 2 indoor temperature out of range and e 3 outdoor temperature out of range Push BS1 to leave program Charging is finished Fill in the amount on the additional refrigerant charge label Input the...

Page 29: ...charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so be careful when connecting the charge hose After adding the refrigera...

Page 30: ...et Retry autocharge procedure Indoor unit is out of temperature range for leak detection operation Retry when ambient conditions are satisfied Outdoor unit is out of temperature range for leak detecti...

Page 31: ...19397 RYYQ40 RXYQ40 20378 RYYQ42 RXYQ42 20629 RYYQ44 RXYQ44 21132 RYYQ46 RXYQ46 21887 RYYQ48 RXYQ48 22641 RYYQ50 RXYQ50 23899 RYYQ52 RXYQ52 25157 RYYQ54 RXYQ54 26415 INFORMATION Multi units are standa...

Page 32: ...iring d Tie wrap a Knockout hole has to be removed Close the hole to avoid small animals or dirt from entering X1A c d a b a b 8 12 HP 14 20 HP Fix to the indicated plastic brackets using field suppli...

Page 33: ...pipes using finishing tape as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 15 7 To route and fix the power supply NOTICE When rout...

Page 34: ...gs it is also possible to confirm the current operation parameters of the unit Push buttons and DIP switches Item Description Push buttons By operating the push buttons it is possible to Perform speci...

Page 35: ...r and to protect the compressor Turn on the power supply of the outdoor unit and all indoor units When the communication between indoor units and outdoor unit s is established and normal the 7 segment...

Page 36: ...ter position 1 6 The current Tc target parameter position 1 10 Shows the total number of connected indoor units 1 13 Shows the total number of connected outdoor units in case of multiple outdoor syste...

Page 37: ...leak detection function see 16 2 Using the leak detection function 438 2 20 Manual additional refrigerant charge 2 20 Description 0 default Deactivated 1 Activated To stop the manual additional refri...

Page 38: ...e as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn ON the power 6 hours before operation in order to have power running to the crankcase heater a...

Page 39: ...erface It is possible to operate the system Leak detection function will NOT be available It is recommended to re execute the test operation If the autocharge function was used the unit informs the us...

Page 40: ...the following is clear for the user Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at...

Page 41: ...t recharge unit Open stop valves Ambient temperature sensor malfunction R1T A1P X18A Check connection on PCB or actuator Discharge temperature sensor malfunction R21T open circuit A1P X19A Check conne...

Page 42: ...ower supply voltage Check if power supply is within range Reversed power supply phase malfunction Correct phase order Reversed power supply phase malfunction Correct phase order INV1 voltage power sho...

Page 43: ...Check if the valve of the refrigerant cylinder is opened Check if the air inlet and outlet of the indoor unit are not obstructed Freeze up prevention indoor unit Close valve A immediately Push BS1 to...

Page 44: ...s along the installation site with obstacles F Front side Suction side In case of an installation site where sides A B C D have obstacles the wall heights of sides A C have no impact on service space...

Page 45: ...T R5T R7T R1T R21T a b n m k k e d d e f l j i o p t s r v h c sv INV INV HPS sv sv HPS M2F M M1F M M2C M1C S1NPH S1NPL S1PH S2PH R22T R9T R8T R4T g x w Piping diagram RYMQ8 12 R8T R3T R6T R5T R7T R1T...

Page 46: ...apter refer to the installation manual of the optional adapter 4 For connection wiring to indoor outdoor transmission F1 F2 outdoor outdoor transmission F1 F2 outdoor multi transmission Q1 Q2 refer to...

Page 47: ...circuit board noise filter A3P A6P Printed circuit board inverter A4P A7P Printed circuit board fan A8P Printed circuit board ABC I P option BS1 BS3 A1P Push button switch MODE SET RETURN C A3P A6P C...

Page 48: ...bcool Z C Noise filter ferrite core Z F A2P Noise filter with surge absorber Connectors for optional accessories X10A Connector drainpan heater X37A Connector power adapter X66A Connector remote switc...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...4P546220 1C 2020 10 Copyright 2018 Daikin 4P546220 1 C 0000000Y Verantwortung f r Energie und Umwelt...

Reviews: