19
|
Electrical installation
Installer and user reference guide
107
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
INFORMATION
Multi units are standard combinations.
Model
Minimum circuit
ampacity
Recommended
fuses
RXMLQ8
16.1 A
20 A
RXYLQ10
22.0 A
25 A
RXYLQ12
24.0 A
32 A
RXYLQ14
27.0 A
32 A
RXYLQ16
32.2 A
40 A
RXYLQ18
38.1 A
45 A
RXYLQ20
44.0 A
50 A
RXYLQ22
46.0 A
60 A
RXYLQ24
48.0 A
60 A
RXYLQ26
51.0 A
60 A
RXYLQ28
54.0 A
60 A
RXYLQ30
66.0 A
80 A
RXYLQ32
68.0 A
80 A
RXYLQ34
70.0 A
80 A
RXYLQ36
72.0 A
80 A
RXYLQ38
75.0 A
90 A
RXYLQ40
78.0 A
90 A
RXYLQ42
81.0 A
90 A
For all models:
▪
Phase and frequency: 3N~ 50 Hz
▪
Voltage: 380~415 V
▪
Transmission line section: 0.75~1.25 mm
2
, maximum length is 1000 m. If the total
transmission wiring exceeds these limits, it may result in communication error.
For non-standard combinations
Calculate the recommended fuse capacity.
Formula
Calculate, by adding the minimum circuit amps of each used unit
(according to the table above), multiply the result by 1.1 and
select the next higher recommended fuse capacity.
Example
Combining the RXYLQ18 by using the RXMLQ8 and the RXYLQ10.
▪
Minimum circuit ampacity of the RXMLQ8=16.1 A
▪
Minimum circuit ampacity of the RXYLQ10=22.0 A
Accordingly, the minimum circuit ampacity of the RXYLQ18=16.1 A
+22.0 A=38.1 A
Multiply the above result by 1.1: (38.1 A×1.1)= 41,91 A, so the
recommended fuse capacity would be
45 A
.