25
|
Technical data
Installer and user reference guide
147
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
25 Technical data
▪
A
subset
of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪
The
full set
of latest technical data is available on the Daikin Business Portal
(authentication required).
In this chapter
25.1 Piping diagram: Compressor unit and heat exchanger unit
5 HP
R2T
R3T
R1T
M1F
M2F
Y1E
Y3E
R2T
M1C
R3T
R7T
R4T
Y1S
S1NPL
S1PH
S1NPH
R5T
f
f
l
c
b
f
g
a
d
f
m
h
f
i
j
k
e
B
A
3D110524-1
A
Heat exchanger unit
B
Compressor unit
a
Stop valve (gas) (circuit 2: to indoor units)
b
Stop valve (liquid) (circuit 2: to indoor units)
c
Stop valve (liquid) (circuit 1: to heat exchanger unit)
d
Stop valve (gas) (circuit 1: to heat exchanger unit)
e
Service port (refrigerant charge)
f
Filter
g
Subcool heat exchanger
h
Pressure regulating valve
i
Capillary tube
j
Accumulator
k
Compressor accumulator
l
Heat exchanger
m
Check valve