Troubleshooting by Indication on the Remote Controller
SiUS34-801A_b
344
Troubleshooting
3.5
A7
Indoor Unit: Malfunction of Louver Motor (M1S)
Remote
Controller
Display
A7
Applicable
Models
FXHQ
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the louver motor
is energized for a specified amount of time (about 30 seconds).
Error code is displayed but the system operates continuously.
Supposed
Causes
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of airflow direction adjusting louver
Defect of indoor unit PC board
Summary of Contents for VRV III
Page 15: ...SiUS34 801A_b xiv ...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Page 563: ...SiUS34 801A_b iv Index ...