Daikin VRV III RXYQ-PY1K Installation Manual Download Page 20

Installation manual

17

RXYQ8~1 RXYQ8~12P7YLK

VRVIII System air conditioner

4PW41760-1

11.2. Stop valve operation procedure

Size of stop valve

The sizes of the stop valves connected to the system are as listed in
the table below.

Opening stop valve 

(See figure 14)

1.

Remove the cap and turn the valve counterclockwise with the
hexagon wrench.

2.

Turn it until the shaft stops.

3.

Make sure to tighten the cap securely. Refer to the table below

Closing stop valve 

(See figure 14)

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body
seal.

3.

Make sure to tighten the cap securely.
For the tightening torque, refer to the table above.

11.3. How to check how many units are connected

It is possible to find out how many indoor units are active and
connected by operating the push-button switch on the printed circuit
board (A1P) of the working outdoor unit. In a multiple outdoor unit
system, you can find out how many outdoor units are connected to
the system by using the same procedure.

Make sure that all the indoor units connected to the outdoor unit are
active. 

Follow the 5-step procedure as explained below.

The LEDs on the A1P shows the operating status of the outdoor
unit and the number of indoor units that are active.

The number of units that are active can be read from the LED
display in the "Monitor Mode" procedure below.
Example: in the following procedure there are 22 units active: 

Do not open the stop valve until all piping and
electrical steps of 

"10. 

Checking of unit and

installation conditions" on page 16

  are completed. If

the stop valve is left open without turning on the
power, it may cause refrigerant to build up in the
compressor, leading to insulation degradation.

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant
leaks are present.

Type

8

10

12

Liquid line stop valve

Ø9.5

(a)

(a) The model RXYQ12 supports field piping of Ø12.7 on the accessory pipe 

supplied with the unit.

Gas line stop valve

Ø19.1

Ø25.4

(b)

(b) The model RXYQ10 supports field piping of Ø22.2 on the accessory pipe 

supplied with the unit.
The model RXYQ12 supports field piping of Ø28.6 on the accessory pipe 
supplied with the unit.

1

Service port

2

Cap

3

Hexagon hole

4

Shaft

5

Seal

Do not apply excessive force to the stop valve. Doing
so may break the valve body, as the valve is not a
backseat type. Always use the special tool.

Stop valve size

Tightening torque N•m (Turn clockwise to close)

Shaft

Cap (valve lid)

Service port

Valve body

Hexagonal 

wrench

Ø9.5

5.4~6.6

4 mm

13.5~16.5

11.5~13.9

Ø12.7

8.1~9.9

18.0~22.0

Ø15.9

13.5~16.5

6 mm

23.0~27.0

Ø19.1

27.0~33.0

8 mm

22.5~27.5

Ø25.4

x

OFF

w

ON

c

Blinking

NOTE

Wherever during this procedure, press the

 button if something becomes unclear.

You will return to setting mode 1 (H1P= 

x

 "OFF").

1

Setting mode 1 (default system status)

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Default status (normal)

x

x w x

x

x

x

Press the 

 

button to switch from setting mode 1 to monitor 

mode.

2

Monitor mode

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Default status display

c x

x

x

x

x

x

To check the number of indoor units, press the 

 

button 5 times

To check the number of outdoor units, p

ress the 

 

button 8 times

3

Monitor mode

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Selection status of how many 
connected indoor units to 
display.

c x

x

x w x w

OR

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Selection status of how many 
connected outdoor units to 
display. 

c x

x w x

x

x

Pressing the 

 

button causes the LED display to show the 

data on the number of indoor units that are connected or how many 
outdoor units that are connected in a multiple outdoor unit system.

4

Monitor mode

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Displaying the number of 
connected indoor units

c x c x c c x

32

16

8

4

2

1

Calculate the number of connected indoor units by adding the values of 
all (H2P~H7P) blinking (

c

) LEDs together. 

In this example: 16+4+2=22 units

Press the 

 

button to return to step 1, setting mode 1 

(H1P= 

x

 "OFF").

BS1  MODE

BS1  MODE

BS2  SET

BS2  SET

BS3  RETURN

BS1  MODE

Summary of Contents for VRV III RXYQ-PY1K

Page 1: ...INSTALLATION MANUAL RXYQ8P7Y1K RXYQ10P7Y1K RXYQ12P7Y1K RXYQ8P7YLK RXYQ10P7YLK RXYQ12P7YLK System air conditioner...

Page 2: ...XYQ16 32 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b...

Page 3: ...OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OF...

Page 4: ...for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R410A To learn which models of indoor units are com...

Page 5: ...5 35 RXYQ24 RXYQ12 RXYQ12 300 780 39 RXYQ26 RXYQ8 RXYQ8 RXYQ10 325 845 42 RXYQ28 RXYQ8 RXYQ10 RXYQ10 350 910 45 RXYQ30 RXYQ8 RXYQ10 RXYQ12 375 975 48 RXYQ32 RXYQ10 RXYQ10 RXYQ12 400 1040 52 RXYQ34 RXY...

Page 6: ...easures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the cust...

Page 7: ...G 1 Packaging material 2 Opening large 3 Belt sling 4 Opening small 40x45 5 Protector NOTE Use a belt sling of 20 mm wide that adequately bears the weight of the unit NOTE Use filler cloth on the fork...

Page 8: ...size is not available stick to the original pipe diameter which may result in a small capacity decrease 6 3 Pipe connection Be sure to perform a nitrogen blow when brazing and to read the paragraph C...

Page 9: ...on into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 1 Pinched piping 2 Stop valve 3 Service port 4 Point of melting the brazing metal Precautions when connecting f...

Page 10: ...e than 500 mm of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the...

Page 11: ...be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the...

Page 12: ...es must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The differenc...

Page 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Page 14: ...stor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S2PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A3P A4P A8P V2R Diode bri...

Page 15: ...prevent malfunctioning of the earth leakage breaker itself Earth leakage breakers that are especially designed for protecting ground faults must be used in conjunction with main switch and fuse for us...

Page 16: ...akage breaker 4 Outdoor unit 5 Indoor unit 6 Remote controller Power supply wiring sheathed cable outdoor 3 phase 380 415 V indoor 1 phase 230 V Transmission wiring sheathed cable 16 V 1 Electric wiri...

Page 17: ...16 branches are possible for unit to unit cabling No branching is allowed after branching See figure 16 Never connect the power supply to transmission wiring terminal block Otherwise the entire system...

Page 18: ...ying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as...

Page 19: ...ansmission wiring between outdoor and indoor unit outdoor and COOL HEAT selector etc 11 CHARGING REFRIGERANT The outdoor unit is factory charged but depending on the length of the piping when installe...

Page 20: ...d line stop valve 9 5 a a The model RXYQ12 supports field piping of 12 7 on the accessory pipe supplied with the unit Gas line stop valve 19 1 25 4 b b The model RXYQ10 supports field piping of 22 2 o...

Page 21: ...r the power is on via the service lid which is in the lid of the electric box Operate switches with an insulated stick such as a ball point pen to avoid touching the life parts Make sure to re attach...

Page 22: ...tton once if the LEDs combination is not as in the figure below 3 Press the button once 4 Hold the button down for 5 seconds or more 5 Charging mode judgement For automatic charging the charging must...

Page 23: ...d check the LEDs and check if the P9 code is displayed on the remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediatel...

Page 24: ...mode is not possible in some cases The unit will automatically select the cooling mode or heating mode for charging Continue with the manually charging in cooling mode OR in heating mode Charging in...

Page 25: ...e controller malfunction code display on page 22 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode R...

Page 26: ...form the overcharge judgement procedure again When there is no more overcharging of refrigerant detected restart the automatic refrigerant charging from 1 Start of automatic charging refrigerant as ex...

Page 27: ...uch as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing...

Page 28: ...selection on page 13 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip s...

Page 29: ...he external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consumption limitation set...

Page 30: ...pleted Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again as decribed in Correc...

Page 31: ...tion will be prohibited 2 Cut off the power supply to the indoor units and the outdoor unit with the circuit breaker After the power supply to one side is cut off cut off the power supply to the other...

Page 32: ...such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the re...

Page 33: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 28 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 29 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 30 13 14 3 5 4 2 1 7 8 9 6...

Page 34: ...4PW41760 1 Copyright Daikin...

Reviews: