RXYQ8~1 RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
Installation manual
14
Fixing transmission wiring
Inside switchbox
Outside unit
Sequential start
The outdoor unit PC board (A1P) is factory set at "Sequential start
available".
Setting the cool/heat operation
1
Performing cool/heat setting with the remote controller
connected to the indoor unit.
Keep the cool/heat selector switch (DS1) on the outdoor unit PC
board at the factory setting position IN/D UNIT.
2
Performing cool/heat setting with the cool/heat selector.
Connect the cool/heat selector remote controller (optional) to the
A/B/C terminals and set the cool/heat selector switch (DS1) on
the outdoor unit PC board (A1P) to OUT/D UNIT.
1
Heating/cooling switching remote control cord (when a heating/
cooling switch remote control (optional) is connected) (ABC)
2
Fix to the indicated plastic brackets using field supplied clamping
material.
3
Wiring between the units (Outdoor - outdoor) (F1+F2 right)
4
Wiring between the units (Indoor - outdoor) (F1+F2 left)
5
Wiring for multi connection (only for RXYQ16~36) (Q1+Q2)
6
Plastic bracket
■
Be sure to follow the limits below. If the unit-to-unit
cables are beyond these limits, it may result in
malfunction of transmission.
-
Maximum wiring length:
1000 m
-
Total wiring length:
2000 m
-
Maximum interunit wiring length
between outdoor units:
30 m
-
Transmission wiring to cool/heat
selector:
500 m
-
Maximum number of branches:
16
■
Maximum number of independent interconnectable
systems :
10.
■
Up to 16 branches are possible for unit-to unit cabling.
No branching is allowed after branching.
■
Never connect the power supply to transmission
wiring terminal block. Otherwise the entire system
may break down.
■
Never connect 400 V to the terminal block of the
interconnecting wiring. Doing so will break the entire
system.
-
The wiring from the indoor units must be
connected to the F1/F2 (In-Out) terminals on the
PC board in the outdoor unit.
-
After installing the interconnecting wires inside the
unit, wrap them along with the on-site refrigerant
pipes using finishing tape, as shown in
For the above wiring, always use vinyl cords with 0.75
to 1.25 mm
2
sheath or cables (2-core wires). (3-core
wire cables are allowable for the cooler/heater
changeover remote controller only.)
(TO OUT/D UNIT F1-F2)
1
Outdoor unit
2
Indoor unit
3
Main line
4
Branch line 1
5
Branch line 2
6
Branch line 3
7
No branch is allowed after branch
8
Central remote controller (etc...)
A
Transmission wiring between outdoor unit and indoo
unit(s)
B
Transmission wiring between outdoor units
1
Liquid pipe
2
Gas pipe
3
Insulator
4
Interconnecting wiring
5
Finishing tape
■
Be sure to keep the power line and transmission line
apart from each other.
■
Be careful about polarity of the transmission line.
■
Make sure that the transmission line is clamped as
shown in
■
Check that wiring lines do not make contact with
refrigerant piping.
■
Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
■
When you do not use a wire conduit, be sure to
protect the wires with vinyl tubes etc, to prevent the
edge of the knock-out hole from cutting the wires.
1
Remote controller
1
Cool/heat selector