Test Operation
SiBE37-701
186
Test Operation
Correcting after abnormal completion of the test operation
The test operation is only completed if there is no malfunction code displayed on the remote
controller. In case of a displayed malfunction code, perform the following actions to correct the
abnormality:
Confirm the malfunction code on the remote controller
After correcting the abnormality, press the
button and reset the malfunction
code.
Carry out the test operation again and confirm that the abnormality is properly corrected.
1.2.6.5
Service mode operation
Note:
Do not shut off the power and do not reset the setting of mode 2 when vaccuuming or
recovering refrigerant. Otherwise the expansion valves will close making it impossible to
vaccuum the system or to recover the refrigerant.
Vacuuming method
At the first installation, this vacuuming is not required. It is required only for repair purposes.
1. When the unit is at standstill and under the setting mode 2, set the required function B
(refrigerant recovery operation/vacuuming operation) to
(ON).
- The indoor unit, BS unit and the outdoor unit expansion valves will fully open.
- The H1P LED is on and the remote controller indicates
(test operation) and
(external control) and the operation will be prohibited.
2. Evacuate the system with a vacuum pump.
3. Press the
button and reset the setting mode 2.
Refrigerant recovery operation method
by a refrigerant reclaimer
1. When the unit is at standstill and under the setting mode 2, set the required function B
(refrigerant recovery operation/vacuuming operation) to
(ON).
- The indoor unit, BS unit and the outdoor unit expansion valves will fully open.
- The H1P LED is on and the remote controller indicates
(test operation) and
(external control) and the operation will be prohibited.
2. Recover the refrigerant by a refrigerant reclaimer. For details, see the operation manual
delivered with the refrigerant reclaimer.
3. Press the
button and reset the setting mode 2.
Installation error
Error code
Remedial action
The stop valve of an outdoor unit
is left closed.
E3
E4
F3
F6
UF
Open the stop valve.
The phases of the power to the
outdoor units are reversed.
U1
Exchange two of the three phases (L1, L2, L3) to
make a positive phase connection.
No power is supplied to an
outdoor or indoor unit (including
phase interruption).
LC
U1
U4
Check if the power wiring for the outdoor units are
connected correctly.
(If the power wire is not connected to L2 phase, no
malfunction display will appear and the compressor
will not work.)
Incorrect interconnections
between units
UF
Check if the refrigerant line piping and the unit wiring
are consistent with each other.
Refrigerant overcharge
E3
F6
UF
Recalculate the required amount of refrigerant from
the piping length and correct the refrigerant charge
level by recovering any excessive refrigerant with a
refrigerant recovery machine.
Insufficient refrigerant
E4
F3
Check if the additional refrigerant charge has been
finished correctly.
Recalculate the required amount of refrigerant from
the piping length and add an adequate amount of
refrigerant.
BS3 RETURN
ON
BS1 MODE
ON
BS1 MODE
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...