English
2
•
The indoor and BS unit should be installed as far away from fluo-
rescent lighting as possible.
Remote controller (wireless kit) transmitting distance can result
shorter than expected in rooms with electronic fluorescent lamps
(inverter or rapid start types).
•
Do not install the air conditioner in the following locations:
(a) where a mineral oil mist or an oil spray or vapor is produced,
for example in a kitchen.
Plastic parts may deteriorate and fall off or result in water leakage.
(b) where corrosive gas, such as sulfurous acid gas, is produced.
Corroding copper pipes or soldered parts may result in refrig-
erant leakage.
(c) near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the con-
trol system and result in a malfunction of the unit.
(d) where flammable gas may leak, where there are carbon fiber
or ignitable dust suspensions in the air, or where volatile flam-
mables such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
(e) Locations where small animals might build nests inside the unit.
If small animals enter and come in contact with electrical parts,
this can cause malfunctions, smoke, and fire.
1-2 Special notice of product
[CLASSIFICATION]
This air conditioner comes under the term “appliances not accessible
to the general public”.
[EMC CHARACTERISTICS]
VRV
III
System is a class A product. In a domestic environment this
product may cause radio interference in which case the user may be
required to take adequate measures.
[REFRIGERANT]
VRV
III
System use R410A refrigerant.
•
The refrigerant R410A requires strict cautions for keeping the sys-
tem clean, dry and tight.
Read the chapter “REFRIGERANT PIPING” carefully and follow
these procedures correctly.
A.Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or
moisture) should be prevented from getting mixed into the system.
B.Tight
Take care to keep the system tight when installing.
R410A does not contain any chlorine, does not destroy the
ozone layer, and does not reduce the earth’s protection against
harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is
released.
•
Since R410A is a mixed refrigerant, the required additional refrig-
erant must be charged in its liquid state. If the refrigerant is
charged in a state of gas, its composition changes and the system
will not work properly.
Limit by the total maximum refrigerant charge
The total maximum refrigerant charge of a VRV
III
system must be
below 100kg, this to be in accordance with CE requirement
(EN60335-2-40 standard).
This means that in case the total maximum refrigerant charge of the
system (factory and additional charge) is equal to or more than
100kg you must divide your multiple outdoor system into smaller
independent systems, each containing less than 100kg refrigerant
charge.
For factory charge, refer to the unit name plate.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type : R410A
GWP
(1)
value : 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
■
the factory refrigerant charge of the product,
■
the additional refrigerant amount charged in the field and
■
+
the total refrigerant charge on the refrigerant charge label
supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the service cover).
(2)
In case of multiple outdoor systems, only 1 label must be adhered,
mentioning the total factory refrigerant charge of all outdoor units
connected on the refrigerant system.
[DESIGN PRESSURE]
Since design pressure is 4.0MPa or 40bar (for R407C units : 3.3MPa
or 33bar), the wall thickness of pipes should be more carefully selected
in accordance with the relevant local and national regulations.
1-3 Disposal requirements
Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local and
national regulations.
2.
INTRODUCTION
•
REYQ-P series are designed for outdoor installation and used for
cooling and heating aplications. The REYQ18-48P system is
multi outdoor unit system, which are only composed of REMQ8-
16P outdoor units. With a multi system combining up to three out-
door units, rated cooling capacity from 50.4kW to 135kW and
rated heating capacity from 56.5kW to 150 kW can be achieved.
•
The BS units that combined with REYQ-P system for changing
the refrigerant flow to indoor units are BSVQ100, 160, 250P type
only. To combine with other type BS unit will cause malfunction.
•
The indoor units that combined with REYQ-P system for air con-
ditioning are Daikin VRV series indoor units that compatible with
R410A. To learn which indoor units are compatible with R410A,
refer to the product catalogs. To combine with other refrigerant
indoor unit will cause malfunction.
2-1 Combination
•
The system name and that independent units are as follows.
〈
The system name
〉
〈
Independent units
〉
REYP18PY1............REMQ10PY1 REMQ8PY1
REYP20PY1............REMQ12PY1 REMQ8PY1
REYP22PY1............REMQ12PY1 REMQ10PY1
REYP24PY1............REMQ12PY1 REMQ12PY1
REYP26PY1............REMQ16PY1 REMQ10PY1
REYP28PY1............REMQ16PY1 REMQ12PY1
REYP30PY1............REMQ16PY1 REMQ14PY1
REYP32PY1............REMQ16PY1 REMQ16PY1
REYP34PY1............REMQ16PY1 REMQ10PY1 REMQ8PY1
REYP36PY1............REMQ16PY1 REMQ12PY1 REMQ8PY1
REYP38PY1............REMQ16PY1 REMQ12PY1 REMQ10PY1
REYP40PY1............REMQ16PY1 REMQ12PY1 REMQ12PY1
REYP42PY1............REMQ16PY1 REMQ16PY1 REMQ10PY1
REYP44PY1............REMQ16PY1 REMQ16PY1 REMQ12PY1
REYP46PY1............REMQ16PY1 REMQ16PY1 REMQ14PY1
REYP48PY1............REMQ16PY1 REMQ16PY1 REMQ16PY1
•
The indoor units can be installed in the following range.
〈
Outdoor unit
〉
〈
Total capacity of indoor units
〉
REYQ18PY1 .......................... 225
~ 585
REYQ20PY1 .......................... 250
~ 650
REYQ22PY1 .......................... 275
~ 715
REYQ24PY1 .......................... 300
~ 780
REYQ26PY1 .......................... 325
~ 845
REYQ28PY1 .......................... 350
~ 910
REYQ30PY1 .......................... 375
~ 975
REYQ32PY1 .......................... 400
~1040
REYQ34PY1 .......................... 425
~1105
REYQ36PY1 .......................... 450
~1170
REYQ38PY1 .......................... 475
~1235
3
5
6
2
1
4
1 factory refrigerant charge
of the product : see unit
name plate
(2)
2 additional refrigerant
amount charged in the field
3 total refrigerant charge
4 Contains fluorinated
greenhouse gases covered
by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and
manifold for charging
Summary of Contents for VRV III REYQ18PY1
Page 23: ...3P201178 5 EM06A072 0702 FS ...