![Daikin VRV III REYQ18PY1 Installation Manual Download Page 18](http://html.mh-extra.com/html/daikin/vrv-iii-reyq18py1/vrv-iii-reyq18py1_installation-manual_502231018.webp)
13
English
•
If there is a possibility that condensation on the shutoff valve
might drip down into the indoor unit through gaps in the insulation
and piping because the outdoor unit is located higher than the
indoor unit, etc., this must be prevented by caulking the connec-
tions, etc.
(Refer to figure 26)
•
The piping lead-out hole lid should be attached after opening a
knock hole.
(Refer to figure 27)
•
If small animals and the like might enter the unit through the pip-
ing lead-out hole, close the hole with blocking material (procured
on site) after completion of “
11. ADDITIONAL REFRIGERANT
CHARGE AND CHECK OPERATION
”.
(Refer to figure 30)
(Refer to figure 26)
1.
Insulation material
2.
Caulking, etc.
(Refer to figure 27)
1.
Piping lead-out hole lid
2.
Open a knock hole at “
”.
3.
Block “
”.
Note
•
After knocking out the holes, we recommend you remove burrs in
the knock holes (
See figure 27
) and paint the edges and areas
around the edges using the repair paint.
10. CHECKING OF DEVICE AND INSTAL-
LATION CONDITIONS
Be sure to check the followings.
For those doing electrical work
1.
Make sure there is no faulty transmission wiring or loosing of a nut.
See “
7-4 Transmission Wiring Connection Procedure
”.
2.
Make sure there is no faulty power wiring or loosing of a nut.
See “
7-5 Power Wiring Connection Procedure
”.
3.
Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular
value in accordance with relevant local and national regulations.
For those doing pipe work
1.
Make sure piping size is correct.
See “
6-1 Selection of piping material and Refrigerant branch-
ing kit
”.
2.
Make sure insulation work is done.
See “
9. PIPE INSULATION”
.
3.
Make sure there is no faulty refrigerant piping.
See “
6. REFRIGERANT PIPING
”.
11. ADDITIONAL REFRIGERANT
CHARGE AND CHECK OPERATION
The outdoor unit is charged with refrigerant when shipped from the factory,
but depending on the size and length of the piping when installed, it may
require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.
11-1 Before working
[About the refrigerant tank]
Check whether the tank has a siphon pipe before charging and place
the tank so that the refrigerant is charged in liquid form.
(See the figure below.)
Note
•
Always use the proper refrigerant (R410A). If charged with the
refrigerant containing an improper material, it may cause an
explosion or accident.
•
R410A is a mixed refrigerant, so charging it as a gas will cause
the refrigerant composition to change, which may prevent normal
operation.
[Shutoff valve operation procedure]
When operating the shutoff valve, follow the procedure instructed below.
Note
•
Do not open the shutoff valve until
“10. CHECKING OF DEVICE
AND INSTALLATION CONDITIONS”
are completed. If the shutoff
valve is left open without turning on the power, it may cause refrig-
erant to buildup in the compressor, leading insulation degradation.
•
Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it
might break the valve body.
•
When using a service port, use the charge hose.
•
After tightening the cap, make sure no refrigerant gas is leaking.
Tightening torque
The sizes of the shutoff valves on each model and the tightening
torque for each size are listed in the table below.
<Size of Shutoff Valve>
(Refer to figure 28)
1.
Service port
2.
Cap
3.
Hex holes
4.
Shaft (valve body)
5.
Seal section
To open
1.
Remove the cap and turn the shaft counterclockwise with the
hexagon wrench (JISB4648).
2.
Turn it until the shaft stops.
3.
Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
To close
1.
Remove the cap and turn the shaft clockwise with the hexagon
wrench (JISB4648).
2.
Securely tighten the valve until the shaft contacts the main body seal.
3.
Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
<Tightening torque>
With siphon pipe
Other tanks
Stand the tank upright and charge.
(The siphon pipe goes all the way inside,
so the tank does not need be put
upside-down charge in liquid form.)
Stand the tank upside-down and charge.
8HP type 10HP type 12HP type 14HP type 16HP type
Liquid pipe
shutoff valve
φ
9.5
φ
12.7
The 12HP type corresponds to
the 12.7-diameter onsite pip-
ing using the accessory pipe.
Suction gas
shutoff valve
φ
25.4
The 8 · 10HP type corresponds to the 22.2-diame-
ter onsite piping using the accessory pipe
The 12-16 HP type corresponds to the 28.6-diam-
eter onsite piping using the accessory pipe.
HP/LP gas
shutoff valve
φ
19.1
The 14 · 16 HP type corresponds to the 22.2-diam-
eter onsite piping using the accessory pipe.
Equalizer pipe
shutoff valve
φ
19.1
Shutoff
valve size
Tightening torque N·m (Turn clockwise to close)
Shaft (valve body)
Cap (valve lid) Service port
φ
9.5
5.4 - 6.6
Hexagonal
wrench
4 mm
13.5 - 16.5
11.5 - 13.9
φ
12.7
8.1 - 9.9
18.0 - 22.0
φ
19.1
27.0 - 33.0
Hexagonal
wrench
8 mm
22.5 - 27.5
φ
25.4
Summary of Contents for VRV III REYQ18PY1
Page 23: ...3P201178 5 EM06A072 0702 FS ...