Troubleshooting by Remote Controller
SiBE37-701
248
Troubleshooting
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
* Refer to Page 215 for Monitor mode.
* Refer to Page 215 for Monitor mode.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Malfunction code indication by outdoor unit
PC board
Malfunctions
Malfunction
code
Description of malfunction
Description of malfunction (PGF)
Remote
controller
PC board malfunction
PC board malfunction
E1
Faulty PC board
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Pe malfunction
E4
Compressor lock
INV compressor lock detected
E5
OC activation
STD1 compressor lock detected
E6
STD2 compressor lock detected
Overload, overcurrent and abnormal
lock of outdoor unit fan motor
Instantaneous overcurrent of 1DC fan motor
E7
1DC fan motor lock detected
Fan 1 IPM faulty protection detected
Instantaneous overcurrent of 2DC fan motor
2DC fan motor lock detected
Fan 2 IPM faulty protection detected
Electronic expansion valve
malfunction
EVM (main)
E9
EVJ (refrigerant charging)
EVT (subcool heat exchanger)
Positioning signal malfunction of
outdoor unit fan motor
1DC fan motor positioning signal
malfunction
H7
2DC fan motor positioning signal
malfunction
Abnormal outdoor temperature
Ta sensor malfunction (short-circuited
or open)
H9
Abnormal discharge pipe temperature Td malfunction
F3
Abnormal heat exchanger temperature Refrigerant overcharged
F6
BS unit electronic expansion valve
malfunction
BS EVH disconnected (Y4E)
F9
BS EVL disconnected (Y5E)
BS EVHS disconnected (Y2E)
BS EVLS disconnected (Y3E)
BS EVSC disconnected (Y1E)
Current sensor malfunction
CT1 sensor malfunction (STD
compressor 1)
J2
CT2 sensor malfunction (STD
compressor 2)
CT sensor malfunction (system)
Discharge pipe temperature sensor
malfunction
Tdi sensor malfunction (R31T)
J3
Tds1 sensor malfunction (short-
circuited) (R32T)
Tds2 sensor malfunction (short-
circuited) (R33T)
Heat exchanger gas temperature
sensor malfunction
Tg sensor malfunction (R2T, R11T)
J4
Suction pipe temperature sensor
malfunction
TsA sensor malfunction (short-
circuited) (R8T, R10T)
J5
Heat exchanger temperature sensor
malfunction
Tb sensor malfunction (R4T, R12T)
J6
Liquid pipe temperature sensor
malfunction
Tsc sensor malfunction (R6T, R14T)
J7
TL sensor malfunction (R9T)
Heat exchanger liquid pipe
temperature sensor malfunction
Tf sensor malfunction (R7T, R15T)
J8
Subcool heat exchanger temperature
sensor malfunction
Tsh sensor malfunction (R5T, R13T)
J9
Discharge pressure sensor malfunction Pc sensor malfunction (S1NPH)
JA
Suction pressure sensor malfunction
Pe sensor malfunction (S1NPL)
JC
INV PC board malfunction
Faulty IPM
Current sensor failure confirmation 1
Current sensor failure confirmation 2
IGBT malfunction
L1
Rise in INV radiation fin temperature
Overheat of INV radiation fin temperature
L4
DC output overcurrent
Instantaneous overcurrent of INV
L5
IGBT malfunction
Electronic thermal
Electronic thermal 1
L8
Electronic thermal 2
Loss of synchronization
Speed degradation after startup
Thunder detected
Stall prevention (time limit)
Stall prevention (increased current)
L9
Stall prevention (startup failure)
Abnormal starting waveform
Loss of synchronization
INV transmission malfunction
INV transmission data malfunction
LC
INV transmission malfunction
k
: ON
l
: Blink
h
: OFF
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...